Omron NB Series panel cutout dimensions
The Omron NB Series NB3Q-TW00B(-V1) / NB3Q-TW01B(-V1) needs a panel cutout of 119 × 93 mm (4.69 × 3.66 in), width by height, and the NB10W-TW01B(-V1) needs 258 × 200 mm (10.16 × 7.87 in). The table gives the opening for each of the 4 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Supported panel thickness: 1.6 to 4.8 mm.
Per model
Omron NB Series cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| NB3Q-TW00B(-V1) / NB3Q-TW01B(-V1) | 3.5" | 119 × 93 mm | 4.69 × 3.66 in * | 129.8 × 103.8 mm | 52.8 mm | 119 × 93 mm (section 2-1; outside dimensions in Appendix A) | Lay it out |
| NB5Q-TW00B(-V1) / NB5Q-TW01B(-V1) | 5.6" | 172.4 × 131 mm | 6.79 × 5.16 in * | 184 × 142 mm | 46 mm | 172.4 × 131 mm (section 2-1; outside dimensions in Appendix A) | Lay it out |
| NB7W-TW00B(-V1) / NB7W-TW01B(-V1) | 7" | 191 × 137 mm | 7.52 × 5.39 in * | 202 × 148 mm | 46 mm | 191 × 137 mm (section 2-1; outside dimensions in Appendix A) | Lay it out |
| NB10W-TW01B(-V1) | 10.1" | 258 × 200 mm | 10.16 × 7.87 in * | 268.8 × 210.8 mm | 54 mm | 258 × 200 mm (section 2-1; outside dimensions in Appendix A) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: NB-series Programmable Terminals Setup Manual, Cat. No. V107, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| NB3Q-TW00B(-V1) / NB3Q-TW01B(-V1) | 10.8 mm | 10.8 mm |
| NB5Q-TW00B(-V1) / NB5Q-TW01B(-V1) | 11.6 mm | 11 mm |
| NB7W-TW00B(-V1) / NB7W-TW01B(-V1) | 11 mm | 11 mm |
| NB10W-TW01B(-V1) | 10.8 mm | 10.8 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- 1.6 to 4.8 mm
- Cutout tolerance
- +0.5/-0 mm
- Mounting
- Inserted from the front of the panel and held by mounting brackets tightened evenly to 0.5 to 0.6 N·m.
- Front rating, as the maker states it
- Front operation part: IP65 (dust proof and drip proof only from the front of the panel).
- Notes
- Each row covers the -TW00B and -TW01B models and their -V1 versions; the NB10W comes as -TW01B only. The NB5Q screen is 5.6 inches, or 5.7 inches on the -V1 version. The manual prints no corner radius.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Omron series
Omron, Sysmac and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
NB Series: questions
What is the panel cutout for the Omron NB Series NB3Q-TW00B(-V1) / NB3Q-TW01B(-V1)?
119 × 93 mm (4.69 × 3.66 in), width by height, behind a bezel of 129.8 × 103.8 mm. The document prints it as: 119 × 93 mm.
What is the panel cutout for the Omron NB Series NB5Q-TW00B(-V1) / NB5Q-TW01B(-V1)?
172.4 × 131 mm (6.79 × 5.16 in), width by height, behind a bezel of 184 × 142 mm. The document prints it as: 172.4 × 131 mm.
What is the panel cutout for the Omron NB Series NB7W-TW00B(-V1) / NB7W-TW01B(-V1)?
191 × 137 mm (7.52 × 5.39 in), width by height, behind a bezel of 202 × 148 mm. The document prints it as: 191 × 137 mm.
What is the panel cutout for the Omron NB Series NB10W-TW01B(-V1)?
258 × 200 mm (10.16 × 7.87 in), width by height, behind a bezel of 268.8 × 210.8 mm. The document prints it as: 258 × 200 mm.
What panel thickness does the Omron NB Series mount in?
The document states: 1.6 to 4.8 mm.
Can you cut the NB Series opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.





