HMI panel cutout dimensions, by make and series
An HMI panel cutout is the opening in the enclosure door that the terminal drops into, and it is set by the series, not by the screen size. Among the 12.1-inch models listed here alone, the cutout width runs from 269 mm to 434 mm. This reference lists the cutout width and height for 229 models in 32 series from 12 makers, in millimetres and inches, with the bezel that covers the opening, each taken from the maker's own installation document and linked to it. Pick the series, check the number against the current drawing, then cut.
By make
Pick the series
Allen-Bradley
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| PanelView Plus 7 Standard | 4.3", 5.7", 6.5", 9", 10.4", 12.1", 15" | 7 | 117 × 92 mm | 353 × 290 mm |
| PanelView Plus 7 Performance | 6.5", 9", 10.4", 12.1", 15", 19" | 9 | 184 × 142 mm | 457 × 383 mm |
| PanelView 800 | 4", 7", 10" | 3 | 119 × 99 mm | 269 × 206 mm |
| PanelView 5510 | 6.5", 7", 9", 10.1", 10.4", 12.1", 15", 15.6", 18.5", 19", 21.5" | 16 | 184 × 142 mm | 457 × 383 mm |
| PanelView 5310 | 6", 7", 9", 10.4", 12.1" | 5 | 156 × 123 mm | 312 × 218 mm |
Siemens
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| SIMATIC HMI Basic Panels (2nd Generation) | 4.3", 7", 9", 12" | 4 | 123 × 99 mm | 310 × 221 mm |
| SIMATIC HMI Comfort Panels | 4.3", 7", 9", 12.1", 15.4", 18.5", 21.5" | 12 | 122 × 98 mm | 542 × 362 mm |
| SIMATIC HMI Unified Comfort Panels | 7", 10.1", 12.1", 15.6", 18.5", 21.5" | 6 | 197 × 141 mm | 513 × 315 mm |
AutomationDirect
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| C-more EA9 | 6", 7", 8", 10", 12", 15" | 7 | 189.5 × 140 mm | 379.2 × 286.3 mm |
| C-more CM5 | 4", 7", 10", 12", 15", 22" | 6 | 102.1 × 70.1 mm | 526.8 × 344.7 mm |
Red Lion
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| CR3000 | 4.3", 7", 10.4", 15" | 4 | 119.1 × 93 mm | 340.1 × 265.7 mm |
| CR1000 | 4.3", 7", 10.4" | 3 | 119.1 × 93 mm | 259.1 × 201.4 mm |
| Graphite | 7", 9", 10", 12", 15" | 5 | 179.3 × 123.7 mm | 340.1 × 265.6 mm |
Pro-face
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| SP5000 Series | 7", 10.1", 10.4", 12.1", 15", 15.6", 18.5" | 10 | 190 × 135 mm | 465 × 319 mm |
| ST6000 Series | 4.3", 5.7", 7", 10.1", 10.4", 12.1", 15.6" | 7 | 118.5 × 92.5 mm | 394 × 250 mm |
| GP4000 Series | 3.5", 5.7", 7", 7.5", 10.4", 12.1" | 7 | 118.5 × 92.5 mm | 301.5 × 227.5 mm |
Schneider Electric
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| Harmony GTO | 3.5", 5.7", 7", 7.5", 10.4", 12.1" | 9 | 118.5 × 92.5 mm | 340.5 × 266.5 mm |
| Harmony ST6 | 4.3", 7", 10.1", 12.1", 15.6" | 5 | 118.5 × 92.5 mm | 394 × 250 mm |
| Harmony GTU | 7", 10.1", 10.4", 12.1", 15", 15.6", 18.5" | 8 | 190 × 135 mm | 465 × 319 mm |
Weintek
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| cMT X Series | 7", 9.7", 10.1", 15", 15.6" | 8 | 192 × 138 mm | 352 × 279 mm |
| MT8000 iP and iE Series | 5", 7", 10.1" | 6 | 119 × 93 mm | 260 × 202 mm |
Mitsubishi Electric
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| GOT SIMPLE GS21 and GS25 | 7", 10", 12.1" | 3 | 191 × 137 mm | 290.5 × 210.5 mm |
| GOT2000 GT27 | 5.7", 8.4", 10.4", 12.1", 15" | 5 | 153 × 121 mm | 383.5 × 282.5 mm |
| GOT2000 GT25 | 5.7", 7", 8.4", 10.1", 10.4", 12.1" | 11 | 153 × 121 mm | 302 × 228 mm |
| GOT2000 GT21 | 3.8", 4.3", 4.5", 5.7", 7" | 5 | 105 × 66 mm | 180.5 × 133.5 mm |
Omron
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| NB Series | 3.5", 5.6", 7", 10.1" | 4 | 119 × 93 mm | 258 × 200 mm |
| NA5 Series | 7", 9", 12.1", 15.4" | 4 | 197 × 141 mm | 392 × 268 mm |
Delta
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| DOP-100 Series | 4.3", 5.6", 7", 8", 10", 10.1", 10.4", 12", 15" | 18 | 118.8 × 92.8 mm | 372.4 × 283.7 mm |
Beijer Electronics
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| X2 base | 5", 7", 10" | 3 | 160.7 × 93 mm | 274.3 × 176.6 mm |
| X2 base v2 | 5", 7", 10.1" | 4 | 161 × 93 mm | 275 × 177 mm |
