Delta DOP-100 Series panel cutout dimensions

The Delta DOP-100 Series DOP-103BQ needs a panel cutout of 118.8 × 92.8 mm (4.68 × 3.65 in), width by height, and the DOP-115WX / DOP-115MX needs 372.4 × 283.7 mm (14.66 × 11.17 in). The table gives the opening for each of the 18 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.

Per model

Delta DOP-100 Series cutout dimensions

Delta DOP-100 Series: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
DOP-103BQ4.3"118.8 × 92.8 mm4.68 × 3.65 in *137 × 103 mm37.1 mm118.8 × 92.8 mm; tolerance +0.5/0 mm (drawing p. 37)Lay it out
DOP-103WQ4.3"118.8 × 92.8 mm4.68 × 3.65 in *137 × 103 mm37.1 mm118.8 × 92.8 mm; tolerance +0.5/0 mm (drawing p. 32)Lay it out
DOP-105CQ5.6"172.4 × 132.4 mm6.79 × 5.21 in *184 × 144 mm50.6 mm172.4 × 132.4 mm; tolerance +1.0/0 mm (drawing p. 35)Lay it out
DOP-107EG7"172.4 × 132.4 mm6.79 × 5.21 in *184 × 144 mm51.5 mm172.4 × 132.4 mm; tolerance +1.0/0 mm (drawing p. 35)Lay it out
DOP-107WV7"186.8 × 126.8 mm7.35 × 4.99 in *196 × 136 mm39 mm186.8 × 126.8 mm; tolerance +1.0/0 mm (drawing p. 32)Lay it out
DOP-107BV7"196 × 142.9 mm7.72 × 5.63 in *215 × 161 mm35.5 mm196 × 142.9 mm; tolerance +1.0/0 mm (drawing p. 37)Lay it out
DOP-107DV7"196 × 142.9 mm7.72 × 5.63 in *215 × 161 mm35.5 mm196 × 142.9 mm; tolerance +1.0/0 mm (drawing p. 37)Lay it out
DOP-107CV7"196.9 × 142.9 mm7.75 × 5.63 in *215 × 161 mm61.2 mm196.9 × 142.9 mm; tolerance +1.0/0 mm (drawing p. 36)Lay it out
DOP-107EV7"196.9 × 142.9 mm7.75 × 5.63 in *215 × 161 mm61.2 mm196.9 × 142.9 mm; tolerance +1.0/0 mm (drawing p. 35)Lay it out
DOP-107IV7"196.9 × 142.9 mm7.75 × 5.63 in *215 × 161 mm61.2 mm196.9 × 142.9 mm; tolerance +1.0/0 mm (drawing p. 33)Lay it out
DOP-108IG8"219.4 × 166.5 mm8.64 × 6.56 in *227.1 × 174.1 mm61 mm219.4 × 166.5 mm; tolerance +1/0 mm (drawing p. 34)Lay it out
DOP-110CS10"261.3 × 189.3 mm10.29 × 7.45 in *272 × 200 mm61 mm261.3 × 189.3 mm; tolerance +1.0/0 mm (drawing p. 36)Lay it out
DOP-110WS10.1"255.5 × 170.5 mm10.06 × 6.71 in *270 × 180.9 mm47.25 mm255.5 × 170.5 mm; tolerance +0.5/0 mm; corner radius R5 (drawing p. 32)Lay it out
DOP-110IS10.1"261.3 × 189.3 mm10.29 × 7.45 in *272.6 × 200.6 mm54 mm261.3 × 189.3 mm; tolerance +1/0 mm (drawing p. 34)Lay it out
DOP-110CG10.4"285.2 × 210.2 mm11.23 × 8.28 in *299 × 224 mm46.75 mm285.2 × 210.2 mm; tolerance +1.0/0 mm (drawing p. 36)Lay it out
DOP-110IG10.4"285.2 × 210.2 mm11.23 × 8.28 in *299 × 224 mm46.75 mm285.2 × 210.2 mm; tolerance +1.0/0 mm (drawing p. 34)Lay it out
DOP-112WX / DOP-112MX12"302.7 × 228.7 mm11.92 × 9.00 in *317.4 × 246.4 mm52.7 mm302.7 × 228.7 mm; tolerance +1.0/0 mm (drawing p. 33)Lay it out
DOP-115WX / DOP-115MX15"372.4 × 283.7 mm14.66 × 11.17 in *387.7 × 295.7 mm63.5 mm372.4 × 283.7 mm; tolerance +0.5/0 mm; corner radius R8 (drawing p. 33)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: Delta Human Machine Interface DOP-100 Series catalogue, DELTA_IA-HMI-DOP-100_C_EN_20200109, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

