Siemens SIMATIC HMI Comfort Panels panel cutout dimensions

The Siemens SIMATIC HMI Comfort Panels KTP400 Comfort needs a panel cutout of 122 × 98 mm (4.80 × 3.86 in), width by height, and the TP2200 Comfort needs 542 × 362 mm (21.34 × 14.25 in). The table gives the opening for each of the 12 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.

Per model

Siemens SIMATIC HMI Comfort Panels cutout dimensions

Siemens SIMATIC HMI Comfort Panels: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
KTP400 Comfort4.3"122 × 98 mm4.80 × 3.86 in *140 × 116 mmnot printed122 mm × 98 mm (p. 38)Lay it out
KP400 Comfort4.3"135 × 171 mm5.31 × 6.73 in *not printednot printed135 mm × 171 mm (p. 38)
TP700 Comfort7"197 × 141 mm7.76 × 5.55 in *214 × 158 mmnot printed197 mm × 141 mm (p. 38)Lay it out
KP700 Comfort7"281 × 177 mm11.06 × 6.97 in *not printednot printed281 mm × 177 mm (p. 38)
TP900 Comfort9"250 × 166 mm9.84 × 6.54 in *274 × 190 mmnot printed250 mm × 166 mm (p. 38)Lay it out
KP900 Comfort9"338 × 206 mm13.31 × 8.11 in *not printednot printed338 mm × 206 mm (p. 38)
TP1200 Comfort12.1"310 × 221 mm12.20 × 8.70 in *330 × 241 mmnot printed310 mm × 221 mm (p. 38)Lay it out
KP1200 Comfort12.1"434 × 268 mm17.09 × 10.55 in *not printednot printed434 mm × 268 mm (p. 38)
TP1500 Comfort15.4"396 × 291 mm15.59 × 11.46 in *415 × 310 mmnot printed396 mm × 291 mm (p. 38)Lay it out
KP1500 Comfort15.4"450 × 291 mm17.72 × 11.46 in *not printednot printed450 mm × 291 mm (p. 38)
TP1900 Comfort18.5"465 × 319 mm18.31 × 12.56 in *483 × 337 mmnot printed465 mm × 319 mm (p. 38)Lay it out
TP2200 Comfort21.5"542 × 362 mm21.34 × 14.25 in *560 × 380 mmnot printed542 mm × 362 mm (p. 38)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: SIMATIC HMI Comfort Panels Operating Instructions, 07/2022, A5E36770603-AE, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

TP2200 ComfortTP1900 ComfortKP1500 ComfortKP1200 ComfortKP900 ComfortTP1200 ComfortKP700 ComfortTP700 ComfortKTP400 Comfort
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
KTP400 Comfort18 mm18 mm
TP700 Comfort17 mm17 mm
TP900 Comfort24 mm24 mm
TP1200 Comfort20 mm20 mm
TP1500 Comfort19 mm19 mm
TP1900 Comfort18 mm18 mm
TP2200 Comfort18 mm18 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
2 mm to 6 mm at the mounting cutout for IP65 or Type 4X/Type 12; permissible deviation from plane at the cutout 0.5 mm.
Cutout tolerance
+1/0 mm
Mounting
From the front, held by mounting clips at the positions the manual marks for each device.
Front rating, as the maker states it
Front, when mounted: IP65 according to IEC 60529 and Type 4X/Type 12 (indoor use only) according to UL50, as the maker states it.
Clearance around the terminal
The manual's clearance drawing gives 15 mm (x), 50 mm (y) and 10 mm (z) around the device.
Notes
Width and height are reversed for portrait mounting, the manual says. The screen column is the active display area the manual's technical specifications give, which differs from the number in the device name on the 15, 19 and 22 inch devices. The key panels (KP) are listed with their cutouts only; their outside dimensions are in the manual's dimension drawings. Each dimension drawing prints several depth figures, so no single depth is shown here. No corner radius is printed, and only millimetres.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other Siemens series

SIMATIC HMI Basic Panels (2nd Generation) · SIMATIC HMI Unified Comfort Panels · every series by screen size

SIMATIC, Siemens and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

SIMATIC HMI Comfort Panels: questions

What is the panel cutout for the Siemens SIMATIC HMI Comfort Panels KTP400 Comfort?

122 × 98 mm (4.80 × 3.86 in), width by height, behind a bezel of 140 × 116 mm. The document prints it as: 122 mm × 98 mm.

What is the panel cutout for the Siemens SIMATIC HMI Comfort Panels KP400 Comfort?

135 × 171 mm (5.31 × 6.73 in), width by height. The document prints it as: 135 mm × 171 mm.

What is the panel cutout for the Siemens SIMATIC HMI Comfort Panels TP700 Comfort?

197 × 141 mm (7.76 × 5.55 in), width by height, behind a bezel of 214 × 158 mm. The document prints it as: 197 mm × 141 mm.

What is the panel cutout for the Siemens SIMATIC HMI Comfort Panels KP700 Comfort?

281 × 177 mm (11.06 × 6.97 in), width by height. The document prints it as: 281 mm × 177 mm.

What panel thickness does the Siemens SIMATIC HMI Comfort Panels mount in?

The document states: 2 mm to 6 mm at the mounting cutout for IP65 or Type 4X/Type 12; permissible deviation from plane at the cutout 0.5 mm..

Can you cut the SIMATIC HMI Comfort Panels opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.