| X2 pro | 7", 10.1", 12.1", 15.4" | 5 | 189 × 128 mm | 394 × 270 mm |
Maple Systems
| Series | Screen sizes | Models | Smallest cutout, W × H | Largest cutout, W × H |
|---|---|---|---|---|
| HMI5000 and cMT Series | 4.3", 7", 9.7", 10.1", 12.1", 15", 15.6", 21.5" | 20 | 119 × 93 mm | 532 × 340 mm |
By screen size
The same screen, a different opening
| Screen | Series | Model | Cutout W × H, mm | Cutout W × H, in | Bezel W × H |
|---|---|---|---|---|---|
| 3.5" | Pro-face GP4000 Series | GP-4201T / GP-4203T / GP-4201TW | 118.5 × 92.5 mm | 4.67 × 3.64 in | 132 × 106 mm |
| 3.5" | Schneider Electric Harmony GTO | HMIGTO1300 / HMIGTO1310 | 118.5 × 92.5 mm | 4.67 × 3.64 in | 132 × 106 mm |
| 3.5" | Omron NB Series | NB3Q-TW00B(-V1) / NB3Q-TW01B(-V1) | 119 × 93 mm | 4.69 × 3.66 in | 129.8 × 103.8 mm |
| 3.8" | Mitsubishi Electric GOT2000 GT21 | GT2103-P | 105 × 66 mm | 4.13 × 2.60 in | 113 × 74 mm |
| 4" | AutomationDirect C-more CM5 | CM5-T4W | 102.1 × 70.1 mm | 4.02 × 2.76 in | 120.9 × 88.3 mm |
| 4" | Allen-Bradley PanelView 800 | 2711R-T4T | 119 × 99 mm | 4.69 × 3.90 in | 138 × 116 mm |
| 4.3" | Allen-Bradley PanelView Plus 7 Standard | 4.3 in. (2711P-T4W21D8S, 2711P-T4W22D8S) | 117 × 92 mm | 4.61 × 3.62 in | 135 × 110 mm |
| 4.3" | Mitsubishi Electric GOT2000 GT21 | GT2104-R | 118 × 92 mm | 4.65 × 3.62 in | 128 × 102 mm |
| 4.3" | Pro-face ST6000 Series | ST-6200WA | 118.5 × 92.5 mm | 4.67 × 3.64 in | 134.5 × 108.5 mm |
| 4.3" | Schneider Electric Harmony ST6 | HMIST6200 | 118.5 × 92.5 mm | 4.67 × 3.64 in | 134.5 × 108.5 mm |
| 4.3" | Delta DOP-100 Series | DOP-103WQ | 118.8 × 92.8 mm | 4.68 × 3.65 in | 137 × 103 mm |
| 4.3" | Delta DOP-100 Series | DOP-103BQ | 118.8 × 92.8 mm | 4.68 × 3.65 in | 137 × 103 mm |
| 4.3" | Maple Systems HMI5000 and cMT Series | HMI5040B | 119 × 93 mm | 4.69 × 3.66 in | 128 × 102 mm |
| 4.3" | Maple Systems HMI5000 and cMT Series | cMT2058XHW | 119 × 93 mm | 4.69 × 3.66 in | 128 × 102 mm |
| 4.3" | Maple Systems HMI5000 and cMT Series | HMI5043Lv2, HMI5043LBv2 | 119 × 93 mm | 4.69 × 3.66 in | not printed |
| 4.3" | Maple Systems HMI5000 and cMT Series | cMT2058XH | 119 × 93 mm | 4.69 × 3.66 in | 128 × 102 mm |
| 4.3" | Red Lion CR1000 | CR1000 04000 | 119.1 × 93 mm | 4.69 × 3.66 in | not printed |
| 4.3" | Red Lion CR3000 | CR3000 4 inch | 119.1 × 93 mm | 4.69 × 3.66 in | 130.7 × 104.7 mm |
| 4.3" | Siemens SIMATIC HMI Comfort Panels | KTP400 Comfort | 122 × 98 mm | 4.80 × 3.86 in | 140 × 116 mm |
| 4.3" | Siemens SIMATIC HMI Basic Panels (2nd Generation) | KTP400 Basic | 123 × 99 mm | 4.84 × 3.90 in | 140 × 116 mm |
| 4.3" | Siemens SIMATIC HMI Comfort Panels | KP400 Comfort | 135 × 171 mm | 5.31 × 6.73 in | not printed |
| 4.5" | Mitsubishi Electric GOT2000 GT21 | GT2104-P | 137 × 66 mm | 5.39 × 2.60 in | 145 × 76 mm |
| 5" | Weintek MT8000 iP and iE Series | MT8051iP1 | 119 × 93 mm | 4.69 × 3.66 in | 128 × 102 mm |
| 5" | Beijer Electronics X2 base | X2 base 5 | 160.7 × 93 mm | 6.33 × 3.66 in | 170.4 × 106.8 mm |
| 5" | Beijer Electronics X2 base v2 | X2 base 5 v2 | 161 × 93 mm | 6.34 × 3.66 in | 172 × 109 mm |
| 5.6" | Omron NB Series | NB5Q-TW00B(-V1) / NB5Q-TW01B(-V1) | 172.4 × 131 mm | 6.79 × 5.16 in | 184 × 142 mm |
| 5.6" | Delta DOP-100 Series | DOP-105CQ | 172.4 × 132.4 mm | 6.79 × 5.21 in | 184 × 144 mm |
| 5.7" | Mitsubishi Electric GOT2000 GT21 | GT2105-Q | 153 × 121 mm | 6.02 × 4.76 in | 164 × 135 mm |
| 5.7" | Mitsubishi Electric GOT2000 GT25 | GT2505-V | 153 × 121 mm | 6.02 × 4.76 in | 164 × 139 mm |
| 5.7" | Mitsubishi Electric GOT2000 GT27 | GT2705-V | 153 × 121 mm | 6.02 × 4.76 in | 167 × 139 mm |
| 5.7" | Allen-Bradley PanelView Plus 7 Standard | 5.7 in. (2711P-T6C21D8S, 2711P-T6C22D8S) | 156 × 123 mm | 6.14 × 4.84 in | 176 × 152 mm |
| 5.7" | Pro-face GP4000 Series | GP-4301T / GP-4301TW / GP-4303T | 156 × 123.5 mm | 6.14 × 4.86 in | 169.5 × 137 mm |
| 5.7" | Pro-face ST6000 Series | ST-6300TA | 156 × 123.5 mm | 6.14 × 4.86 in | 169.5 × 137 mm |
