Beijer Electronics X2 base panel cutout dimensions
The Beijer Electronics X2 base X2 base 5 needs a panel cutout of 160.7 × 93 mm (6.33 × 3.66 in), width by height, and the X2 base 10 needs 274.3 × 176.6 mm (10.80 × 6.95 in). The table gives the opening for each of the 3 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Supported panel thickness: Maximum installation plate thickness 5.5 mm (base 5) or 6.5 mm (base 7 and base 10)..
Per model
Beijer Electronics X2 base cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| X2 base 5 | 5" | 160.7 × 93 mm | 6.33 × 3.66 in * | 170.4 × 106.8 mm | 41.7 mm | 160.7 × 93 mm; tolerance ±1 mm (manual MAEN180, technical data) | Lay it out |
| X2 base 7 | 7" | 185.8 × 135.8 mm | 7.31 × 5.35 in * | 196 × 146 mm | 44.7 mm | 185.8 × 135.8 mm (manual MAEN181, technical data) | Lay it out |
| X2 base 10 | 10" | 274.3 × 176.6 mm | 10.80 × 6.95 in * | 284.3 × 186.6 mm | 44.7 mm | 274.3 × 176.6 mm; tolerance ±0.8 mm (manual MAEN182, technical data) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: X2 base Hardware and Installation Manuals, MAEN180, MAEN181 and MAEN182, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| X2 base 5 | 9.7 mm | 13.8 mm |
| X2 base 7 | 10.2 mm | 10.2 mm |
| X2 base 10 | 10 mm | 10 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- Maximum installation plate thickness 5.5 mm (base 5) or 6.5 mm (base 7 and base 10).
- Mounting
- Installed into the cutout from the front and fastened from behind; each manual gives the screw torque.
- Front rating, as the maker states it
- Front panel seal IP 65, rear panel seal IP 20.
- Clearance around the terminal
- Mounting depth including clearance: 141.7 mm (base 5), 145 mm (base 7 and base 10).
- Notes
- The first generation, before the v2 models. The screen size is the number in the model name, which the manual's naming table gives as the size in inches. The depth shown is the mounting depth the manual prints. The base 7 table prints no cutout tolerance.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Beijer Electronics series
Beijer Electronics and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
X2 base: questions
What is the panel cutout for the Beijer Electronics X2 base X2 base 5?
160.7 × 93 mm (6.33 × 3.66 in), width by height, behind a bezel of 170.4 × 106.8 mm. The document prints it as: 160.7 × 93 mm.
What is the panel cutout for the Beijer Electronics X2 base X2 base 7?
185.8 × 135.8 mm (7.31 × 5.35 in), width by height, behind a bezel of 196 × 146 mm. The document prints it as: 185.8 × 135.8 mm.
What is the panel cutout for the Beijer Electronics X2 base X2 base 10?
274.3 × 176.6 mm (10.80 × 6.95 in), width by height, behind a bezel of 284.3 × 186.6 mm. The document prints it as: 274.3 × 176.6 mm.
What panel thickness does the Beijer Electronics X2 base mount in?
The document states: Maximum installation plate thickness 5.5 mm (base 5) or 6.5 mm (base 7 and base 10)..
Can you cut the X2 base opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.