Allen-Bradley PanelView 5510 panel cutout dimensions
The Allen-Bradley PanelView 5510 6.5 in. resistive touch needs a panel cutout of 184 × 142 mm (7.24 × 5.59 in), width by height, and the 19 in. resistive touch needs 457 × 383 mm (17.99 × 15.08 in). The table gives the opening for each of the 16 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.
Per model
Allen-Bradley PanelView 5510 cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| 6.5 in. resistive touch | 6.5" | 184 × 142 mm | 7.24 × 5.59 in * | 212 × 170 mm | 64 mm | 184 mm (7.24 in.) × 142 mm (5.59 in.) (UM001 p. 27, Table 14) | Lay it out |
| 6.5 in. keypad and resistive touch | 6.5" | 237 × 142 mm | 9.33 × 5.59 in * | 285 × 179 mm | 64 mm | 237 mm (9.33 in.) × 142 mm (5.59 in.) (UM001 p. 27, Table 14) | Lay it out |
| 7 in. capacitive touch | 7" | 196 × 139.5 mm | 7.72 × 5.49 in * | 207 × 150.6 mm | 58.1 mm | 196 mm (7.72 in.) × 139.5 mm (5.49 in.) (UM001 p. 27, Table 14) | Lay it out |
| 7 in. resistive touch (2715P-T7WD) | 7" | 210 × 150 mm | 8.27 × 5.91 in * | 237 × 178 mm | 64 mm | 210 mm (8.25 in.) × 150 mm (5.9 in.) (UM001 p. 27, Table 14) | Lay it out |
| 9 in. resistive touch | 9" | 252 × 162 mm | 9.92 × 6.38 in * | 280 × 190 mm | 64 mm | 252 mm (9.92 in.) × 162 mm (6.38 in.) (UM001 p. 27, Table 14) | Lay it out |
| 10.1 in. capacitive touch | 10.1" | 255.5 × 174 mm | 10.06 × 6.85 in * | 269.5 × 187.9 mm | 57.4 mm | 255.5 mm (10.06 in.) × 174 mm (6.85 in.) (UM001 p. 27, Table 14) | Lay it out |
| 10.4 in. resistive touch | 10.4" | 269 × 224 mm | 10.59 × 8.82 in * | 297 × 252 mm | 64 mm | 269 mm (10.59 in.) × 224 mm (8.82 in.) (UM001 p. 27, Table 14) | Lay it out |
| 10.4 in. keypad and resistive touch | 10.4" | 335 × 224 mm | 13.19 × 8.82 in * | 385 × 252 mm | 64 mm | 335 mm (13.19 in.) × 224 mm (8.82 in.) (UM001 p. 27, Table 14) | Lay it out |
| 12.1 in. capacitive touch | 12.1" | 301 × 203 mm | 11.85 × 7.99 in * | 315 × 217 mm | 57.4 mm | 301 mm (11.85 in.) × 203 mm (7.99 in.) (UM001 p. 27, Table 14) | Lay it out |
| 12.1 in. resistive touch | 12.1" | 312 × 218 mm | 12.28 × 8.58 in * | 340 × 246 mm | 64 mm | 312 mm (12.28 in.) × 218 mm (8.58 in.) (UM001 p. 27, Table 14) | Lay it out |
| 15 in. resistive touch | 15" | 353 × 290 mm | 13.90 × 11.42 in * | 381 × 318 mm | 64 mm | 353 mm (13.90 in.) × 290 mm (11.42 in.) (UM001 p. 27, Table 14) | Lay it out |
| 15 in. keypad and resistive touch | 15" | 418 × 290 mm | 16.46 × 11.42 in * | 484 × 322 mm | 64 mm | 418 mm (16.46 in.) × 290 mm (11.42 in.) (UM001 p. 27, Table 14) | Lay it out |
| 15.6 in. capacitive touch | 15.6" | 387.5 × 237.5 mm | 15.26 × 9.35 in * | 401.5 × 251 mm | 57.4 mm | 387.5 mm (15.26 in.) × 237.5 mm (9.35 in.) (UM001 p. 27, Table 14) | Lay it out |
| 18.5 in. capacitive touch | 18.5" | 453 × 274 mm | 17.83 × 10.79 in * | 467.2 × 288 mm | 57.4 mm | 453 mm (17.83 in.) × 274 mm (10.79 in.) (UM001 p. 27, Table 14) | Lay it out |
| 19 in. resistive touch | 19" | 457 × 383 mm | 17.99 × 15.08 in * | 485 × 411 mm | 64 mm | 457 mm (17.99 in.) × 383 mm (15.08 in.) (UM001 p. 27, Table 14) | Lay it out |
| 21.5 in. capacitive touch | 21.5" | 520 × 311.5 mm | 20.47 × 12.26 in * | 534.2 × 325.6 mm | 57.4 mm | 520 mm (20.47 in.) × 311.5 mm (12.26 in.) (UM001 p. 27, Table 14) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: PanelView 5510 Terminals User Manual, 2715P-UM001H-EN-P, September 2026 (cutout, Table 14); bezel and depth from Technical Data 2715P-TD001G-EN-P, September 2026, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| 6.5 in. resistive touch | 28 mm | 28 mm |
| 6.5 in. keypad and resistive touch | 48 mm | 37 mm |
| 7 in. capacitive touch | 11 mm | 11.1 mm |
| 7 in. resistive touch (2715P-T7WD) | 27 mm | 28 mm |
| 9 in. resistive touch | 28 mm | 28 mm |
| 10.1 in. capacitive touch | 14 mm | 13.9 mm |
| 10.4 in. resistive touch | 28 mm | 28 mm |
