Maple Systems HMI5000 and cMT Series panel cutout dimensions
The Maple Systems HMI5000 and cMT Series HMI5040B needs a panel cutout of 119 × 93 mm (4.69 × 3.66 in), width by height, and the cMT3218XP needs 532 × 340 mm (20.94 × 13.39 in). The table gives the opening for each of the 20 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.
Per model
Maple Systems HMI5000 and cMT Series cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| HMI5040B | 4.3" | 119 × 93 mm | 4.69 × 3.66 in * | 128 × 102 mm | 32 mm | 4.69 x 3.66 [119 x 93] (product page) | Lay it out |
| HMI5043Lv2, HMI5043LBv2 | 4.3" | 119 × 93 mm | 4.69 × 3.66 in * | not printed | not printed | 119 mm x 93 mm (Installation Guide) | |
| cMT2058XH | 4.3" | 119 × 93 mm | 4.69 × 3.66 in * | 128 × 102 mm | 32 mm | 4.69 x 3.66 [119 x 93] (product page) | Lay it out |
| cMT2058XHW | 4.3" | 119 × 93 mm | 4.69 × 3.66 in * | 128 × 102 mm | 32 mm | 4.69 x 3.66 [119 x 93] (product page) | Lay it out |
| HMI5070B | 7" | 192 × 138 mm | 7.56 × 5.43 in * | 200.4 × 146.5 mm | 34 mm | 7.56 x 5.43 [192 x 138] (product page) | Lay it out |
| cMT2078X | 7" | 192 × 138 mm | 7.56 × 5.43 in * | 200.3 × 146.3 mm | 35 mm | 7.56 x 5.43 [192.0 x 138.0] (product page) | Lay it out |
| cMT3072XH3 | 7" | 192 × 138 mm | 7.56 × 5.43 in * | 200.4 × 146.5 mm | 35 mm | 7.56 x 5.43 [192 x 138] (product page) | Lay it out |
| cMT3072XP | 7" | 192 × 138 mm | 7.56 × 5.43 in * | 200.3 × 146.3 mm | 36.9 mm | 7.56 x 5.43 [192 x 138] (product page) | Lay it out |
| cMT3092Xv2 | 9.7" | 250 × 192 mm | 9.84 × 7.56 in * | 260.6 × 203.1 mm | 44.5 mm | 9.84 x 7.56 [250 x 192] (product page) | Lay it out |
| cMT3108XH | 10.1" | 255 × 185 mm | 10.04 × 7.28 in * | 266 × 196 mm | 43 mm | 10.04 x 7.28 [255 x 185] (product page) | Lay it out |
| cMT3108XP | 10.1" | 255 × 185 mm | 10.04 × 7.28 in * | 266 × 196 mm | 43 mm | 10.04 x 7.28 [255 x 185] (product page) | Lay it out |
| HMI5100Bv3 | 10.1" | 260 × 202 mm | 10.24 × 7.95 in * | 271 × 213 mm | 36.5 mm | 10.24 x 7.95 [260 x 202] (product page) | Lay it out |
| cMT2108X2 | 10.1" | 260 × 202 mm | 10.24 × 7.95 in * | 271 × 213 mm | 38 mm | 10.24 x 7.95 [260 x 202] (product page) | Lay it out |
| cMT3102XV2R | 10.1" | 260 × 202 mm | 10.24 × 7.95 in * | 271 × 213 mm | 38 mm | 10.24 x 7.95 [260 x 202] (product page) | Lay it out |
| cMT2128X | 12.1" | 305 × 231 mm | 12.01 × 9.09 in * | 317 × 243 mm | 41 mm | 12.01 x 9.09 [305 x 231] (product page) | Lay it out |
| cMT2158XV2 | 15" | 352 × 279 mm | 13.86 × 10.98 in * | 366 × 293 mm | 48.2 mm | 13.86 x 10.98 [352 x 279] (product page) | Lay it out |
| cMT3152XV2 | 15" | 352 × 279 mm | 13.86 × 10.98 in * | 366 × 293 mm | 51.5 mm | 13.86 x 10.98 [352 x 279] (product page) | Lay it out |
| cMT2166X | 15.6" | 384 × 247 mm | 15.12 × 9.72 in * | 400 × 263 mm | 24.9 mm | 15.12 x 9.72 [384 x 247] (product page) | Lay it out |
| cMT3162XW | 15.6" | 384 × 247 mm | 15.12 × 9.72 in * | 400 × 263 mm | 26.1 mm | 15.12 x 9.72 [384 x 247] (product page) | Lay it out |
| cMT3218XP | 21.5" | 532 × 340 mm | 20.94 × 13.39 in * | 546 × 354 mm | 47.5 mm | 20.94 x 13.39" [532 x 340 mm] (product page) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: Maple Systems product pages, one per model (each row links its own), and the installation guides for the 4.3 in. units, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| HMI5040B | 9 mm | 9 mm |
