Mitsubishi Electric GOT2000 GT25 panel cutout dimensions
The Mitsubishi Electric GOT2000 GT25 GT2505-V needs a panel cutout of 153 × 121 mm (6.02 × 4.76 in), width by height, and the GT2512-S needs 302 × 228 mm (11.89 × 8.98 in). The table gives the opening for each of the 11 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.
Per model
Mitsubishi Electric GOT2000 GT25 cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| GT2505-V | 5.7" | 153 × 121 mm | 6.02 × 4.76 in * | 164 × 139 mm | 53.5 mm | 153 × 121 mm; tolerance +2/0 mm (+0.08/0 in) (spec p.90, panel cut p.176) | Lay it out |
| GT2507-W | 7" | 180.5 × 133.5 mm | 7.11 × 5.26 in * | 189 × 142 mm | 48 mm | 180.5 × 133.5 mm; tolerance +1/0 mm (+0.04/0 in) (spec p.80, panel cut p.174) | Lay it out |
| GT2507T-W | 7" | 197 × 141 mm | 7.76 × 5.55 in * | 214 × 158 mm | 55 mm | 197 × 141 mm; tolerance +1/0 mm (+0.04/0 in) (spec p.82, panel cut p.175) | Lay it out |
| GT2508F-V (open frame) | 8.4" | 194 × 158 mm | 7.64 × 6.22 in * | not printed | 54 mm | 194 × 158 mm; tolerance +2/0 mm (+0.08/0 in) (spec p.88, panel cut p.177) | |
| GT2508-V | 8.4" | 227 × 176 mm | 8.94 × 6.93 in * | 241 × 194 mm | 52 mm | 227 × 176 mm; tolerance +2/0 mm (+0.08/0 in) (spec p.88, panel cut p.176) | Lay it out |
| GT2510-WX | 10.1" | 243.5 × 185.5 mm | 9.59 × 7.30 in * | 252 × 194 mm | 48 mm | 243.5 × 185.5 mm; tolerance +1/0 mm (+0.04/0 in) (spec p.78, panel cut p.174) | Lay it out |
| GT2510F-V (open frame) | 10.4" | 234 × 187 mm | 9.21 × 7.36 in * | not printed | 54 mm | 234 × 187 mm; tolerance +2/0 mm (+0.08/0 in) (spec p.86, panel cut p.177) | |
| GT2510-V | 10.4" | 289 × 200 mm | 11.38 × 7.87 in * | 303 × 218 mm | 52 mm | 289 × 200 mm; tolerance +2/0 mm (+0.08/0 in) (spec p.86, panel cut p.176) | Lay it out |
| GT2512F-S (open frame) | 12.1" | 269 × 214 mm | 10.59 × 8.43 in * | not printed | 54 mm | 269 × 214 mm; tolerance +2/0 mm (+0.08/0 in) (spec p.84, panel cut p.177) | |
| GT2512-WX | 12.1" | 290.5 × 210.5 mm | 11.44 × 8.29 in * | 299 × 219 mm | 48 mm | 290.5 × 210.5 mm; tolerance +1/0 mm (+0.04/0 in) (spec p.76, panel cut p.174) | Lay it out |
| GT2512-S | 12.1" | 302 × 228 mm | 11.89 × 8.98 in * | 316 × 246 mm | 52 mm | 302 × 228 mm; tolerance +2/0 mm (+0.08/0 in) (spec p.84, panel cut p.176) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: GOT2000 Series User's Manual (Hardware), SH-081194ENG, version AX, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| GT2505-V | 11 mm | 18 mm |
| GT2507-W | 8.5 mm | 8.5 mm |
| GT2507T-W | 17 mm | 17 mm |
| GT2508-V | 14 mm | 18 mm |
| GT2510-WX | 8.5 mm | 8.5 mm |
| GT2510-V | 14 mm | 18 mm |
| GT2512-WX | 8.5 mm | 8.5 mm |
| GT2512-S | 14 mm | 18 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- 1.6 to 4 mm (0.06 to 0.16 in). Open-frame GT2512F-S, GT2510F-V and GT2508F-V: 1.5 to 4 mm (0.06 to 0.16 in).
- Mounting
- Installation fittings. The open-frame models (GT25xxF) sit flush with the control panel and are fastened to M4 studs welded to it (manual section 6.3).
- Front rating, as the maker states it
- Front: IP67F (GT2507T-W: IP66F/IP67F). Inside the control panel: IP2X. The specification tables qualify these with footnotes.
- Notes
- The outside dimensions of an open-frame model are its frame behind the panel, not a bezel, so none is shown for those three. The Handy GOT models GT2506HS-V and GT2505HS-V are not panel-cut models. The manual prints no corner radius.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Mitsubishi Electric series
GOT SIMPLE GS21 and GS25 · GOT2000 GT27 · GOT2000 GT21 · every series by screen size
GOT, Mitsubishi Electric and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
GOT2000 GT25: questions
What is the panel cutout for the Mitsubishi Electric GOT2000 GT25 GT2505-V?
153 × 121 mm (6.02 × 4.76 in), width by height, behind a bezel of 164 × 139 mm. The document prints it as: 153 × 121 mm.
What is the panel cutout for the Mitsubishi Electric GOT2000 GT25 GT2507-W?
180.5 × 133.5 mm (7.11 × 5.26 in), width by height, behind a bezel of 189 × 142 mm. The document prints it as: 180.5 × 133.5 mm.
What is the panel cutout for the Mitsubishi Electric GOT2000 GT25 GT2507T-W?
197 × 141 mm (7.76 × 5.55 in), width by height, behind a bezel of 214 × 158 mm. The document prints it as: 197 × 141 mm.
What is the panel cutout for the Mitsubishi Electric GOT2000 GT25 GT2508F-V (open frame)?
194 × 158 mm (7.64 × 6.22 in), width by height. The document prints it as: 194 × 158 mm.
What panel thickness does the Mitsubishi Electric GOT2000 GT25 mount in?
The document states: 1.6 to 4 mm (0.06 to 0.16 in). Open-frame GT2512F-S, GT2510F-V and GT2508F-V: 1.5 to 4 mm (0.06 to 0.16 in)..
Can you cut the GOT2000 GT25 opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.