Red Lion Graphite panel cutout dimensions

The Red Lion Graphite G07 needs a panel cutout of 179.3 × 123.7 mm (7.06 × 4.87 in), width by height, and the G15 needs 340.1 × 265.6 mm (13.39 × 10.46 in). The table gives the opening for each of the 5 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.

Per model

Red Lion Graphite cutout dimensions

Red Lion Graphite: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
G077"179.3 × 123.7 mm7.06 × 4.87 in *195.5 × 139.9 mm50.8 mm7.060 in. (179.3 mm) × 4.869 in. (123.7 mm) (p. 4)Lay it out
G099"239.3 × 148.1 mm9.42 × 5.83 in *255.6 × 164.4 mm52.4 mm9.423 in. (239.3 mm) × 5.832 in. (148.1 mm) (p. 5)Lay it out
G1010"259 × 201.4 mm10.20 × 7.93 in *275.2 × 217.7 mm52.4 mm10.197 in. (259.0 mm) × 7.931 in. (201.4 mm) (p. 5)Lay it out
G1212"291 × 192 mm11.46 × 7.56 in *307.3 × 208.3 mm52.4 mm11.458 in. (291.0 mm) × 7.561 in. (192.0 mm) (p. 5)Lay it out
G1515"340.1 × 265.6 mm13.39 × 10.46 in *356.3 × 281.8 mm54.3 mm13.390 in. (340.1 mm) × 10.457 in. (265.6 mm) (p. 6)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: Graphite Series Hardware Guide, Bulletin GRAPH-N, Drawing No. LP0918, Revised 10/2026, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

G15G12G10G09G07
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
G0716.2 mm16.2 mm
G0916.3 mm16.3 mm
G1016.2 mm16.3 mm
G1216.3 mm16.3 mm
G1516.2 mm16.2 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
Maximum 0.188 in (4.78 mm) with the removable foot, or 0.375 in (9.53 mm) without it. For NEMA 4X/IP66 sealing the guide recommends a steel panel at least 0.125 in (3.17 mm) thick.
Cutout tolerance
±.059 in (±1.5 mm)
Corner radius
4X R.10 (2.5) MAX.
Mounting
From the front, sealed by the gasket provided. Maximum mounting screw torque 6.0 lbf-in (0.68 Nm).
Front rating, as the maker states it
Type 4X Indoor / IP66 enclosure rating (face only) for all models, and Type 4X Outdoor (face only) for the GxxS models, as the maker states it. The rear of the unit is IP20.
Notes
The drawings are in inches with millimetres in brackets. One cutout per size: the C, S and R versions of a size share it. The depth shown is the figure printed on the side view; a plug-in module adds to it. The guide is published on the site of HMS Networks, which Red Lion is part of.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other Red Lion series

CR3000 · CR1000 · every series by screen size

Graphite, HMS Networks, Red Lion and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

Graphite: questions

What is the panel cutout for the Red Lion Graphite G07?

179.3 × 123.7 mm (7.06 × 4.87 in), width by height, behind a bezel of 195.5 × 139.9 mm. The document prints it as: 7.060 in. (179.3 mm) × 4.869 in. (123.7 mm).

What is the panel cutout for the Red Lion Graphite G09?

239.3 × 148.1 mm (9.42 × 5.83 in), width by height, behind a bezel of 255.6 × 164.4 mm. The document prints it as: 9.423 in. (239.3 mm) × 5.832 in. (148.1 mm).

What is the panel cutout for the Red Lion Graphite G10?

259 × 201.4 mm (10.20 × 7.93 in), width by height, behind a bezel of 275.2 × 217.7 mm. The document prints it as: 10.197 in. (259.0 mm) × 7.931 in. (201.4 mm).

What is the panel cutout for the Red Lion Graphite G12?

291 × 192 mm (11.46 × 7.56 in), width by height, behind a bezel of 307.3 × 208.3 mm. The document prints it as: 11.458 in. (291.0 mm) × 7.561 in. (192.0 mm).

What panel thickness does the Red Lion Graphite mount in?

The document states: Maximum 0.188 in (4.78 mm) with the removable foot, or 0.375 in (9.53 mm) without it. For NEMA 4X/IP66 sealing the guide recommends a steel panel at least 0.125 in (3.17 mm) thick..

Can you cut the Graphite opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.