| cMT2058XHW | 9 mm | 9 mm |
| cMT2058XH | 9 mm | 9 mm |
| HMI5070B | 8.4 mm | 8.5 mm |
| cMT2078X | 8.3 mm | 8.3 mm |
| cMT3072XH3 | 8.4 mm | 8.5 mm |
| cMT3072XP | 8.3 mm | 8.3 mm |
| cMT3092Xv2 | 10.6 mm | 11.1 mm |
| cMT3108XH | 11 mm | 11 mm |
| cMT3108XP | 11 mm | 11 mm |
| HMI5100Bv3 | 11 mm | 11 mm |
| cMT2108X2 | 11 mm | 11 mm |
| cMT3102XV2R | 11 mm | 11 mm |
| cMT2128X | 12 mm | 12 mm |
| cMT2158XV2 | 14 mm | 14 mm |
| cMT3152XV2 | 14 mm | 14 mm |
| cMT2166X | 16 mm | 16 mm |
| cMT3162XW | 16 mm | 16 mm |
| cMT3218XP | 14 mm | 14 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- Installation guides for the HMI5043Lv2, HMI5043LBv2 and cMT2058XH: maximum panel thickness 4.5 mm. The product pages print none.
- Mounting
- Panel mount. The installation guides for the 4.3 in. units call for a control box with enough stiffness, every fastening hole used with the provided brackets and screws, tightened to 2.6 to 3.9 lbf·in.
- Front rating, as the maker states it
- Product pages: "IP65 compliant front panel" and NEMA4 (HMI5070B); "IP66 Compliant Front Panel" and NEMA4 (cMT2058XHW, cMT2166X, cMT3092Xv2, cMT3108XH, cMT3162XW, cMT3218XP), most of them also "UL Type 4X (indoor use only)". Read the page for your model; the rows differ.
- Clearance around the terminal
- Installation guides for the 4.3 in. units: 15 mm top, 50 mm bottom, 15 mm sides, along the overlay.
- Notes
- The product pages print the cutout as inches, then millimetres in brackets, without naming which figure is the width; the first is given here as the width, the order the same pages use for the overall dimensions (W x H x D). No cutout tolerance or corner radius is printed. Depth is the overall depth of the unit. The HMI5043Lv2 and HMI5043LBv2 row comes from the installation guide, which prints the cutout only; the cMT2058XH guide prints the same cutout as its product page.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Maple Systems and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
HMI5000 and cMT Series: questions
What is the panel cutout for the Maple Systems HMI5000 and cMT Series HMI5040B?
119 × 93 mm (4.69 × 3.66 in), width by height, behind a bezel of 128 × 102 mm. The document prints it as: 4.69 x 3.66 [119 x 93].
What is the panel cutout for the Maple Systems HMI5000 and cMT Series cMT2058XHW?
119 × 93 mm (4.69 × 3.66 in), width by height, behind a bezel of 128 × 102 mm. The document prints it as: 4.69 x 3.66 [119 x 93].
What is the panel cutout for the Maple Systems HMI5000 and cMT Series HMI5043Lv2, HMI5043LBv2?
119 × 93 mm (4.69 × 3.66 in), width by height. The document prints it as: 119 mm x 93 mm.
What is the panel cutout for the Maple Systems HMI5000 and cMT Series cMT2058XH?
119 × 93 mm (4.69 × 3.66 in), width by height, behind a bezel of 128 × 102 mm. The document prints it as: 4.69 x 3.66 [119 x 93].
What panel thickness does the Maple Systems HMI5000 and cMT Series mount in?
The document states: Installation guides for the HMI5043Lv2, HMI5043LBv2 and cMT2058XH: maximum panel thickness 4.5 mm. The product pages print none..
Can you cut the HMI5000 and cMT Series opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.