| 5.7" | Schneider Electric Harmony GTO | HMIGTO2300 / HMIGTO2310 | 156 × 123.5 mm | 6.14 × 4.86 in | 169.5 × 137 mm |
| 5.7" | Schneider Electric Harmony GTO | HMIGTO2315 | 195 × 162.5 mm | 7.68 × 6.40 in | 213.5 × 181 mm |
| 6" | Allen-Bradley PanelView 5310 | 6 in. (2713P-T6CD1) | 156 × 123 mm | 6.14 × 4.84 in | 186 × 153 mm |
| 6" | AutomationDirect C-more EA9 | EA9-T6CL / EA9-T6CL-R | 189.5 × 140 mm | 7.46 × 5.51 in | not printed |
| 6.5" | Allen-Bradley PanelView 5510 | 6.5 in. resistive touch | 184 × 142 mm | 7.24 × 5.59 in | 212 × 170 mm |
| 6.5" | Allen-Bradley PanelView Plus 7 Performance | 6.5 in. touch (2711P-T7C22D9P) | 184 × 142 mm | 7.24 × 5.59 in | 212 × 170 mm |
| 6.5" | Allen-Bradley PanelView Plus 7 Standard | 6.5 in. (2711P-T7C21D8S, 2711P-T7C22D8S) | 184 × 142 mm | 7.24 × 5.59 in | 212 × 170 mm |
| 6.5" | Allen-Bradley PanelView 5510 | 6.5 in. keypad and resistive touch | 237 × 142 mm | 9.33 × 5.59 in | 285 × 179 mm |
| 6.5" | Allen-Bradley PanelView Plus 7 Performance | 6.5 in. keypad and touch (2711P-B7C22D9P) | 237 × 142 mm | 9.33 × 5.59 in | 285 × 179 mm |
| 7" | Red Lion Graphite | G07 | 179.3 × 123.7 mm | 7.06 × 4.87 in | 195.5 × 139.9 mm |
| 7" | Red Lion CR1000 | CR1000 07000 | 179.3 × 123.7 mm | 7.06 × 4.87 in | not printed |
| 7" | Red Lion CR3000 | CR3000 7 inch | 179.3 × 123.7 mm | 7.06 × 4.87 in | 194 × 138 mm |
| 7" | Allen-Bradley PanelView 800 | 2711R-T7T | 179 × 125 mm | 7.05 × 4.92 in | 197 × 144 mm |
| 7" | Delta DOP-100 Series | DOP-107EG | 172.4 × 132.4 mm | 6.79 × 5.21 in | 184 × 144 mm |
| 7" | Delta DOP-100 Series | DOP-107WV | 186.8 × 126.8 mm | 7.35 × 4.99 in | 196 × 136 mm |
| 7" | Mitsubishi Electric GOT2000 GT21 | GT2107-W | 180.5 × 133.5 mm | 7.11 × 5.26 in | 189 × 142 mm |
| 7" | Mitsubishi Electric GOT2000 GT25 | GT2507-W | 180.5 × 133.5 mm | 7.11 × 5.26 in | 189 × 142 mm |
| 7" | Beijer Electronics X2 pro | X2 pro 7 | 189 × 128 mm | 7.44 × 5.04 in | 204 × 143 mm |
| 7" | Beijer Electronics X2 pro | X2 pro 7 2eth | 189 × 128 mm | 7.44 × 5.04 in | 204 × 143 mm |
| 7" | Beijer Electronics X2 base | X2 base 7 | 185.8 × 135.8 mm | 7.31 × 5.35 in | 196 × 146 mm |
| 7" | Beijer Electronics X2 base v2 | X2 base 7 v2 | 186 × 136 mm | 7.32 × 5.35 in | 202 × 152 mm |
| 7" | Pro-face SP5000 Series | SP-5400WA | 190 × 135 mm | 7.48 × 5.31 in | 203.6 × 148.6 mm |
| 7" | Pro-face ST6000 Series | ST-6400WA | 190 × 135 mm | 7.48 × 5.31 in | 208 × 153 mm |
| 7" | Schneider Electric Harmony GTU | HMIDT351 | 190 × 135 mm | 7.48 × 5.31 in | 203.6 × 148.6 mm |
| 7" | Schneider Electric Harmony ST6 | HMIST6400 | 190 × 135 mm | 7.48 × 5.31 in | 208 × 153 mm |
| 7" | Mitsubishi Electric GOT SIMPLE GS21 and GS25 | GS2107-WTBD / GS2107-WTBD-N | 191 × 137 mm | 7.52 × 5.39 in | 206 × 155 mm |
| 7" | Omron NB Series | NB7W-TW00B(-V1) / NB7W-TW01B(-V1) | 191 × 137 mm | 7.52 × 5.39 in | 202 × 148 mm |
| 7" | Maple Systems HMI5000 and cMT Series | HMI5070B | 192 × 138 mm | 7.56 × 5.43 in | 200.4 × 146.5 mm |
| 7" | Maple Systems HMI5000 and cMT Series | cMT2078X | 192 × 138 mm | 7.56 × 5.43 in | 200.3 × 146.3 mm |
| 7" | Maple Systems HMI5000 and cMT Series | cMT3072XH3 | 192 × 138 mm | 7.56 × 5.43 in | 200.4 × 146.5 mm |
| 7" | Maple Systems HMI5000 and cMT Series | cMT3072XP | 192 × 138 mm | 7.56 × 5.43 in | 200.3 × 146.3 mm |
| 7" | Weintek cMT X Series | cMT2078X | 192 × 138 mm | 7.56 × 5.43 in | 200.3 × 146.3 mm |
| 7" | Weintek cMT X Series | cMT3072X | 192 × 138 mm | 7.56 × 5.43 in | 200.3 × 146.3 mm |
| 7" | Weintek cMT X Series | cMT3072XH | 192 × 138 mm | 7.56 × 5.43 in | 200.3 × 146.3 mm |
| 7" | Weintek cMT X Series | cMT3072XH2 | 192 × 138 mm | 7.56 × 5.43 in | 200.3 × 146.3 mm |
| 7" | Weintek MT8000 iP and iE Series | MT8071iP1 | 192 × 138 mm | 7.56 × 5.43 in | 200.4 × 146.5 mm |
| 7" | Weintek MT8000 iP and iE Series | MT8071iP2 | 192 × 138 mm | 7.56 × 5.43 in | 200.4 × 146.5 mm |
| 7" | Weintek MT8000 iP and iE Series | MT8071iE1 | 192 × 138 mm | 7.56 × 5.43 in | 200.3 × 146.3 mm |