| 10.4 in. keypad and resistive touch | 50 mm | 28 mm |
| 12.1 in. capacitive touch | 14 mm | 14 mm |
| 12.1 in. resistive touch | 28 mm | 28 mm |
| 15 in. resistive touch | 28 mm | 28 mm |
| 15 in. keypad and resistive touch | 66 mm | 32 mm |
| 15.6 in. capacitive touch | 14 mm | 13.5 mm |
| 18.5 in. capacitive touch | 14.2 mm | 14 mm |
| 19 in. resistive touch | 28 mm | 28 mm |
| 21.5 in. capacitive touch | 14.2 mm | 14.1 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- Resistive touch and keypad terminals: 1.5...4.8 mm (0.06...0.19 in.). Capacitive touch terminals: 3...6 mm (0.11...0.24 in.), with a deformation limit on the plane of 0.5 mm.
- Mounting
- From the front, held by mounting levers. The manual says to mark the cutout with the template shipped with the terminal.
- Front rating, as the maker states it
- The technical data gives three sets, each tied to a panel thickness: NEMA and UL Type 1, 4X, 12 and 13, rated IP66 as Classified by UL, on a 1.5...4.8 mm panel; NEMA and UL Type 1, 4X, 12 and 13, rated IP69 as Classified by UL and tested for IP69K according to ISO 20653, on a 1.5...4.8 mm panel; and NEMA and UL Type 1, 4X and 12, rated IP65 according to IEC 60529, on a 3...6 mm panel. See the document for which terminal each set applies to.
- Clearance around the terminal
- Top 51 mm (2 in.); bottom 102 mm (4 in.); side 25 mm (1 in.), or 102 mm (4 in.) on a side used to insert or remove an SD card or cable; back 0.
- Notes
- The manual's cutout table gives height first, then width; this page gives width × height. The depth shown is the mounted depth, behind the panel. Two of the maker's documents disagree on the 7 in. resistive touch terminal: the user manual prints a cutout of 210 mm (8.25 in.) wide by 150 mm (5.9 in.) high, shown here, and the technical data prints 207 mm (8.15 in.) by 148 mm (5.82 in.). Use the template shipped with the terminal before cutting. The user manual also prints an overall height of 329 mm (12.95 in.) for the 15 in. keypad terminal where the technical data prints 322 mm (12.68 in.), shown here, and names the largest capacitive terminal 21.5 in. where the technical data names it 21.1 in. No cutout tolerance or corner radius is printed. Rows are named by size and input type, as the manual's table is.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Allen-Bradley series
PanelView Plus 7 Standard · PanelView Plus 7 Performance · PanelView 800 · PanelView 5310 · every series by screen size
Allen-Bradley, PanelView, Rockwell Automation and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
PanelView 5510: questions
What is the panel cutout for the Allen-Bradley PanelView 5510 6.5 in. resistive touch?
184 × 142 mm (7.24 × 5.59 in), width by height, behind a bezel of 212 × 170 mm. The document prints it as: 184 mm (7.24 in.) × 142 mm (5.59 in.).
What is the panel cutout for the Allen-Bradley PanelView 5510 6.5 in. keypad and resistive touch?
237 × 142 mm (9.33 × 5.59 in), width by height, behind a bezel of 285 × 179 mm. The document prints it as: 237 mm (9.33 in.) × 142 mm (5.59 in.).
What is the panel cutout for the Allen-Bradley PanelView 5510 7 in. capacitive touch?
196 × 139.5 mm (7.72 × 5.49 in), width by height, behind a bezel of 207 × 150.6 mm. The document prints it as: 196 mm (7.72 in.) × 139.5 mm (5.49 in.).
What is the panel cutout for the Allen-Bradley PanelView 5510 7 in. resistive touch (2715P-T7WD)?
210 × 150 mm (8.27 × 5.91 in), width by height, behind a bezel of 237 × 178 mm. The document prints it as: 210 mm (8.25 in.) × 150 mm (5.9 in.).
What panel thickness does the Allen-Bradley PanelView 5510 mount in?
The document states: Resistive touch and keypad terminals: 1.5...4.8 mm (0.06...0.19 in.). Capacitive touch terminals: 3...6 mm (0.11...0.24 in.), with a deformation limit on the plane of 0.5 mm..
Can you cut the PanelView 5510 opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.