Pro-face SP5000 Series panel cutout dimensions
The Pro-face SP5000 Series SP-5400WA needs a panel cutout of 190 × 135 mm (7.48 × 5.31 in), width by height, and the SP-5800WC needs 465 × 319 mm (18.31 × 12.56 in). The table gives the opening for each of the 10 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Supported panel thickness: 1.6...5 mm (0.06...0.2 in). Check the current drawing for your exact catalog number before cutting.
Per model
Pro-face SP5000 Series cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| SP-5400WA | 7" | 190 × 135 mm | 7.48 × 5.31 in * | 203.6 × 148.6 mm | 36 mm | 190 mm (7.48 in) × 135 mm (5.31 in) (Spec table p.53; Panel Cut Dimensions p.92-93) | Lay it out |
| SP-5500WA | 10.1" | 255 × 185 mm | 10.04 × 7.28 in * | 268.5 × 198.5 mm | 67 mm | 255 mm (10.04 in) × 185 mm (7.28 in) (Spec table p.53; Panel Cut Dimensions p.92-93) | Lay it out |
| SP-5500TP | 10.4" | 259 × 201 mm | 10.20 × 7.91 in * | 272.5 × 214.5 mm | 67 mm | 259 mm (10.2 in) × 201 mm (7.91 in) (Spec table p.52; Panel Cut Dimensions p.92) | Lay it out |
| SP-5600WA | 12.1" | 295 × 217 mm | 11.61 × 8.54 in * | 308.5 × 230.5 mm | 67 mm | 295 mm (11.61 in) × 217 mm (8.54 in) (Spec table p.53; Panel Cut Dimensions p.92-93) | Lay it out |
| SP-5600TA | 12.1" | 301.5 × 227.5 mm | 11.87 × 8.96 in * | 315 × 241 mm | 67 mm | 301.5 mm (11.87 in) × 227.5 mm (8.96 in) (Spec table p.53; Panel Cut Dimensions p.92-93) | Lay it out |
| SP-5600TP | 12.1" | 301.5 × 227.5 mm | 11.87 × 8.96 in * | 315 × 241 mm | 67 mm | 301.5 mm (11.87 in) × 227.5 mm (8.96 in) (Spec table p.52; Panel Cut Dimensions p.92) | Lay it out |
| SP-5660TP | 12.1" | 301.5 × 227.5 mm | 11.87 × 8.96 in * | not printed | not printed | 301.5 mm (11.87 in) × 227.5 mm (8.96 in) (Spec table p.52; Panel Cut Dimensions p.92) | |
| SP-5700TP | 15" | 383.5 × 282.5 mm | 15.10 × 11.12 in * | 397 × 296 mm | 67 mm | 383.5 mm (15.1 in) × 282.5 mm (11.12 in) (Spec table p.52; Panel Cut Dimensions p.92) | Lay it out |
| SP-5700WC | 15.6" | 396 × 277 mm | 15.59 × 10.91 in * | 414 × 295 mm | 69 mm | 396 mm (15.59 in) × 277 mm (10.91 in) (Spec table p.52; Panel Cut Dimensions p.92) | Lay it out |
| SP-5800WC | 18.5" | 465 × 319 mm | 18.31 × 12.56 in * | 483 × 337 mm | 69 mm | 465 mm (18.31 in) × 319 mm (12.56 in) (Spec table p.52; Panel Cut Dimensions p.92) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: SP5000 Series Hardware Manual, SP5000-MM01-EN, 02/2022, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| SP-5400WA | 13.6 mm | 13.6 mm |
| SP-5500WA | 13.5 mm | 13.5 mm |
| SP-5500TP | 13.5 mm | 13.5 mm |
| SP-5600WA | 13.5 mm | 13.5 mm |
| SP-5600TA | 13.5 mm | 13.5 mm |
| SP-5600TP | 13.5 mm | 13.5 mm |
| SP-5700TP | 13.5 mm | 13.5 mm |
| SP-5700WC | 18 mm | 18 mm |
| SP-5800WC | 18 mm | 18 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- 1.6...5 mm (0.06...0.2 in)
- Cutout tolerance
- +1/-0 mm (+0.04/-0 in)
- Corner radius
- below R3 (R0.12 in)
- Mounting
- From the front, held by installation fasteners against a gasket.
- Front rating, as the maker states it
- SP-5400WA, SP-5500WA, SP-5600WA and SP-5600TA: IP66F, IP67F, Type 1, Type 4X (indoor use only), Type 13. TP and WC models: IP65F, IP67F, Type 1 with the factory-fitted front USB cover; IP66F, IP67F, Type 1, Type 4X (indoor use only), Type 13 with the optional front USB cover. On the front panel, when properly installed in an enclosure and not using the front USB port.
- Notes
- In the manual's panel cut table A is the width and B the height. The table here is the display module, with its depth from the specification table; the box module attaches behind it. The manual prints no outside dimensions for the SP-5660TP.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Pro-face series
Pro-face, Schneider Electric and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
SP5000 Series: questions
What is the panel cutout for the Pro-face SP5000 Series SP-5400WA?
190 × 135 mm (7.48 × 5.31 in), width by height, behind a bezel of 203.6 × 148.6 mm. The document prints it as: 190 mm (7.48 in) × 135 mm (5.31 in).
What is the panel cutout for the Pro-face SP5000 Series SP-5500WA?
255 × 185 mm (10.04 × 7.28 in), width by height, behind a bezel of 268.5 × 198.5 mm. The document prints it as: 255 mm (10.04 in) × 185 mm (7.28 in).
What is the panel cutout for the Pro-face SP5000 Series SP-5500TP?
259 × 201 mm (10.20 × 7.91 in), width by height, behind a bezel of 272.5 × 214.5 mm. The document prints it as: 259 mm (10.2 in) × 201 mm (7.91 in).
What is the panel cutout for the Pro-face SP5000 Series SP-5600WA?
295 × 217 mm (11.61 × 8.54 in), width by height, behind a bezel of 308.5 × 230.5 mm. The document prints it as: 295 mm (11.61 in) × 217 mm (8.54 in).
What panel thickness does the Pro-face SP5000 Series mount in?
The document states: 1.6...5 mm (0.06...0.2 in).
Can you cut the SP5000 Series opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.