| 7" | AutomationDirect C-more CM5 | CM5-T7W | 189.5 × 140 mm | 7.46 × 5.51 in | 205.2 × 155.8 mm |
| 7" | AutomationDirect C-more EA9 | EA9-T7CL / EA9-T7CL-R | 189.5 × 140 mm | 7.46 × 5.51 in | not printed |
| 7" | Allen-Bradley PanelView 5510 | 7 in. capacitive touch | 196 × 139.5 mm | 7.72 × 5.49 in | 207 × 150.6 mm |
| 7" | Mitsubishi Electric GOT2000 GT25 | GT2507T-W | 197 × 141 mm | 7.76 × 5.55 in | 214 × 158 mm |
| 7" | Omron NA5 Series | NA5-7W | 197 × 141 mm | 7.76 × 5.55 in | 236 × 165 mm |
| 7" | Siemens SIMATIC HMI Basic Panels (2nd Generation) | KTP700 Basic | 197 × 141 mm | 7.76 × 5.55 in | 214 × 158 mm |
| 7" | Siemens SIMATIC HMI Comfort Panels | TP700 Comfort | 197 × 141 mm | 7.76 × 5.55 in | 214 × 158 mm |
| 7" | Siemens SIMATIC HMI Unified Comfort Panels | MTP700 Unified Comfort | 197 × 141 mm | 7.76 × 5.55 in | 214 × 158 mm |
| 7" | Delta DOP-100 Series | DOP-107BV | 196 × 142.9 mm | 7.72 × 5.63 in | 215 × 161 mm |
| 7" | Delta DOP-100 Series | DOP-107DV | 196 × 142.9 mm | 7.72 × 5.63 in | 215 × 161 mm |
| 7" | Delta DOP-100 Series | DOP-107CV | 196.9 × 142.9 mm | 7.75 × 5.63 in | 215 × 161 mm |
| 7" | Delta DOP-100 Series | DOP-107EV | 196.9 × 142.9 mm | 7.75 × 5.63 in | 215 × 161 mm |
| 7" | Delta DOP-100 Series | DOP-107IV | 196.9 × 142.9 mm | 7.75 × 5.63 in | 215 × 161 mm |
| 7" | Allen-Bradley PanelView 5310 | 7 in. (2713P-T7WD1) | 210 × 150 mm | 8.27 × 5.91 in | 237 × 178 mm |
| 7" | Allen-Bradley PanelView 5510 | 7 in. resistive touch (2715P-T7WD) | 210 × 150 mm | 8.27 × 5.91 in | 237 × 178 mm |
| 7" | Pro-face GP4000 Series | GP-4401WW | 204.5 × 159.5 mm | 8.05 × 6.28 in | 218 × 173 mm |
| 7" | Schneider Electric Harmony GTO | HMIGTO3510 | 204.5 × 159.5 mm | 8.05 × 6.28 in | 218 × 173 mm |
| 7" | Siemens SIMATIC HMI Comfort Panels | KP700 Comfort | 281 × 177 mm | 11.06 × 6.97 in | not printed |
| 7.5" | Pro-face GP4000 Series | GP-4401T | 204.5 × 159.5 mm | 8.05 × 6.28 in | 218 × 173 mm |
| 7.5" | Schneider Electric Harmony GTO | HMIGTO4310 | 204.5 × 159.5 mm | 8.05 × 6.28 in | 218 × 173 mm |
| 8" | Delta DOP-100 Series | DOP-108IG | 219.4 × 166.5 mm | 8.64 × 6.56 in | 227.1 × 174.1 mm |
| 8" | AutomationDirect C-more EA9 | EA9-T8CL | 235 × 179.6 mm | 9.25 × 7.07 in | not printed |
| 8.4" | Mitsubishi Electric GOT2000 GT25 | GT2508F-V (open frame) | 194 × 158 mm | 7.64 × 6.22 in | not printed |
| 8.4" | Mitsubishi Electric GOT2000 GT25 | GT2508-V | 227 × 176 mm | 8.94 × 6.93 in | 241 × 194 mm |
| 8.4" | Mitsubishi Electric GOT2000 GT27 | GT2708-S / GT2708-V | 227 × 176 mm | 8.94 × 6.93 in | 241 × 194 mm |
| 9" | Red Lion Graphite | G09 | 239.3 × 148.1 mm | 9.42 × 5.83 in | 255.6 × 164.4 mm |
| 9" | Allen-Bradley PanelView 5310 | 9 in. (2713P-T9WD1) | 252 × 162 mm | 9.92 × 6.38 in | 280 × 190 mm |
| 9" | Allen-Bradley PanelView 5510 | 9 in. resistive touch | 252 × 162 mm | 9.92 × 6.38 in | 280 × 190 mm |
| 9" | Allen-Bradley PanelView Plus 7 Performance | 9 in. touch (2711P-T9W22D9P) | 252 × 162 mm | 9.92 × 6.38 in | 280 × 190 mm |
| 9" | Allen-Bradley PanelView Plus 7 Standard | 9 in. (2711P-T9W21D8S, 2711P-T9W22D8S) | 252 × 162 mm | 9.92 × 6.38 in | 280 × 190 mm |
| 9" | Siemens SIMATIC HMI Comfort Panels | TP900 Comfort | 250 × 166 mm | 9.84 × 6.54 in | 274 × 190 mm |
| 9" | Siemens SIMATIC HMI Basic Panels (2nd Generation) | KTP900 Basic | 251 × 166 mm | 9.88 × 6.54 in | 267 × 182 mm |
| 9" | Omron NA5 Series | NA5-9W | 261 × 166 mm | 10.28 × 6.54 in | 290 × 190 mm |
| 9" | Siemens SIMATIC HMI Comfort Panels | KP900 Comfort | 338 × 206 mm | 13.31 × 8.11 in | not printed |
| 9.7" | Maple Systems HMI5000 and cMT Series | cMT3092Xv2 | 250 × 192 mm | 9.84 × 7.56 in | 260.6 × 203.1 mm |
| 9.7" | Weintek cMT X Series | cMT3092X | 250 × 192 mm | 9.84 × 7.56 in | 260.6 × 203.1 mm |
| 10" | AutomationDirect C-more CM5 | CM5-T10W | 235 × 179.6 mm | 9.25 × 7.07 in | 268 × 195.9 mm |
| 10" | AutomationDirect C-more EA9 | EA9-T10WCL | 235 × 179.6 mm | 9.25 × 7.07 in | not printed |
| 10" | Beijer Electronics X2 base | X2 base 10 | 274.3 × 176.6 mm | 10.80 × 6.95 in | 284.3 × 186.6 mm |
