AutomationDirect C-more CM5 panel cutout dimensions

The AutomationDirect C-more CM5 CM5-T4W needs a panel cutout of 102.1 × 70.1 mm (4.02 × 2.76 in), width by height, and the CM5-T22W needs 526.8 × 344.7 mm (20.74 × 13.57 in). The table gives the opening for each of the 6 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Supported panel thickness: Enclosure mounting thickness 0.039 - 0.20 inch [1 - 5 mm], metal..

Per model

AutomationDirect C-more CM5 cutout dimensions

AutomationDirect C-more CM5: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
CM5-T4W4"102.1 × 70.1 mm4.02 × 2.76 in *120.9 × 88.3 mmnot printed4.02 in. [102.1 mm] × 2.76 in. [70.1 mm] (p. 4-5)Lay it out
CM5-T7W7"189.5 × 140 mm7.46 × 5.51 in *205.2 × 155.8 mmnot printed7.46 in. [189.5 mm] × 5.51 in. [140.0 mm] (p. 4-6)Lay it out
CM5-T10W10"235 × 179.6 mm9.25 × 7.07 in *268 × 195.9 mmnot printed9.25 in. [235.0 mm] × 7.07 in. [179.6 mm] (p. 4-7)Lay it out
CM5-T12W12"302.5 × 226.6 mm11.91 × 8.92 in *318.8 × 242.9 mmnot printed11.91 in. [302.5 mm] × 8.92 in. [226.6 mm] (p. 4-8)Lay it out
CM5-T15W15"391.9 × 265.9 mm15.43 × 10.47 in *407.7 × 281.5 mmnot printed15.43 in. [391.9 mm] × 10.47 in. [265.9 mm] (p. 4-9)Lay it out
CM5-T22W22"526.8 × 344.7 mm20.74 × 13.57 in *542 × 360 mmnot printed20.74 in. [526.8 mm] × 13.57 in. [344.7 mm] (p. 4-10)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: C-more CM5 Hardware User Manual, CM5-USER-M, 2nd Edition Rev. I, Chapter 4 (Installation and Wiring), read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

CM5-T22WCM5-T15WCM5-T12WCM5-T10WCM5-T7WCM5-T4W
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
CM5-T4W18.8 mm18.2 mm
CM5-T7W15.7 mm15.8 mm
CM5-T10W33 mm16.3 mm
CM5-T12W16.3 mm16.3 mm
CM5-T15W15.8 mm15.6 mm
CM5-T22W15.2 mm15.3 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
Enclosure mounting thickness 0.039 - 0.20 inch [1 - 5 mm], metal.
Mounting
Through the cutout from the front, held by mounting clips: 2 on the CM5-T4W, 4 on the CM5-T7W and CM5-T10W, 8 on the CM5-T12W and CM5-T15W, 12 on the CM5-T22W. Clip screw torque 21 - 28 oz-in [0.15 - 0.20 Nm] on the 4 inch panel, 135 - 149 oz-in [0.95 - 1.05 Nm] on the 7 inch through 22 inch.
Front rating, as the maker states it
NEMA 250 type 4/4X indoor use only, UL50 type 4X indoor use only and IP65 indoor, in the manual's specifications.
Clearance around the terminal
Minimum 4 in. on all sides and 1.72 in. at the rear, in the manual's clearance drawing.
Notes
The drawings are in inches with millimetres in brackets; each shows the cutout and, around it, the bezel outline given here as the bezel. The CM5-T7W and CM5-T10W print the same cutouts as the EA9-T7CL and EA9-T10WCL of the EA9 series. No cutout tolerance, corner radius or depth is printed in chapter 4.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other AutomationDirect series

C-more EA9 · every series by screen size

AutomationDirect, C-more and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

C-more CM5: questions

What is the panel cutout for the AutomationDirect C-more CM5 CM5-T4W?

102.1 × 70.1 mm (4.02 × 2.76 in), width by height, behind a bezel of 120.9 × 88.3 mm. The document prints it as: 4.02 in. [102.1 mm] × 2.76 in. [70.1 mm].

What is the panel cutout for the AutomationDirect C-more CM5 CM5-T7W?

189.5 × 140 mm (7.46 × 5.51 in), width by height, behind a bezel of 205.2 × 155.8 mm. The document prints it as: 7.46 in. [189.5 mm] × 5.51 in. [140.0 mm].

What is the panel cutout for the AutomationDirect C-more CM5 CM5-T10W?

235 × 179.6 mm (9.25 × 7.07 in), width by height, behind a bezel of 268 × 195.9 mm. The document prints it as: 9.25 in. [235.0 mm] × 7.07 in. [179.6 mm].

What is the panel cutout for the AutomationDirect C-more CM5 CM5-T12W?

302.5 × 226.6 mm (11.91 × 8.92 in), width by height, behind a bezel of 318.8 × 242.9 mm. The document prints it as: 11.91 in. [302.5 mm] × 8.92 in. [226.6 mm].

What panel thickness does the AutomationDirect C-more CM5 mount in?

The document states: Enclosure mounting thickness 0.039 - 0.20 inch [1 - 5 mm], metal..

Can you cut the C-more CM5 opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.