Short answer: bond the armor tape to earth at both ends of the run, and land the signal shield at both ends in normal service. On an intrinsically safe loop, or whenever the analog input maker calls for single-point grounding, the shield lands at the cabinet only, and a field junction box holds shield continuity on an insulated splice instead of a second earth bond. The armor tape and the foil shield are two separate metal paths with two separate jobs, and they never share a terminal. The sections below sort the layers out, give the landing decision for each circuit type including thermocouples, and walk the termination sequence at the box.
Which conductor is which inside an armored instrument cable?
You are handling two separate metal paths — a steel armor tape wrapped around the cable for mechanical protection, and a foil shield with a bare drain wire wrapped around the signal pairs for electrical noise — and they never share a terminal.
The armor is ferrous: one or two steel tapes wound helically under the outer sheath, or a steel wire braid on some constructions. A magnet sticks to it and it resists bending. The shield is aluminum-polyester foil crinkled around the pairs, bonded to a bare tinned drain wire, typically 0.5 mm² (20 AWG) on instrumentation cable. The drain exists because foil alone cannot be terminated; the drain collects the foil and gives you a wire to land.
Tag each layer at both ends of the section before you cut anything: tape on one label, drain on the other. Where a layer's identity stays unclear, read the cable construction drawing first — the two layers carry different currents and different failure modes.
Where does the armor tape get grounded?
Bond the armor tape at both ends of the run — at the field instrument's gland, at every junction box, and at the cabinet entry — so the tape carries induced interference and surge currents straight to earth instead of leaking them into the signal shield.
A tape bonded at one end and left floating at the other picks up interference it cannot shunt, which is why both-end bonding is the standing practice for armored instrument cable. At the box, an armored gland grips the tape and bonds it to the gland body; a short jumper from the gland to the box earth stud completes the path. A through-type box that splits one run into two cables lands the tape of both cables on the same stud, so the overall run keeps armor continuity to earth at both ends.
The box itself needs its own bond to the plant earth, and a gasketed gland plate only carries that bond when it is sized for the current: the earth continuity through a gasketed gland plate article works the sizing. The box-to-plant-earth fundamentals, including why the earth return is a designed conductor, sit in the grounding and bonding guide.
Does the signal shield land at one end or both ends?
For a standard 4-20 mA or digital loop, land the signal shield at both ends — at the field device and on the cabinet shield bar — and land it at the cabinet only on an intrinsically safe loop or when the input card manual asks for single-point grounding.
| Circuit crossing the box | Where the signal shield lands |
|---|---|
| 4-20 mA or digital loop, no maker instruction | Both ends: field device and cabinet shield bar |
| Input card or transmitter manual calls for single-point | That end only; the far-end splice stays insulated |
| Intrinsically safe loop | Cabinet (safe-area) end, on the IS earth bar; the box splice stays insulated |
| Thermocouple | Per the input card manual; the usual instruction is the card end |
Both-end bonding holds the whole shield run near earth potential and shields best against electric and magnetic pickup, so it stays the default for short loops on a plant with healthy equipotential bonding. Single-point bonding exists because two earth points are rarely at the same potential, and the difference drives a current through the shield. Here is what that current looks like:
Worked example — the loop that single-point bonding removes. Take a 150 m instrument cable run with a 0.5 mm² tinned-copper drain wire, about 35 Ω/km at 20 °C. Bonded at both ends, the drain loop resistance is 35 Ω/km × 0.150 km = 5.25 Ω. With 3 V between the field earth and the cabinet earth — a difference you can genuinely measure where stray currents are around — the shield carries I = 3 V ÷ 5.25 Ω ≈ 0.6 A, continuously. A type K thermocouple on the same cable outputs about 41 µV/°C near room temperature, so a 100 °C process change moves the signal only 4.1 mV; a shield current of that size couples enough noise to swamp a millivolt-level signal. Break the shield at one end and the loop current falls to zero, at the cost of some high-frequency shielding.
That arithmetic is why analog input makers often specify single-point grounding for sensitive front ends, and their instruction wins over convention. Where the shield bar sits relative to the earth bar in the cabinet, the panel earth and shield earth article shows the bar arrangement, and the 4-20 mA loop wiring article places the shield landing against the loop's fuse and polarity. one-end-versus-both-end comparison for instrumentation shields goes deeper into where each school wins.
How does an intrinsically safe loop cross a junction box?
On an intrinsically safe loop the shield bonds to earth at the cabinet only — on the same IS earth bar as the barriers — and a field junction box keeps shield continuity through an insulated splice that never touches the box metal, the gland plate or the armor.
The NEC grounds shielded instrument conductors as a rule and excepts intrinsically safe circuits: their shields follow the loop's certified design, which puts the bond on the safe-area side of the barriers, tied to the same earth the barriers use. In the field box that leaves one operation: crimp the drain wires shield-to-shield for continuity, sleeve the joint, and keep it clear of box metal, plate and armor. Many IS loops run plain shielded cable with no armor at all, because intrinsic safety needs no mechanical protection layer; where armor is fitted, it still bonds at both ends like any other run. The intrinsically safe ground bar article covers the separate-bar, single-earth arrangement at the cabinet.
What changes for thermocouples?
A grounded junction welds the measuring tip to the sheath, so the tip already reaches process metal through the thermowell and the shield lands at the input card end only.
