Schneider Electric Harmony ST6 panel cutout dimensions
The Schneider Electric Harmony ST6 HMIST6200 needs a panel cutout of 118.5 × 92.5 mm (4.67 × 3.64 in), width by height, and the HMIST6700 needs 394 × 250 mm (15.51 × 9.84 in). The table gives the opening for each of the 5 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.
Per model
Schneider Electric Harmony ST6 cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| HMIST6200 | 4.3" | 118.5 × 92.5 mm | 4.67 × 3.64 in * | 134.5 × 108.5 mm | 43 mm | 118.5 × 92.5 mm (p. 24 (spec), 42 (panel cut)) | Lay it out |
| HMIST6400 | 7" | 190 × 135 mm | 7.48 × 5.31 in * | 208 × 153 mm | 45 mm | 190 × 135 mm (p. 24 (spec), 42 (panel cut)) | Lay it out |
| HMIST6500 | 10.1" | 255 × 185 mm | 10.04 × 7.28 in * | 273 × 203 mm | 47 mm | 255 × 185 mm (p. 24 (spec), 42 (panel cut)) | Lay it out |
| HMIST6600 | 12.1" | 295 × 217 mm | 11.61 × 8.54 in * | 313 × 235 mm | 50 mm | 295 × 217 mm (p. 24 (spec), 42 (panel cut)) | Lay it out |
| HMIST6700 | 15.6" | 394 × 250 mm | 15.51 × 9.84 in * | 412 × 268 mm | 50 mm | 394 × 250 mm (p. 24 (spec), 42 (panel cut)) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: Harmony ST6 User Manual, EIO0000003527.04, 01/2024, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| HMIST6200 | 16 mm | 16 mm |
| HMIST6400 | 18 mm | 18 mm |
| HMIST6500 | 18 mm | 18 mm |
| HMIST6600 | 18 mm | 18 mm |
| HMIST6700 | 18 mm | 18 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- 1.6...5 mm (0.06...0.2 in). HMIST6200 on spring clips: 1.5...4 mm (0.06...0.16 in) in position 1, 4...6 mm (0.16...0.24 in) in position 2.
- Cutout tolerance
- +1/-0 mm (+0.04/-0 in)
- Mounting
- From the front, held by spring clips or installation fasteners.
- Front rating, as the maker states it
- IP65F, UL 50/50E, Type 1, Type 4X (indoor use only), Type 13, on the front panel when properly installed in an enclosure.
- Notes
- The panel cut table prints no corner radius.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Schneider Electric series
Harmony, Schneider Electric and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
Harmony ST6: questions
What is the panel cutout for the Schneider Electric Harmony ST6 HMIST6200?
118.5 × 92.5 mm (4.67 × 3.64 in), width by height, behind a bezel of 134.5 × 108.5 mm. The document prints it as: 118.5 × 92.5 mm.
What is the panel cutout for the Schneider Electric Harmony ST6 HMIST6400?
190 × 135 mm (7.48 × 5.31 in), width by height, behind a bezel of 208 × 153 mm. The document prints it as: 190 × 135 mm.
What is the panel cutout for the Schneider Electric Harmony ST6 HMIST6500?
255 × 185 mm (10.04 × 7.28 in), width by height, behind a bezel of 273 × 203 mm. The document prints it as: 255 × 185 mm.
What is the panel cutout for the Schneider Electric Harmony ST6 HMIST6600?
295 × 217 mm (11.61 × 8.54 in), width by height, behind a bezel of 313 × 235 mm. The document prints it as: 295 × 217 mm.
What panel thickness does the Schneider Electric Harmony ST6 mount in?
The document states: 1.6...5 mm (0.06...0.2 in). HMIST6200 on spring clips: 1.5...4 mm (0.06...0.16 in) in position 1, 4...6 mm (0.16...0.24 in) in position 2..
Can you cut the Harmony ST6 opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.