Allen-Bradley PanelView Plus 7 Standard panel cutout dimensions
The Allen-Bradley PanelView Plus 7 Standard 4.3 in. (2711P-T4W21D8S, 2711P-T4W22D8S) needs a panel cutout of 117 × 92 mm (4.61 × 3.62 in), width by height, and the 15 in. (2711P-T15C21D8S, 2711P-T15C22D8S) needs 353 × 290 mm (13.90 × 11.42 in). The table gives the opening for each of the 7 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below.
Per model
Allen-Bradley PanelView Plus 7 Standard cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| 4.3 in. (2711P-T4W21D8S, 2711P-T4W22D8S) | 4.3" | 117 × 92 mm | 4.61 × 3.62 in * | 135 × 110 mm | 50.14 mm | 117 mm (4.61 in.) × 92 mm (3.62 in.) (UM007 p. 25, Table 12) | Lay it out |
| 5.7 in. (2711P-T6C21D8S, 2711P-T6C22D8S) | 5.7" | 156 × 123 mm | 6.14 × 4.84 in * | 176 × 152 mm | 50.14 mm | 156 mm (6.14 in.) × 123 mm (4.84 in.) (UM007 p. 25, Table 12) | Lay it out |
| 6.5 in. (2711P-T7C21D8S, 2711P-T7C22D8S) | 6.5" | 184 × 142 mm | 7.24 × 5.59 in * | 212 × 170 mm | 50.14 mm | 184 mm (7.24 in.) × 142 mm (5.59 in.) (UM007 p. 25, Table 12) | Lay it out |
| 9 in. (2711P-T9W21D8S, 2711P-T9W22D8S) | 9" | 252 × 162 mm | 9.92 × 6.38 in * | 280 × 190 mm | 50.14 mm | 252 mm (9.92 in.) × 162 mm (6.38 in.) (UM007 p. 25, Table 12) | Lay it out |
| 10.4 in. (2711P-T10C21D8S, 2711P-T10C22D8S) | 10.4" | 269 × 224 mm | 10.59 × 8.82 in * | 297 × 252 mm | 50.14 mm | 269 mm (10.59 in.) × 224 mm (8.82 in.) (UM007 p. 25, Table 12) | Lay it out |
| 12.1 in. (2711P-T12W21D8S, 2711P-T12W22D8S) | 12.1" | 312 × 218 mm | 12.28 × 8.58 in * | 340 × 246 mm | 50.14 mm | 312 mm (12.28 in.) × 218 mm (8.58 in.) (UM007 p. 25, Table 12) | Lay it out |
| 15 in. (2711P-T15C21D8S, 2711P-T15C22D8S) | 15" | 353 × 290 mm | 13.90 × 11.42 in * | 381 × 318 mm | 50.14 mm | 353 mm (13.90 in.) × 290 mm (11.42 in.) (UM007 p. 25, Table 12) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: PanelView Plus 7 Standard Terminals User Manual, 2711P-UM007I-EN-P, March 2023 (cutout, Table 12); bezel and depth from Technical Data 2711P-TD008J-EN-P, March 2023 (Table 6), read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| 4.3 in. (2711P-T4W21D8S, 2711P-T4W22D8S) | 18 mm | 18 mm |
| 5.7 in. (2711P-T6C21D8S, 2711P-T6C22D8S) | 20 mm | 29 mm |
| 6.5 in. (2711P-T7C21D8S, 2711P-T7C22D8S) | 28 mm | 28 mm |
| 9 in. (2711P-T9W21D8S, 2711P-T9W22D8S) | 28 mm | 28 mm |
| 10.4 in. (2711P-T10C21D8S, 2711P-T10C22D8S) | 28 mm | 28 mm |
| 12.1 in. (2711P-T12W21D8S, 2711P-T12W22D8S) | 28 mm | 28 mm |
| 15 in. (2711P-T15C21D8S, 2711P-T15C22D8S) | 28 mm | 28 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- 1.5...4.8 mm (0.060...0.188 in.)
- Mounting
- From the front, held by mounting levers. The manual says to mark the cutout with the template shipped with the terminal.
- Front rating, as the maker states it
- NEMA and UL Type 12, 13, 4X (indoor use only), also rated IP54 or IP66 as Classified by UL, in the maker's technical data.
- Clearance around the terminal
- Top 51 mm (2 in.); bottom 51 mm (2 in.); side 25 mm (1 in.), or 51 mm (2 in.) on the side where an SD card is inserted; back 0.
- Notes
- The manual's cutout table gives height first, then width; this page gives width × height. The depth shown is the mounted depth, behind the panel; the overall depth is 56.5 mm (2.22 in.) and the front of the bezel extends less than 6.36 mm (0.25 in.) from the front of the panel. The manual prints no cutout tolerance and no corner radius. The catalog numbers beside each size are from the manual's product selection table.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Allen-Bradley series
PanelView Plus 7 Performance · PanelView 800 · PanelView 5510 · PanelView 5310 · every series by screen size
Allen-Bradley, PanelView, Rockwell Automation and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
PanelView Plus 7 Standard: questions
What is the panel cutout for the Allen-Bradley PanelView Plus 7 Standard 4.3 in. (2711P-T4W21D8S, 2711P-T4W22D8S)?
117 × 92 mm (4.61 × 3.62 in), width by height, behind a bezel of 135 × 110 mm. The document prints it as: 117 mm (4.61 in.) × 92 mm (3.62 in.).
What is the panel cutout for the Allen-Bradley PanelView Plus 7 Standard 5.7 in. (2711P-T6C21D8S, 2711P-T6C22D8S)?
156 × 123 mm (6.14 × 4.84 in), width by height, behind a bezel of 176 × 152 mm. The document prints it as: 156 mm (6.14 in.) × 123 mm (4.84 in.).
What is the panel cutout for the Allen-Bradley PanelView Plus 7 Standard 6.5 in. (2711P-T7C21D8S, 2711P-T7C22D8S)?
184 × 142 mm (7.24 × 5.59 in), width by height, behind a bezel of 212 × 170 mm. The document prints it as: 184 mm (7.24 in.) × 142 mm (5.59 in.).
What is the panel cutout for the Allen-Bradley PanelView Plus 7 Standard 9 in. (2711P-T9W21D8S, 2711P-T9W22D8S)?
252 × 162 mm (9.92 × 6.38 in), width by height, behind a bezel of 280 × 190 mm. The document prints it as: 252 mm (9.92 in.) × 162 mm (6.38 in.).
What panel thickness does the Allen-Bradley PanelView Plus 7 Standard mount in?
The document states: 1.5...4.8 mm (0.060...0.188 in.).
Can you cut the PanelView Plus 7 Standard opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.