An isolated junction keeps the tip electrically separate from the sheath, so the sensor end offers no metal path and the decision falls to the input card manual — which usually asks for single-point grounding at the card anyway. The card's thermocouple wiring pages are the deciding document in both cases, because the front end is designed around where its shield lands.
A thermocouple output sits at tens of microvolts per degree, so a shield loop does not show up as vague noise; it shows up as a steady temperature offset that tracks plant operating state. A grounded junction puts the sheath in a thermowell screwed into process metal: bond the shield at the sensor end on top of that and you have built a loop with the vessel in it. The sensor-end-versus-cabinet decision for thermocouple and RTD shields, including the isolation check that identifies the junction type, is worked through in the thermocouple and RTD shield grounding article.
What order do you follow to re-terminate the shield at the box?
Work one loop at a time with the loop isolated and proved dead, and land the layers in order: armor to the box earth through the gland, drain wires spliced shield-to-shield, then the splice bonded to the box earth or sleeved and insulated, depending on the end rule.
What you need at the box:
- Armored cable glands matched to the tape or braid on the cable
- Crimp butt sleeves or insulated shield terminal blocks for the drain splices
- Heat-shrink tubing over every insulated splice
- A meter, labels, and the input card manual for the loop
- A stainless wall-mount junction box with an earth stud: ours come with a hinged gasketed door, a removable mounting panel and wall-mount feet, rated NEMA 4X / IP66 by the manufacturer; not UL listed, and delivered in 10 business days
Gland holes in a pattern the stock plate cannot give are a factory job: the custom stainless enclosure page and its cutout drawing checklist cover what to send, in 304 or 316L, and the cutouts and glands guide covers hole sizes and gland selection. The wall-mount sizes are listed under stainless steel junction boxes. Then the sequence:
- Isolate the loop at the panel and prove the box dead with a meter you have first proven on a known live source.
- Tag the armor tape and the drain wire on every cable at the box, using the magnet test and the cable drawing.
- Dress each cable into its armored gland so the clamp grips the tape, then bond the tape to the box earth stud through the gland body or a short jumper — at every entry, on both sides of a through box.
- Crimp the drain wires shield-to-shield in a butt sleeve or land them on an insulated shield terminal, keeping the pigtail short and routed clear of power wiring.
- Apply the end rule: on a both-end circuit, bond that splice to the box earth stud; on a single-point or IS circuit, shrink the sleeve over it so it touches nothing metallic.
- Land the signal cores on their terminals, label the loop, and close the door.
- Re-energize and run the checks in the next section.
How do you check the loop when you are done?
Three measurements settle it — shield continuity end to end in ohms, a firm bond to the box where the end rule calls for one, and megohms of isolation where it does not — and then the live reading under real load proves the loop clean.
- Continuity: with the loop isolated, measure the shield from cabinet to field end. The 150 m example run reads close to the 5.25 Ω the worked example calculated; an open circuit means a splice never landed, and kilohms mean a corroded or loose crimp.
- Isolation: on a single-point or IS circuit, measure from the sleeved splice to the box metal. Expect megohms, effectively open; anything under a megohm means a strand or the sleeve is touching metal.
- Bond: on a both-end circuit, measure from the splice to the box earth stud and expect a reading near 0 Ω.
- Live reading: compare the field device's indication with the card reading under normal operation, then again with nearby drives and large starters running — loop noise shows up under load long after a bench check passes.
Two of these readings have dedicated walkthroughs: the control signal ground loop checks article for hunting down a loop, and the PT100 fluctuation article for the classic case where grounding the shield creates the fault it was meant to cure.
Finish with the mistakes that undo the work:
- Landing the drain on the armor stud: the two layers merge and the end rule disappears, so give each layer its own terminal.
- Taping the foil back against the box to keep it tidy: that is an accidental second bond on a single-point circuit, and heat-shrink is the tidy alternative.
- A splice that continues the shield but skips the bond on a both-end circuit: continuity without the earth bond gives little low-frequency shielding.
- Turning an insulated IS splice into a bonded one during a quick repair: the loop's earth design is gone until the certified arrangement is rebuilt.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What happens if a single-point shield splice touches the box metal?
The accidental contact restores the second earth bond, and the circulating current returns — about 0.6 A on the 150 m example run with a 3 V earth difference. On the loop it shows up as an offset or noise that appears and disappears as cables get moved. Sleeve every shield splice in heat-shrink and re-measure: splice to box metal should read megohms.
Can the drain wire double as the protective earth for a powered transmitter?
The drain wire is a noise conductor, not a protective earth: at 0.5 mm² (20 AWG) tinned copper it is sized for shield currents, not fault current. A powered transmitter's protective earth follows the NEC rules for equipment grounding conductors, sized from the rating of the overcurrent device protecting the circuit, and lands on the box earth stud or the cabinet ground bar.
Do both cable sections need armor bonds at a through-type junction box?
Yes. Land the armor tape of every cable entering the box on the box earth stud, so a run that one box splits into two cables keeps tape continuity to earth at both ends of the overall run. A stainless wall-mount box keeps this tidy: earth stud, removable mounting panel, armored glands on a common plate.
What reading proves an intrinsically safe shield splice is isolated inside the box?
With the loop isolated, an ohmmeter between the sleeved splice and the box metal reads megohms, effectively open, while the shield itself reads continuous end to end at single-digit ohms.