| 10" | Delta DOP-100 Series | DOP-110CS | 261.3 × 189.3 mm | 10.29 × 7.45 in | 272 × 200 mm |
| 10" | Mitsubishi Electric GOT SIMPLE GS21 and GS25 | GS2110-WTBD / GS2110-WTBD-N | 258 × 200 mm | 10.16 × 7.87 in | 272 × 214 mm |
| 10" | Red Lion Graphite | G10 | 259 × 201.4 mm | 10.20 × 7.93 in | 275.2 × 217.7 mm |
| 10" | Allen-Bradley PanelView 800 | 2711R-T10T | 269 × 206 mm | 10.59 × 8.11 in | 287 × 225 mm |
| 10" | AutomationDirect C-more EA9 | EA9-T10CL | 302.3 × 226.3 mm | 11.90 × 8.91 in | not printed |
| 10.1" | Delta DOP-100 Series | DOP-110WS | 255.5 × 170.5 mm | 10.06 × 6.71 in | 270 × 180.9 mm |
| 10.1" | Allen-Bradley PanelView 5510 | 10.1 in. capacitive touch | 255.5 × 174 mm | 10.06 × 6.85 in | 269.5 × 187.9 mm |
| 10.1" | Mitsubishi Electric GOT2000 GT25 | GT2510-WX | 243.5 × 185.5 mm | 9.59 × 7.30 in | 252 × 194 mm |
| 10.1" | Maple Systems HMI5000 and cMT Series | cMT3108XH | 255 × 185 mm | 10.04 × 7.28 in | 266 × 196 mm |
| 10.1" | Maple Systems HMI5000 and cMT Series | cMT3108XP | 255 × 185 mm | 10.04 × 7.28 in | 266 × 196 mm |
| 10.1" | Pro-face SP5000 Series | SP-5500WA | 255 × 185 mm | 10.04 × 7.28 in | 268.5 × 198.5 mm |
| 10.1" | Pro-face ST6000 Series | ST-6500WA | 255 × 185 mm | 10.04 × 7.28 in | 273 × 203 mm |
| 10.1" | Schneider Electric Harmony GTU | HMIDT551 | 255 × 185 mm | 10.04 × 7.28 in | 268.5 × 198.5 mm |
| 10.1" | Schneider Electric Harmony ST6 | HMIST6500 | 255 × 185 mm | 10.04 × 7.28 in | 273 × 203 mm |
| 10.1" | Beijer Electronics X2 base v2 | X2 base 10 v2 | 275 × 177 mm | 10.83 × 6.97 in | 290 × 193 mm |
| 10.1" | Beijer Electronics X2 base v2 | X2 base 10 v2 HP | 275 × 177 mm | 10.83 × 6.97 in | 290 × 193 mm |
| 10.1" | Beijer Electronics X2 pro | X2 pro 10 | 275 × 177 mm | 10.83 × 6.97 in | 292 × 194 mm |
| 10.1" | Delta DOP-100 Series | DOP-110IS | 261.3 × 189.3 mm | 10.29 × 7.45 in | 272.6 × 200.6 mm |
| 10.1" | Siemens SIMATIC HMI Unified Comfort Panels | MTP1000 Unified Comfort | 264 × 189 mm | 10.39 × 7.44 in | 280 × 205 mm |
| 10.1" | Omron NB Series | NB10W-TW01B(-V1) | 258 × 200 mm | 10.16 × 7.87 in | 268.8 × 210.8 mm |
| 10.1" | Maple Systems HMI5000 and cMT Series | HMI5100Bv3 | 260 × 202 mm | 10.24 × 7.95 in | 271 × 213 mm |
| 10.1" | Maple Systems HMI5000 and cMT Series | cMT2108X2 | 260 × 202 mm | 10.24 × 7.95 in | 271 × 213 mm |
| 10.1" | Maple Systems HMI5000 and cMT Series | cMT3102XV2R | 260 × 202 mm | 10.24 × 7.95 in | 271 × 213 mm |
| 10.1" | Weintek cMT X Series | cMT3102X | 260 × 202 mm | 10.24 × 7.95 in | 271 × 213 mm |
| 10.1" | Weintek MT8000 iP and iE Series | MT8102iP1 | 260 × 202 mm | 10.24 × 7.95 in | 271 × 213 mm |
| 10.1" | Weintek MT8000 iP and iE Series | MT8102iE1 | 260 × 202 mm | 10.24 × 7.95 in | 271 × 213 mm |
| 10.4" | Mitsubishi Electric GOT2000 GT25 | GT2510F-V (open frame) | 234 × 187 mm | 9.21 × 7.36 in | not printed |
| 10.4" | Pro-face GP4000 Series | GP-4501T / GP-4503T / GP-4521T | 259 × 201 mm | 10.20 × 7.91 in | 272.5 × 214.5 mm |
| 10.4" | Pro-face SP5000 Series | SP-5500TP | 259 × 201 mm | 10.20 × 7.91 in | 272.5 × 214.5 mm |
| 10.4" | Schneider Electric Harmony GTO | HMIGTO5310 | 259 × 201 mm | 10.20 × 7.91 in | 272.5 × 214.5 mm |
| 10.4" | Schneider Electric Harmony GTU | HMIDT542 | 259 × 201 mm | 10.20 × 7.91 in | 272.5 × 214.5 mm |
| 10.4" | Red Lion CR1000 | CR1000 10000 | 259.1 × 201.4 mm | 10.20 × 7.93 in | 273.7 × 216 mm |
| 10.4" | Red Lion CR3000 | CR3000 10 inch | 259.1 × 201.4 mm | 10.20 × 7.93 in | 273.7 × 216 mm |
| 10.4" | Mitsubishi Electric GOT2000 GT25 | GT2510-V | 289 × 200 mm | 11.38 × 7.87 in | 303 × 218 mm |
| 10.4" | Mitsubishi Electric GOT2000 GT27 | GT2710-S / GT2710-V | 289 × 200 mm | 11.38 × 7.87 in | 303 × 218 mm |
| 10.4" | Delta DOP-100 Series | DOP-110CG | 285.2 × 210.2 mm | 11.23 × 8.28 in | 299 × 224 mm |
| 10.4" | Delta DOP-100 Series | DOP-110IG | 285.2 × 210.2 mm | 11.23 × 8.28 in | 299 × 224 mm |
