AutomationDirect C-more EA9 panel cutout dimensions

The AutomationDirect C-more EA9 EA9-T6CL / EA9-T6CL-R needs a panel cutout of 189.5 × 140 mm (7.46 × 5.51 in), width by height, and the EA9-T15CL / EA9-T15CL-R needs 379.2 × 286.3 mm (14.93 × 11.27 in). The table gives the opening for each of the 7 models, the bezel that covers it and the depth the document prints, from the maker's own document, which is linked below. Supported panel thickness: Enclosure mounting thickness 0.039 - 0.20 inch [1 - 5 mm], metal..

Per model

AutomationDirect C-more EA9 cutout dimensions

AutomationDirect C-more EA9: panel cutout per model, width × height
ModelScreenCutout W × H, mmCutout W × H, inBezel W × HDepthAs the document prints itCutout designer
EA9-T6CL / EA9-T6CL-R6"189.5 × 140 mm7.46 × 5.51 in *not printednot printed7.46 in. [189.5 mm] × 5.51 in. [140.0 mm] (p. 4-5)
EA9-T7CL / EA9-T7CL-R7"189.5 × 140 mm7.46 × 5.51 in *not printednot printed7.46 in. [189.5 mm] × 5.51 in. [140.0 mm] (p. 4-5)
EA9-T8CL8"235 × 179.6 mm9.25 × 7.07 in *not printednot printed9.25 in. [235.0 mm] × 7.07 in. [179.6 mm] (p. 4-6)
EA9-T10WCL10"235 × 179.6 mm9.25 × 7.07 in *not printednot printed9.25 in. [235.0 mm] × 7.07 in. [179.6 mm] (p. 4-7)
EA9-T10CL10"302.3 × 226.3 mm11.90 × 8.91 in *not printednot printed11.90 in. [302.3 mm] × 8.91 in. [226.3 mm] (p. 4-8)
EA9-T12CL12"319.3 × 259.6 mm12.57 × 10.22 in *not printednot printed12.57 in. [319.3 mm] × 10.22 in. [259.6 mm] (p. 4-9)
EA9-T15CL / EA9-T15CL-R15"379.2 × 286.3 mm14.93 × 11.27 in *not printednot printed14.93 in. [379.2 mm] × 11.27 in. [286.3 mm] (p. 4-10)

* converted at 25.4 mm to the inch from the unit the document prints; the printed figure is in the column "As the document prints it".

Source: C-more EA9 Hardware User Manual, EA9-USER-M, 1st Edition Rev. X, Chapter 4 (Installation and Wiring), read on November 12, 2026. Width is the horizontal side with the terminal mounted in landscape, as the document draws it.

To one scale

The openings side by side

Solid outline: the cutout. Dashed outline: the bezel that has to land on flat door around it, drawn centred on the cutout. Leave the bezel clear of the door stiffeners, the hinge and the latch.

EA9-T15CL / EA9-T15CL-REA9-T12CLEA9-T10CLEA9-T8CLEA9-T6CL / EA9-T6CL-R

From the maker's documents

Panel thickness, mounting and front rating

Panel thickness
Enclosure mounting thickness 0.039 - 0.20 inch [1 - 5 mm], metal.
Mounting
Through the cutout from the front, held by mounting clips: four on the 6, 7, 8 and 10 inch wide panels, eight on the 10, 12 and 15 inch panels. Clip screw torque 63 - 77 oz-in [0.45 - 0.55 Nm] on the 6, 7, 8, 10 and 12 inch panels, 92 - 106 oz-in [0.65 - 0.75 Nm] on the 10 inch wide and 15 inch.
Front rating, as the maker states it
NEMA 250 type 4/4X indoor use only, UL50 type 4X indoor use only, in the manual's specifications.
Clearance around the terminal
Minimum 4 in. on all sides and 1.72 in. at the rear, in the manual's clearance drawing.
Notes
The drawings are in inches with millimetres in brackets. The manual prints the same cutout, 9.25 x 7.07 in., for the EA9-T8CL and the EA9-T10WCL, and one drawing for the 6 and 7 inch panels. Chapter 4 draws the outer edge of the front bezel around each cutout without printing its overall size, so no bezel is shown here. No cutout tolerance or corner radius is printed. Each panel ships with a cutout template.

A terminal's front rating is its maker's, and it holds only when the terminal is mounted as that document instructs, in an enclosure of a matching type. The assembled rating is limited by the weakest fitting on the enclosure.

In the enclosure

What the opening needs from the door

Room on the door

The bezel is larger than the cutout on every side, and the mounting clips sit behind it. Place the opening so the bezel lands on flat sheet, and keep the depth of the terminal plus the connectors and the cable bend inside the usable depth of the enclosure: each size's usable depth is in the enclosure size chart.

Heat and the seal

A terminal adds its own heat to a sealed box; check the total in the enclosure heat calculator. The gasket seals against the door face, so the cut edge has to be flat and free of burrs. More on door openings in the guide to cutouts, glands and HMI windows.

Need the opening cut for you?

The cutout, cut into a stainless door at the factory.

Send the terminal's model, or enter its cutout and bezel under "My own display" in the cutout designer. We draw the opening on a 304 or 316L stainless enclosure in your size, you approve the drawing, and it is cut before it ships. From one piece. Delivered in 10 business days, anywhere in the world. Counted from your approval of the drawing.

Same maker

Other AutomationDirect series

C-more CM5 · every series by screen size

AutomationDirect, C-more and the product names on this page are trademarks of their owners. NEMA4 Enclosure is not affiliated with or endorsed by them. The dimensions are quoted from the documents cited for panel layout; a maker can revise a drawing at any time, so check the current document for your exact catalog number before you cut.

Asked and answered

C-more EA9: questions

What is the panel cutout for the AutomationDirect C-more EA9 EA9-T6CL / EA9-T6CL-R?

189.5 × 140 mm (7.46 × 5.51 in), width by height. The document prints it as: 7.46 in. [189.5 mm] × 5.51 in. [140.0 mm].

What is the panel cutout for the AutomationDirect C-more EA9 EA9-T7CL / EA9-T7CL-R?

189.5 × 140 mm (7.46 × 5.51 in), width by height. The document prints it as: 7.46 in. [189.5 mm] × 5.51 in. [140.0 mm].

What is the panel cutout for the AutomationDirect C-more EA9 EA9-T8CL?

235 × 179.6 mm (9.25 × 7.07 in), width by height. The document prints it as: 9.25 in. [235.0 mm] × 7.07 in. [179.6 mm].

What is the panel cutout for the AutomationDirect C-more EA9 EA9-T10WCL?

235 × 179.6 mm (9.25 × 7.07 in), width by height. The document prints it as: 9.25 in. [235.0 mm] × 7.07 in. [179.6 mm].

What panel thickness does the AutomationDirect C-more EA9 mount in?

The document states: Enclosure mounting thickness 0.039 - 0.20 inch [1 - 5 mm], metal..

Can you cut the C-more EA9 opening into a stainless enclosure?

Yes. Send the model, or enter its cutout and bezel in the cutout designer under "My own display". We draw the opening on a 304 or 316L stainless enclosure in your size and cut it at the factory after you approve the drawing. Our standard enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed; with a terminal installed, the assembled rating is limited by the weakest fitting.