Beijer Electronics X2 pro panel cutout dimensions
The Beijer Electronics X2 pro X2 pro 7 needs a panel cutout of 189 × 128 mm (7.44 × 5.04 in), width by height, and the X2 pro 15 needs 394 × 270 mm (15.51 × 10.63 in). The table gives the opening for each of the 5 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.
Per model
Beijer Electronics X2 pro cutout dimensions
| Model | Screen | Cutout W × H, mm | Cutout W × H, in | Bezel W × H | Depth | As the document prints it | Cutout designer |
|---|---|---|---|---|---|---|---|
| X2 pro 7 | 7" | 189 × 128 mm | 7.44 × 5.04 in * | 204 × 143 mm | 43 mm | 189 × 128 mm (manual MAEN214, technical data) | Lay it out |
| X2 pro 7 2eth | 7" | 189 × 128 mm | 7.44 × 5.04 in * | 204 × 143 mm | 43 mm | 189 × 128 mm (manual MAEN265, technical data) | Lay it out |
| X2 pro 10 | 10.1" | 275 × 177 mm | 10.83 × 6.97 in * | 292 × 194 mm | 45 mm | 275 × 177 mm (manual MAEN220, technical data) | Lay it out |
| X2 pro 12 | 12.1" | 324 × 226 mm | 12.76 × 8.90 in * | 340 × 242 mm | 49 mm | 324 × 226 mm (manual MAEN222, technical data) | Lay it out |
| X2 pro 15 | 15.4" | 394 × 270 mm | 15.51 × 10.63 in * | 410 × 286 mm | 53 mm | 394 × 270 mm (manual MAEN224, technical data) | Lay it out |
* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".
Source: X2 pro Hardware and Installation Manuals, MAEN214, MAEN265, MAEN220, MAEN222 and MAEN224, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.
To one scale
The openings side by side
Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.
| Model | Bezel wider than the cutout by | Taller by |
|---|---|---|
| X2 pro 7 | 15 mm | 15 mm |
| X2 pro 7 2eth | 15 mm | 15 mm |
| X2 pro 10 | 17 mm | 17 mm |
| X2 pro 12 | 16 mm | 16 mm |
| X2 pro 15 | 16 mm | 16 mm |
Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.
From the maker's documents
Panel thickness, mounting and front rating
- Panel thickness
- Maximum installation plate thickness 11 mm (pro 7 and pro 7 2eth), 7 mm (pro 10), 8 mm (pro 12 and pro 15).
- Mounting
- Installed into the cutout from the front and fastened from behind; each manual gives the screw torque.
- Front rating, as the maker states it
- Front panel seal IP 65, rear panel seal IP 20.
- Clearance around the terminal
- Mounting depth including clearance: 143 mm (pro 7 and pro 7 2eth), 145 mm (pro 10), 149 mm (pro 12), 153 mm (pro 15).
- Notes
- The depth shown is the mounting depth the manual prints. The technical data tables print no cutout tolerance. Each size has its own manual, linked from its row.
A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.
In the enclosure
What the opening needs from the door
Room on the door
The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.
Heat and the seal
A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.
Need the opening cut for you?
The cutout, cut into a stainless door at the factory.
Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.
Same maker
Other Beijer Electronics series
Beijer Electronics and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.
Asked and answered
X2 pro: questions
What is the panel cutout for the Beijer Electronics X2 pro X2 pro 7?
189 × 128 mm (7.44 × 5.04 in), width by height, behind a bezel of 204 × 143 mm. The document prints it as: 189 × 128 mm.
What is the panel cutout for the Beijer Electronics X2 pro X2 pro 7 2eth?
189 × 128 mm (7.44 × 5.04 in), width by height, behind a bezel of 204 × 143 mm. The document prints it as: 189 × 128 mm.
What is the panel cutout for the Beijer Electronics X2 pro X2 pro 10?
275 × 177 mm (10.83 × 6.97 in), width by height, behind a bezel of 292 × 194 mm. The document prints it as: 275 × 177 mm.
What is the panel cutout for the Beijer Electronics X2 pro X2 pro 12?
324 × 226 mm (12.76 × 8.90 in), width by height, behind a bezel of 340 × 242 mm. The document prints it as: 324 × 226 mm.
What panel thickness does the Beijer Electronics X2 pro mount in?
The document states: Maximum installation plate thickness 11 mm (pro 7 and pro 7 2eth), 7 mm (pro 10), 8 mm (pro 12 and pro 15)..
Can you cut the X2 pro opening into a stainless enclosure?
Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.