| 10.4" | Allen-Bradley PanelView 5310 | 10.4 in. (2713P-T10CD1) | 269 × 224 mm | 10.59 × 8.82 in | 297 × 252 mm |
| 10.4" | Allen-Bradley PanelView 5510 | 10.4 in. resistive touch | 269 × 224 mm | 10.59 × 8.82 in | 297 × 252 mm |
| 10.4" | Allen-Bradley PanelView Plus 7 Performance | 10.4 in. touch (2711P-T10C22D9P) | 269 × 224 mm | 10.59 × 8.82 in | 297 × 252 mm |
| 10.4" | Allen-Bradley PanelView Plus 7 Standard | 10.4 in. (2711P-T10C21D8S, 2711P-T10C22D8S) | 269 × 224 mm | 10.59 × 8.82 in | 297 × 252 mm |
| 10.4" | Pro-face GP4000 Series | GP-4501TW | 301.5 × 227.5 mm | 11.87 × 8.96 in | 315 × 241 mm |
| 10.4" | Pro-face ST6000 Series | ST-6500TA | 301.5 × 227.5 mm | 11.87 × 8.96 in | 315 × 241 mm |
| 10.4" | Schneider Electric Harmony GTO | HMIGTO5315 | 298 × 240 mm | 11.73 × 9.45 in | 316.5 × 258.5 mm |
| 10.4" | Allen-Bradley PanelView 5510 | 10.4 in. keypad and resistive touch | 335 × 224 mm | 13.19 × 8.82 in | 385 × 252 mm |
| 10.4" | Allen-Bradley PanelView Plus 7 Performance | 10.4 in. keypad and touch (2711P-B10C22D9P) | 335 × 224 mm | 13.19 × 8.82 in | 385 × 252 mm |
| 12" | Red Lion Graphite | G12 | 291 × 192 mm | 11.46 × 7.56 in | 307.3 × 208.3 mm |
| 12" | Siemens SIMATIC HMI Basic Panels (2nd Generation) | KTP1200 Basic | 310 × 221 mm | 12.20 × 8.70 in | 330 × 245 mm |
| 12" | AutomationDirect C-more CM5 | CM5-T12W | 302.5 × 226.6 mm | 11.91 × 8.92 in | 318.8 × 242.9 mm |
| 12" | Delta DOP-100 Series | DOP-112WX / DOP-112MX | 302.7 × 228.7 mm | 11.92 × 9.00 in | 317.4 × 246.4 mm |
| 12" | AutomationDirect C-more EA9 | EA9-T12CL | 319.3 × 259.6 mm | 12.57 × 10.22 in | not printed |
| 12.1" | Mitsubishi Electric GOT2000 GT25 | GT2512F-S (open frame) | 269 × 214 mm | 10.59 × 8.43 in | not printed |
| 12.1" | Allen-Bradley PanelView 5510 | 12.1 in. capacitive touch | 301 × 203 mm | 11.85 × 7.99 in | 315 × 217 mm |
| 12.1" | Mitsubishi Electric GOT SIMPLE GS21 and GS25 | GS2512-WXTBD | 290.5 × 210.5 mm | 11.44 × 8.29 in | 299 × 219 mm |
| 12.1" | Mitsubishi Electric GOT2000 GT25 | GT2512-WX | 290.5 × 210.5 mm | 11.44 × 8.29 in | 299 × 219 mm |
| 12.1" | Pro-face SP5000 Series | SP-5600WA | 295 × 217 mm | 11.61 × 8.54 in | 308.5 × 230.5 mm |
| 12.1" | Pro-face ST6000 Series | ST-6600WA | 295 × 217 mm | 11.61 × 8.54 in | 313 × 235 mm |
| 12.1" | Schneider Electric Harmony GTU | HMIDT651 | 295 × 217 mm | 11.61 × 8.54 in | 308.5 × 230.5 mm |
| 12.1" | Schneider Electric Harmony ST6 | HMIST6600 | 295 × 217 mm | 11.61 × 8.54 in | 313 × 235 mm |
| 12.1" | Allen-Bradley PanelView 5310 | 12.1 in. (2713P-T12WD1) | 312 × 218 mm | 12.28 × 8.58 in | 340 × 246 mm |
| 12.1" | Allen-Bradley PanelView 5510 | 12.1 in. resistive touch | 312 × 218 mm | 12.28 × 8.58 in | 340 × 246 mm |
| 12.1" | Allen-Bradley PanelView Plus 7 Performance | 12.1 in. touch (2711P-T12W22D9P) | 312 × 218 mm | 12.28 × 8.58 in | 340 × 246 mm |
| 12.1" | Allen-Bradley PanelView Plus 7 Standard | 12.1 in. (2711P-T12W21D8S, 2711P-T12W22D8S) | 312 × 218 mm | 12.28 × 8.58 in | 340 × 246 mm |
| 12.1" | Omron NA5 Series | NA5-12W | 310 × 221 mm | 12.20 × 8.70 in | 340 × 244 mm |
| 12.1" | Siemens SIMATIC HMI Comfort Panels | TP1200 Comfort | 310 × 221 mm | 12.20 × 8.70 in | 330 × 241 mm |
| 12.1" | Siemens SIMATIC HMI Unified Comfort Panels | MTP1200 Unified Comfort | 310 × 221 mm | 12.20 × 8.70 in | 326 × 237 mm |
| 12.1" | Pro-face GP4000 Series | GP-4601T / GP-4603T / GP-4621T | 301.5 × 227.5 mm | 11.87 × 8.96 in | 315 × 241 mm |
| 12.1" | Pro-face SP5000 Series | SP-5600TA | 301.5 × 227.5 mm | 11.87 × 8.96 in | 315 × 241 mm |
| 12.1" | Pro-face SP5000 Series | SP-5600TP | 301.5 × 227.5 mm | 11.87 × 8.96 in | 315 × 241 mm |
| 12.1" | Pro-face SP5000 Series | SP-5660TP | 301.5 × 227.5 mm | 11.87 × 8.96 in | not printed |
| 12.1" | Schneider Electric Harmony GTO | HMIGTO6310 | 301.5 × 227.5 mm | 11.87 × 8.96 in | 315 × 241 mm |
| 12.1" | Schneider Electric Harmony GTU | HMIDT642 / HMIDT643 | 301.5 × 227.5 mm | 11.87 × 8.96 in | 315 × 241 mm |
