Siemens SIMATIC HMI Basic Panels (2nd Generation) panel cutout dimensions

The Siemens SIMATIC HMI Basic Panels (2nd Generation) KTP400 Basic needs a panel cutout of 123 × 99 mm (4.84 × 3.90 in), width by height, and the KTP1200 Basic needs 310 × 221 mm (12.20 × 8.70 in). The table gives the opening for each of the 4 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Check the current drawing for your exact catalog number before cutting.

Per model

Siemens SIMATIC HMI Basic Panels (2nd Generation) cutout dimensions

Siemens SIMATIC HMI Basic Panels (2nd Generation): panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
KTP400 Basic4.3"123 × 99 mm4.84 × 3.90 in *140 × 116 mmnot printed123 mm × 99 mm (p. 26; dimension drawings in section 8.6)Lay it out
KTP700 Basic7"197 × 141 mm7.76 × 5.55 in *214 × 158 mm39 mm197 mm × 141 mm (p. 26; dimension drawings in section 8.6)Lay it out
KTP900 Basic9"251 × 166 mm9.88 × 6.54 in *267 × 182 mm40 mm251 mm × 166 mm (p. 26; dimension drawings in section 8.6)Lay it out
KTP1200 Basic12"310 × 221 mm12.20 × 8.70 in *330 × 245 mm55 mm310 mm × 221 mm (p. 26; dimension drawings in section 8.6)Lay it out

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: SIMATIC HMI Basic Panels 2nd Generation Operating Instructions, 10/2024, A5E33293231-AE, read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

KTP1200 BasicKTP900 BasicKTP700 BasicKTP400 Basic
Door covered by the bezel
ModelBezel wider than the cutout byTaller by
KTP400 Basic17 mm17 mm
KTP700 Basic17 mm17 mm
KTP900 Basic16 mm16 mm
KTP1200 Basic20 mm24 mm

Totals across both sides. Where the terminal sits centred on its cutout, half of each figure lands on the door at each edge; the drawing in the document shows whether it does.

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
2 mm to 6 mm at the mounting cutout for IP65 or Type 4X/12; permissible deviation from plane at the cutout 0.5 mm.
Cutout tolerance
+1/0 mm
Mounting
From the front, held by mounting clips: 4 on the KTP400 Basic, 7 on the KTP700 Basic, 10 on the KTP900 Basic and 12 on the KTP1200 Basic.
Front rating, as the maker states it
Front, when mounted: IP65 according to IEC 60529 and Type 4X/12 (indoor use only, front face only) according to UL50E, as the maker states it.
Clearance around the terminal
The manual's clearance drawing gives 15 mm (x), 50 mm (y) and 10 mm (z) around the device.
Notes
Landscape mounting; for portrait mounting the manual swaps width and height. The cutout table names the sizes KTP400, KTP700, KTP900 and KTP1200, so the KTP700 Basic DP and KTP1200 Basic DP use the same rows. The manual lists these cutouts as compatible with those of the TP700 Comfort (KTP700 Basic), the TP900 Comfort (KTP900 Basic) and the TP1200 Comfort (KTP1200 Basic). The depth shown is the housing behind the front; the front itself stands 6.2 mm proud of the panel in the drawings. No corner radius is printed, and only millimetres.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other Siemens series

SIMATIC HMI Comfort Panels · SIMATIC HMI Unified Comfort Panels · every series by screen size

SIMATIC, Siemens and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

SIMATIC HMI Basic Panels (2nd Generation): questions

What is the panel cutout for the Siemens SIMATIC HMI Basic Panels (2nd Generation) KTP400 Basic?

123 × 99 mm (4.84 × 3.90 in), width by height, behind a bezel of 140 × 116 mm. The document prints it as: 123 mm × 99 mm.

What is the panel cutout for the Siemens SIMATIC HMI Basic Panels (2nd Generation) KTP700 Basic?

197 × 141 mm (7.76 × 5.55 in), width by height, behind a bezel of 214 × 158 mm. The document prints it as: 197 mm × 141 mm.

What is the panel cutout for the Siemens SIMATIC HMI Basic Panels (2nd Generation) KTP900 Basic?

251 × 166 mm (9.88 × 6.54 in), width by height, behind a bezel of 267 × 182 mm. The document prints it as: 251 mm × 166 mm.

What is the panel cutout for the Siemens SIMATIC HMI Basic Panels (2nd Generation) KTP1200 Basic?

310 × 221 mm (12.20 × 8.70 in), width by height, behind a bezel of 330 × 245 mm. The document prints it as: 310 mm × 221 mm.

What panel thickness does the Siemens SIMATIC HMI Basic Panels (2nd Generation) mount in?

The document states: 2 mm to 6 mm at the mounting cutout for IP65 or Type 4X/12; permissible deviation from plane at the cutout 0.5 mm..

Can you cut the SIMATIC HMI Basic Panels (2nd Generation) opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.