Red Lion CR3000 panel cutout dimensions

The Red Lion CR3000 CR3000 4 inch needs a panel cutout of 119.1 × 93 mm (4.69 × 3.66 in), width by height, and the CR3000 15 inch needs 340.1 × 265.7 mm (13.39 × 10.46 in). The table gives the opening for each of the 4 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.

Per model

Red Lion CR3000 cutout dimensions

Red Lion CR3000: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
CR3000 4 inch4.3"119.1 × 93 mm4.69 × 3.66 in *130.7 × 104.7 mm38.1 mm4.69 in. (119.13 mm) × 3.66 in. (92.96 mm); corner radius R.08 (R2.03) (p. 4; dimensions p. 3)Lay it out
CR3000 7 inch7"179.3 × 123.7 mm7.06 × 4.87 in *194 × 138 mm50.8 mm7.06 in. (179.32 mm) × 4.87 in. (123.7 mm); corner radius R.10 (R2.54) (p. 4; dimensions p. 3)Lay it out
CR3000 10 inch10.4"259.1 × 201.4 mm10.20 × 7.93 in *273.7 × 216 mm50.8 mm10.20 in. (259.08 mm) × 7.93 in. (201.42 mm); corner radius R.10 (R2.54) (p. 4; dimensions p. 3)Lay it out
CR3000 15 inch15"340.1 × 265.7 mm13.39 × 10.46 in *364.6 × 290.1 mm67.2 mm13.39 in. (340.11 mm) × 10.46 in. (265.68 mm); corner radius R.10 (R2.54) (p. 4; dimensions p. 3)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: CR3000 Installation Guide, Drawing No. LP1042, Revised 11/2023, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

CR3000 15 inchCR3000 10 inchCR3000 7 inchCR3000 4 inch
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
CR3000 4 inch11.5 mm11.7 mm
CR3000 7 inch14.7 mm14.3 mm
CR3000 10 inch14.7 mm14.6 mm
CR3000 15 inch24.5 mm24.4 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
Mounting surface 0.06 in (1.53 mm) minimum, 0.375 in (9.53 mm) maximum. Maximum 0.25 in (6.35 mm) with the stiffener plate that comes with the unit. For NEMA 4X / IP66 sealing the guide recommends the stiffener plate and a panel at least 0.06 in (1.52 mm) thick.
Cutout tolerance
±0.03 in (0.76 mm)
Mounting
From the front, with the stiffener plate fitted over the unit on the inside of the panel and all supplied clamps used. Clamp torque 4.0 lbf-in (0.45 Nm) on the 4, 7 and 10 inch units, 2.0 lbf-in (0.23 Nm) on the 15 inch. The panel must not flex more than 0.010 in for proper sealing.
Front rating, as the maker states it
Type 4X Indoor / IP66 enclosure rating (face only), as the maker states it.
Notes
The drawings are in inches with millimetres in brackets. The depth shown is the figure printed on the side view of each dimension drawing. No clearance figure is printed on the pages used. The guide is published on the site of HMS Networks, which Red Lion is part of.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other Red Lion series

CR1000 · Graphite · every series by screen size

Graphite, HMS Networks, Red Lion and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

CR3000: questions

What is the panel cutout for the Red Lion CR3000 CR3000 4 inch?

119.1 × 93 mm (4.69 × 3.66 in), width by height, behind a bezel of 130.7 × 104.7 mm. The document prints it as: 4.69 in. (119.13 mm) × 3.66 in. (92.96 mm).

What is the panel cutout for the Red Lion CR3000 CR3000 7 inch?

179.3 × 123.7 mm (7.06 × 4.87 in), width by height, behind a bezel of 194 × 138 mm. The document prints it as: 7.06 in. (179.32 mm) × 4.87 in. (123.7 mm).

What is the panel cutout for the Red Lion CR3000 CR3000 10 inch?

259.1 × 201.4 mm (10.20 × 7.93 in), width by height, behind a bezel of 273.7 × 216 mm. The document prints it as: 10.20 in. (259.08 mm) × 7.93 in. (201.42 mm).

What is the panel cutout for the Red Lion CR3000 CR3000 15 inch?

340.1 × 265.7 mm (13.39 × 10.46 in), width by height, behind a bezel of 364.6 × 290.1 mm. The document prints it as: 13.39 in. (340.11 mm) × 10.46 in. (265.68 mm).

What panel thickness does the Red Lion CR3000 mount in?

The document states: Mounting surface 0.06 in (1.53 mm) minimum, 0.375 in (9.53 mm) maximum. Maximum 0.25 in (6.35 mm) with the stiffener plate that comes with the unit. For NEMA 4X / IP66 sealing the guide recommends the stiffener plate and a panel at least 0.06 in (1.52 mm) thick..

Can you cut the CR3000 opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.