| 12.1" | Mitsubishi Electric GOT2000 GT25 | GT2512-S | 302 × 228 mm | 11.89 × 8.98 in | 316 × 246 mm |
| 12.1" | Mitsubishi Electric GOT2000 GT27 | GT2712-S | 302 × 228 mm | 11.89 × 8.98 in | 316 × 246 mm |
| 12.1" | Maple Systems HMI5000 and cMT Series | cMT2128X | 305 × 231 mm | 12.01 × 9.09 in | 317 × 243 mm |
| 12.1" | Beijer Electronics X2 pro | X2 pro 12 | 324 × 226 mm | 12.76 × 8.90 in | 340 × 242 mm |
| 12.1" | Schneider Electric Harmony GTO | HMIGTO6315 | 340.5 × 266.5 mm | 13.41 × 10.49 in | 359 × 285 mm |
| 12.1" | Siemens SIMATIC HMI Comfort Panels | KP1200 Comfort | 434 × 268 mm | 17.09 × 10.55 in | not printed |
| 15" | Red Lion Graphite | G15 | 340.1 × 265.6 mm | 13.39 × 10.46 in | 356.3 × 281.8 mm |
| 15" | Red Lion CR3000 | CR3000 15 inch | 340.1 × 265.7 mm | 13.39 × 10.46 in | 364.6 × 290.1 mm |
| 15" | Maple Systems HMI5000 and cMT Series | cMT2158XV2 | 352 × 279 mm | 13.86 × 10.98 in | 366 × 293 mm |
| 15" | Maple Systems HMI5000 and cMT Series | cMT3152XV2 | 352 × 279 mm | 13.86 × 10.98 in | 366 × 293 mm |
| 15" | Weintek cMT X Series | cMT3152X | 352 × 279 mm | 13.86 × 10.98 in | 366 × 293 mm |
| 15" | Allen-Bradley PanelView 5510 | 15 in. resistive touch | 353 × 290 mm | 13.90 × 11.42 in | 381 × 318 mm |
| 15" | Allen-Bradley PanelView Plus 7 Performance | 15 in. touch (2711P-T15C22D9P) | 353 × 290 mm | 13.90 × 11.42 in | 381 × 318 mm |
| 15" | Allen-Bradley PanelView Plus 7 Standard | 15 in. (2711P-T15C21D8S, 2711P-T15C22D8S) | 353 × 290 mm | 13.90 × 11.42 in | 381 × 318 mm |
| 15" | AutomationDirect C-more CM5 | CM5-T15W | 391.9 × 265.9 mm | 15.43 × 10.47 in | 407.7 × 281.5 mm |
| 15" | Delta DOP-100 Series | DOP-115WX / DOP-115MX | 372.4 × 283.7 mm | 14.66 × 11.17 in | 387.7 × 295.7 mm |
| 15" | Mitsubishi Electric GOT2000 GT27 | GT2715-X | 383.5 × 282.5 mm | 15.10 × 11.12 in | 397 × 300 mm |
| 15" | Pro-face SP5000 Series | SP-5700TP | 383.5 × 282.5 mm | 15.10 × 11.12 in | 397 × 296 mm |
| 15" | Schneider Electric Harmony GTU | HMIDT732 | 383.5 × 282.5 mm | 15.10 × 11.12 in | 397 × 296 mm |
| 15" | AutomationDirect C-more EA9 | EA9-T15CL / EA9-T15CL-R | 379.2 × 286.3 mm | 14.93 × 11.27 in | not printed |
| 15" | Allen-Bradley PanelView 5510 | 15 in. keypad and resistive touch | 418 × 290 mm | 16.46 × 11.42 in | 484 × 322 mm |
| 15" | Allen-Bradley PanelView Plus 7 Performance | 15 in. keypad and touch (2711P-B15C22D9P) | 418 × 290 mm | 16.46 × 11.42 in | 484 × 322 mm |
| 15.4" | Omron NA5 Series | NA5-15W | 392 × 268 mm | 15.43 × 10.55 in | 420 × 291 mm |
| 15.4" | Beijer Electronics X2 pro | X2 pro 15 | 394 × 270 mm | 15.51 × 10.63 in | 410 × 286 mm |
| 15.4" | Siemens SIMATIC HMI Comfort Panels | TP1500 Comfort | 396 × 291 mm | 15.59 × 11.46 in | 415 × 310 mm |
| 15.4" | Siemens SIMATIC HMI Comfort Panels | KP1500 Comfort | 450 × 291 mm | 17.72 × 11.46 in | not printed |
| 15.6" | Allen-Bradley PanelView 5510 | 15.6 in. capacitive touch | 387.5 × 237.5 mm | 15.26 × 9.35 in | 401.5 × 251 mm |
| 15.6" | Siemens SIMATIC HMI Unified Comfort Panels | MTP1500 Unified Comfort | 382 × 241 mm | 15.04 × 9.49 in | 398 × 257 mm |
| 15.6" | Maple Systems HMI5000 and cMT Series | cMT2166X | 384 × 247 mm | 15.12 × 9.72 in | 400 × 263 mm |
| 15.6" | Maple Systems HMI5000 and cMT Series | cMT3162XW | 384 × 247 mm | 15.12 × 9.72 in | 400 × 263 mm |
| 15.6" | Weintek cMT X Series | cMT3162X | 384 × 247 mm | 15.12 × 9.72 in | 400 × 263 mm |
| 15.6" | Pro-face ST6000 Series | ST-6700WA | 394 × 250 mm | 15.51 × 9.84 in | 412 × 268 mm |
| 15.6" | Schneider Electric Harmony ST6 | HMIST6700 | 394 × 250 mm | 15.51 × 9.84 in | 412 × 268 mm |
| 15.6" | Pro-face SP5000 Series | SP-5700WC | 396 × 277 mm | 15.59 × 10.91 in | 414 × 295 mm |
| 15.6" | Schneider Electric Harmony GTU | HMIDT752 | 396 × 277 mm | 15.59 × 10.91 in | 414 × 295 mm |
| 18.5" | Allen-Bradley PanelView 5510 | 18.5 in. capacitive touch | 453 × 274 mm | 17.83 × 10.79 in | 467.2 × 288 mm |
| 18.5" | Siemens SIMATIC HMI Unified Comfort Panels | MTP1900 Unified Comfort | 448 × 278 mm | 17.64 × 10.94 in | 464 × 294 mm |