DOP-115WX / DOP-115MXDOP-112WX / DOP-112MXDOP-110CGDOP-110CSDOP-110WSDOP-107CVDOP-107WVDOP-103WQ
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
DOP-103WQ18.2 mm10.2 mm
DOP-103BQ18.2 mm10.2 mm
DOP-105CQ11.6 mm11.6 mm
DOP-107EG11.6 mm11.6 mm
DOP-107WV9.2 mm9.2 mm
DOP-107BV19 mm18.1 mm
DOP-107DV19 mm18.1 mm
DOP-107CV18.1 mm18.1 mm
DOP-107EV18.1 mm18.1 mm
DOP-107IV18.1 mm18.1 mm
DOP-108IG7.7 mm7.6 mm
DOP-110CS10.7 mm10.7 mm
DOP-110WS14.5 mm10.4 mm
DOP-110IS11.3 mm11.3 mm
DOP-110CG13.8 mm13.8 mm
DOP-110IG13.8 mm13.8 mm
DOP-112WX / DOP-112MX14.7 mm17.7 mm
DOP-115WX / DOP-115MX15.3 mm12 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
T = 1.6 to 6 mm (0.063 to 0.24 in) for most models. DOP-103WQ and DOP-103BQ: 1.6 to 3 mm (0.063 to 0.12 in). DOP-108IG: 1.6 to 5 mm (0.063 to 0.2 in).
Mounting
From the front; the catalogue calls the opening the mounting dimension.
Front rating, as the maker states it
IP65 / NEMA4 / UL Type 4X (indoor use only), in the catalogue's hardware specifications.
Notes
The figures are from the catalogue's dimension drawings, not from an instruction sheet. Its specification table differs on a few: for the DOP-110WS it prints a 255 mm cutout width where the drawing prints 255.5 mm. The drawings mark corner radii for two models only, 4-R5 on the DOP-110WS and 4-R8 on the DOP-115. Check the instruction sheet packed with the unit before cutting.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Delta and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

DOP-100 Series: questions

What is the panel cutout for the Delta DOP-100 Series DOP-103WQ?

118.8 × 92.8 mm (4.68 × 3.65 in), width by height, behind a bezel of 137 × 103 mm. The document prints it as: 118.8 × 92.8 mm.

What is the panel cutout for the Delta DOP-100 Series DOP-103BQ?

118.8 × 92.8 mm (4.68 × 3.65 in), width by height, behind a bezel of 137 × 103 mm. The document prints it as: 118.8 × 92.8 mm.

What is the panel cutout for the Delta DOP-100 Series DOP-105CQ?

172.4 × 132.4 mm (6.79 × 5.21 in), width by height, behind a bezel of 184 × 144 mm. The document prints it as: 172.4 × 132.4 mm.

What is the panel cutout for the Delta DOP-100 Series DOP-107EG?

172.4 × 132.4 mm (6.79 × 5.21 in), width by height, behind a bezel of 184 × 144 mm. The document prints it as: 172.4 × 132.4 mm.

What panel thickness does the Delta DOP-100 Series mount in?

The document states: T = 1.6 to 6 mm (0.063 to 0.24 in) for most models. DOP-103WQ and DOP-103BQ: 1.6 to 3 mm (0.063 to 0.12 in). DOP-108IG: 1.6 to 5 mm (0.063 to 0.2 in)..

Can you cut the DOP-100 Series opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.