Siemens SIMATIC HMI Unified Comfort Panels panel cutout dimensions
The Siemens SIMATIC HMI Unified Comfort Panels MTP700 Unified Comfort needs a panel cutout of 197 × 141 mm (7.76 × 5.55 in), width by height, and the MTP2200 Unified Comfort needs 513 × 315 mm (20.20 × 12.40 in). The table gives the opening for each of the 6 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.
Per model
Siemens SIMATIC HMI Unified Comfort Panels cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| MTP700 Unified Comfort | 7" | 197 × 141 mm | 7.76 × 5.55 in * | 214 × 158 mm | not printed | 197 mm × 141 mm (p. 32; dimension drawings in section 8.7) | Lay it out |
| MTP1000 Unified Comfort | 10.1" | 264 × 189 mm | 10.39 × 7.44 in * | 280 × 205 mm | not printed | 264 mm × 189 mm (p. 32; dimension drawings in section 8.7) | Lay it out |
| MTP1200 Unified Comfort | 12.1" | 310 × 221 mm | 12.20 × 8.70 in * | 326 × 237 mm | not printed | 310 mm × 221 mm (p. 32; dimension drawings in section 8.7) | Lay it out |
| MTP1500 Unified Comfort | 15.6" | 382 × 241 mm | 15.04 × 9.49 in * | 398 × 257 mm | not printed | 382 mm × 241 mm (p. 32; dimension drawings in section 8.7) | Lay it out |
| MTP1900 Unified Comfort | 18.5" | 448 × 278 mm | 17.64 × 10.94 in * | 464 × 294 mm | not printed | 448 mm × 278 mm (p. 32; dimension drawings in section 8.7) | Lay it out |
| MTP2200 Unified Comfort | 21.5" | 513 × 315 mm | 20.20 × 12.40 in * | 529 × 331 mm | not printed | 513 mm × 315 mm (p. 32; dimension drawings in section 8.7) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: SIMATIC HMI Unified Comfort Panels Operating Instructions, TIA V18 (11/2022), A5E46641217-AD, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| MTP700 Unified Comfort | 17 mm | 17 mm |
| MTP1000 Unified Comfort | 16 mm | 16 mm |
| MTP1200 Unified Comfort | 16 mm | 16 mm |
| MTP1500 Unified Comfort | 16 mm | 16 mm |
| MTP1900 Unified Comfort | 16 mm | 16 mm |
| MTP2200 Unified Comfort | 16 mm | 16 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- 2 mm to 6 mm at the mounting cutout for IP65 or Type 4X/Type 12; permissible deviation from plane at the cutout 0.5 mm.
- Cutout tolerance
- +1/0 mm
- Mounting
- From the front, held by mounting clips; the manual ties IP65 to the clips being fitted at the positions it marks.
- Front rating, as the maker states it
- Front, when mounted: IP65 according to IEC 60529 and Type 4X/Type 12 (indoor use only, front face only) according to UL50, as the maker states it. The manual adds that the front protection holds only if the mounting seal lies flush against the cutout.
- Clearance around the terminal
- The manual's clearance drawing gives 15 mm (x), 50 mm (y) and 10 mm (z) around the device.
- Notes
- Width and height are reversed for portrait mounting, the manual says. The screen column is the display size the manual's technical specifications give. Each dimension drawing prints several depth figures, so no single depth is shown here. No corner radius is printed, and only millimetres.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Siemens series
SIMATIC HMI Basic Panels (2nd Generation) · SIMATIC HMI Comfort Panels · every series by screen size
SIMATIC, Siemens and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
SIMATIC HMI Unified Comfort Panels: questions
What is the panel cutout for the Siemens SIMATIC HMI Unified Comfort Panels MTP700 Unified Comfort?
197 × 141 mm (7.76 × 5.55 in), width by height, behind a bezel of 214 × 158 mm. The document prints it as: 197 mm × 141 mm.
What is the panel cutout for the Siemens SIMATIC HMI Unified Comfort Panels MTP1000 Unified Comfort?
264 × 189 mm (10.39 × 7.44 in), width by height, behind a bezel of 280 × 205 mm. The document prints it as: 264 mm × 189 mm.
What is the panel cutout for the Siemens SIMATIC HMI Unified Comfort Panels MTP1200 Unified Comfort?
310 × 221 mm (12.20 × 8.70 in), width by height, behind a bezel of 326 × 237 mm. The document prints it as: 310 mm × 221 mm.
What is the panel cutout for the Siemens SIMATIC HMI Unified Comfort Panels MTP1500 Unified Comfort?
382 × 241 mm (15.04 × 9.49 in), width by height, behind a bezel of 398 × 257 mm. The document prints it as: 382 mm × 241 mm.
What panel thickness does the Siemens SIMATIC HMI Unified Comfort Panels mount in?
The document states: 2 mm to 6 mm at the mounting cutout for IP65 or Type 4X/Type 12; permissible deviation from plane at the cutout 0.5 mm..
Can you cut the SIMATIC HMI Unified Comfort Panels opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.