Mitsubishi Electric GOT2000 GT27 panel cutout dimensions

The Mitsubishi Electric GOT2000 GT27 GT2705-V needs a panel cutout of 153 × 121 mm (6.02 × 4.76 in), width by height, and the GT2715-X needs 383.5 × 282.5 mm (15.10 × 11.12 in). The table gives the opening for each of the 5 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Supported panel thickness: 1.6 to 4 mm (0.06 to 0.16 in).

Per model

Mitsubishi Electric GOT2000 GT27 cutout dimensions

Mitsubishi Electric GOT2000 GT27: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
GT2705-V5.7"153 × 121 mm6.02 × 4.76 in *167 × 139 mm60 mm153 × 121 mm (spec p.74, panel cut p.173)Lay it out
GT2708-S / GT2708-V8.4"227 × 176 mm8.94 × 6.93 in *241 × 194 mm52 mm227 × 176 mm (spec p.72, panel cut p.173)Lay it out
GT2710-S / GT2710-V10.4"289 × 200 mm11.38 × 7.87 in *303 × 218 mm52 mm289 × 200 mm (spec p.70, panel cut p.173)Lay it out
GT2712-S12.1"302 × 228 mm11.89 × 8.98 in *316 × 246 mm52 mm302 × 228 mm (spec p.68, panel cut p.173)Lay it out
GT2715-X15"383.5 × 282.5 mm15.10 × 11.12 in *397 × 300 mm60 mm383.5 × 282.5 mm (spec p.66, panel cut p.172)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: GOT2000 Series User's Manual (Hardware), SH-081194ENG, version AX, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

GT2715-XGT2712-SGT2710-S / GT2710-VGT2708-S / GT2708-VGT2705-V
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
GT2705-V14 mm18 mm
GT2708-S / GT2708-V14 mm18 mm
GT2710-S / GT2710-V14 mm18 mm
GT2712-S14 mm18 mm
GT2715-X13.5 mm17.5 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
1.6 to 4 mm (0.06 to 0.16 in)
Cutout tolerance
+2/0 mm (+0.08/0 in)
Mounting
Installation fittings; the manual's dimension C, the space left for fitting them, is 10 mm (0.39 in) or more.
Front rating, as the maker states it
Front: IP67F. Inside the control panel: IP2X. The specification tables qualify both with footnotes.
Notes
In the manual's panel cut table (section 6.2) A is the width and B the height. The manual prints no corner radius.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other Mitsubishi Electric series

GOT SIMPLE GS21 and GS25 · GOT2000 GT25 · GOT2000 GT21 · every series by screen size

GOT, Mitsubishi Electric and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

GOT2000 GT27: questions

What is the panel cutout for the Mitsubishi Electric GOT2000 GT27 GT2705-V?

153 × 121 mm (6.02 × 4.76 in), width by height, behind a bezel of 167 × 139 mm. The document prints it as: 153 × 121 mm.

What is the panel cutout for the Mitsubishi Electric GOT2000 GT27 GT2708-S / GT2708-V?

227 × 176 mm (8.94 × 6.93 in), width by height, behind a bezel of 241 × 194 mm. The document prints it as: 227 × 176 mm.

What is the panel cutout for the Mitsubishi Electric GOT2000 GT27 GT2710-S / GT2710-V?

289 × 200 mm (11.38 × 7.87 in), width by height, behind a bezel of 303 × 218 mm. The document prints it as: 289 × 200 mm.

What is the panel cutout for the Mitsubishi Electric GOT2000 GT27 GT2712-S?

302 × 228 mm (11.89 × 8.98 in), width by height, behind a bezel of 316 × 246 mm. The document prints it as: 302 × 228 mm.

What panel thickness does the Mitsubishi Electric GOT2000 GT27 mount in?

The document states: 1.6 to 4 mm (0.06 to 0.16 in).

Can you cut the GOT2000 GT27 opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.