Allen-Bradley PanelView 800 panel cutout dimensions

The Allen-Bradley PanelView 800 2711R-T4T needs a panel cutout of 119 × 99 mm (4.69 × 3.90 in), width by height, and the 2711R-T10T needs 269 × 206 mm (10.59 × 8.11 in). The table gives the opening for each of the 3 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.

Per model

Allen-Bradley PanelView 800 cutout dimensions

Allen-Bradley PanelView 800: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
2711R-T4T4"119 × 99 mm4.69 × 3.90 in *138 × 116 mm39 mm119.0 ±0.5 mm (4.68 ±0.02 in.) × 99.0 ±0.5 mm (3.89 ±0.02 in.) (p. 7; product dimensions p. 11)Lay it out
2711R-T7T7"179 × 125 mm7.05 × 4.92 in *197 × 144 mm50 mm179.0 ±0.5 mm (7.05 ±0.02 in.) × 125.0 ±0.5 mm (4.92 ±0.02 in.) (p. 7; product dimensions p. 11)Lay it out
2711R-T10T10"269 × 206 mm10.59 × 8.11 in *287 × 225 mm51 mm269.0 ±0.5 mm (10.59 ±0.02 in.) × 206.0 ±0.5 mm (8.11 ±0.02 in.) (p. 7; product dimensions p. 11)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: PanelView 800 HMI Terminals Installation Instructions, 2711R-IN001E-EN-P, June 2024, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

2711R-T10T2711R-T7T2711R-T4T
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
2711R-T4T19 mm17 mm
2711R-T7T18 mm19 mm
2711R-T10T18 mm19 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
Supporting panels must be at least 16 gauge, the instructions say, to seal against water and dust and to give proper support.
Cutout tolerance
±0.5 mm (±0.02 in.)
Mounting
From the front, held by mounting levers. The instructions say to mark the cutout with the template shipped with the terminal.
Front rating, as the maker states it
Meets NEMA/UL Type 4X (indoor), 12, 13, and IP65, in the maker's instructions.
Clearance around the terminal
Top / bottom / sides / back: 2711R-T4T 51 / 51 / 51 / 51 mm (2 in. each); 2711R-T7T 51 / 51 / 25 / 51 mm (2 / 2 / 1 / 2 in.); 2711R-T10T 51 / 25 / 25 / 51 mm (2 / 1 / 1 / 2 in.).
Notes
The manual's cutout table gives height first, then width; this page gives width × height. The depth shown is the mounted depth, behind the panel; the overall depths are 43 mm, 54 mm and 55 mm. The instructions print no corner radius.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other Allen-Bradley series

PanelView Plus 7 Standard · PanelView Plus 7 Performance · PanelView 5510 · PanelView 5310 · every series by screen size

Allen-Bradley, PanelView, Rockwell Automation and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

PanelView 800: questions

What is the panel cutout for the Allen-Bradley PanelView 800 2711R-T4T?

119 × 99 mm (4.69 × 3.90 in), width by height, behind a bezel of 138 × 116 mm. The document prints it as: 119.0 ±0.5 mm (4.68 ±0.02 in.) × 99.0 ±0.5 mm (3.89 ±0.02 in.).

What is the panel cutout for the Allen-Bradley PanelView 800 2711R-T7T?

179 × 125 mm (7.05 × 4.92 in), width by height, behind a bezel of 197 × 144 mm. The document prints it as: 179.0 ±0.5 mm (7.05 ±0.02 in.) × 125.0 ±0.5 mm (4.92 ±0.02 in.).

What is the panel cutout for the Allen-Bradley PanelView 800 2711R-T10T?

269 × 206 mm (10.59 × 8.11 in), width by height, behind a bezel of 287 × 225 mm. The document prints it as: 269.0 ±0.5 mm (10.59 ±0.02 in.) × 206.0 ±0.5 mm (8.11 ±0.02 in.).

What panel thickness does the Allen-Bradley PanelView 800 mount in?

The document states: Supporting panels must be at least 16 gauge, the instructions say, to seal against water and dust and to give proper support..

Can you cut the PanelView 800 opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.