| 18.5" | Pro-face SP5000 Series | SP-5800WC | 465 × 319 mm | 18.31 × 12.56 in | 483 × 337 mm |
| 18.5" | Schneider Electric Harmony GTU | HMIDT952 | 465 × 319 mm | 18.31 × 12.56 in | 483 × 337 mm |
| 18.5" | Siemens SIMATIC HMI Comfort Panels | TP1900 Comfort | 465 × 319 mm | 18.31 × 12.56 in | 483 × 337 mm |
| 19" | Allen-Bradley PanelView 5510 | 19 in. resistive touch | 457 × 383 mm | 17.99 × 15.08 in | 485 × 411 mm |
| 19" | Allen-Bradley PanelView Plus 7 Performance | 19 in. touch (2711P-T19C22D9P) | 457 × 383 mm | 17.99 × 15.08 in | 485 × 411 mm |
| 21.5" | Siemens SIMATIC HMI Unified Comfort Panels | MTP2200 Unified Comfort | 513 × 315 mm | 20.20 × 12.40 in | 529 × 331 mm |
| 21.5" | Allen-Bradley PanelView 5510 | 21.5 in. capacitive touch | 520 × 311.5 mm | 20.47 × 12.26 in | 534.2 × 325.6 mm |
| 21.5" | Maple Systems HMI5000 and cMT Series | cMT3218XP | 532 × 340 mm | 20.94 × 13.39 in | 546 × 354 mm |
| 21.5" | Siemens SIMATIC HMI Comfort Panels | TP2200 Comfort | 542 × 362 mm | 21.34 × 14.25 in | 560 × 380 mm |
| 22" | AutomationDirect C-more CM5 | CM5-T22W | 526.8 × 344.7 mm | 20.74 × 13.57 in | 542 × 360 mm |
Download all 229 rows as a CSV file: maker, series, model, cutout and bezel in mm and inches, depth, tolerance, source document and link.
Before you cut
Reading a cutout drawing
Cutout, bezel, depth
The cutout is the hole. The bezel (the overall front) is larger and has to land on flat door all round. The depth is the figure the document prints for the body: some drawings measure it from the door face and some from the front of the bezel, and none include the connectors or the cable bend. A drawing gives width first with the terminal in landscape; a portrait mounting swaps the two.
Tolerance, corners, thickness
Cut to the tolerance and the corner radius the maker prints: the gasket has only a few millimetres of land around the opening. The mounting clips clamp a stated range of panel thickness, so check the door sheet against it; each enclosure size's sheet is in the enclosure size chart. Where a document prints no tolerance or radius, this reference shows none.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Allen-Bradley, AutomationDirect, Beijer Electronics, C-more, Delta, GOT, Graphite, HMS Networks, Harmony, Maple Systems, Mitsubishi Electric, Omron, PanelView, Pro-face, Red Lion, Rockwell Automation, SIMATIC, Schneider Electric, Siemens, Sysmac, Weintek and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
HMI cutout dimensions: questions
Is an HMI cutout the same as its bezel size?
No. The cutout is the hole in the door; the bezel is the front of the terminal, which is larger on every side and covers the hole and the gasket. Lay out the door with the bezel size and cut it with the cutout size.
Are HMI panel cutouts standardized between makers?
No. Each series has its own opening, and two terminals with the same screen size usually need different cutouts, even from one maker. Compare them in the table by screen size.
Can a new HMI go into the cutout of the one it replaces?
Only when the new cutout is no smaller than the old one in width and in height, and the new bezel still covers the old hole. A smaller terminal needs an adapter plate from its maker or a new door; a larger one means enlarging the opening and checking that the bezel clears the hinge, the latch and the door stiffeners.
Where do these dimensions come from?
From each maker's own installation instructions, user manual or data sheet, named and linked on the series page with the page where the number is printed. Makers revise drawings, so confirm the current document for your catalog number before cutting.
Can you supply the enclosure with the HMI opening already cut?
Yes. Enter the cutout and bezel in the cutout designer under "My own display", or send the model with your quote request. The opening is drawn on a stainless enclosure in your size and cut at the factory after you approve the drawing.