Cutouts, cable glands and HMI windows: how to specify them

Every hole in a sealed enclosure is a place water can get in. Here is how to size and place conduit entries, cable glands, pushbuttons, HMI and panel PC cutouts and windows, and how to send us a layout we can quote.

NEMA4 Enclosure engineering team · Updated October 24, 2026 · 9 min read

Key takeaways

  • An enclosure keeps its rating only if every opening is closed by a device or fitting rated at least as high, installed to its instructions.
  • Conduit entries follow standard knockout diameters; cable glands follow their thread system (metric, PG or NPT) and the cable diameter.
  • 22 mm operators need a 22.3–22.5 mm hole; 30 mm operators a hole of about 30.5 mm.
  • For an HMI or panel PC, the maker's cutout drawing, tolerance and panel thickness range rule.
  • Send the face, the datum, every hole size and position and the device part numbers; the cutout designer does this for you.

A type rating applies to the enclosure as installed. NEMA states that fittings "are to be independently tested to a Type rating equal to or better than the enclosure's Type rating on which they are intended to be installed", and that a field-installed assembly's overall rating "is always limited by the least severe Type rating of all the components involved". IP ratings work the same way: an enclosure maker's technical guide puts it as "the IP can only be maintained if a component/accessory/peripheral is fitted in the hole/cutout that meets at minimum the enclosure's standard IP rating."

In practice, for a NEMA 4X-type / IP66 enclosure:

  • Use conduit hubs, cable glands, operators, displays, vents and windows marked Type 4X (and IP66 or better).
  • Install each with its own gasket or seal, on a clean, flat, deburred surface, tightened to the torque in its instructions.
  • Close unused holes with closure plugs rated for the enclosure type, not tape or sealant.

Conduit entries and knockout sizes

Holes for conduit fittings follow the knockout diameters in NEMA Bulletin 71 (the same table appears in UL 50). Use a sealing, watertight hub for conduit entries on a 4X enclosure, and check that the hub itself is marked for Type 4X.

Knockout diameters by conduit trade size (NEMA Bulletin 71)
Trade sizeMetric designatorNominal holeMin – max
1/2160.875 in (22.23 mm)0.859 – 0.906 in
3/4211.109 in (28.17 mm)1.094 – 1.141 in
1271.375 in (34.93 mm)1.359 – 1.406 in
1-1/4351.734 in (44.04 mm)1.719 – 1.766 in
1-1/2411.984 in (50.39 mm)1.958 – 2.016 in
2532.469 in (62.71 mm)2.433 – 2.500 in

Punch sets may cut slightly differently from these nominal values; what matters is that the fitting's locknut and seal fully cover the hole.

Cable glands: thread, hole and cable diameter

A cable gland seals one cable through the wall. Three choices define it:

  • Thread system. Metric threads (EN 60423, M12 to M63 at 1.5 mm pitch in common gland ranges) are the standard for new equipment. PG threads (DIN 40430) are the older European system and are not interchangeable with metric. NPT is the North American tapered pipe thread used with conduit-style fittings.
  • Hole size. Through-holes are sized just over the thread: gland makers' drawings for M20, for example, call for about 20.0–20.5 mm. Use the hole size on the drawing of the gland you will fit.
  • Clamping range. Each gland seals cables within a stated outside diameter range. Measure the cable and pick the gland for it; a cable below the range will not seal.

Gland IP ratings are proven under specific conditions: one maker rates its polyamide glands IP68 at 5 bar for 30 minutes, with the correct cable and the gland fitted per its sheet. Tightening torque is part of that, and it varies by size and material (the same maker lists 3 N·m for an M20 polyamide gland and 10 N·m for M20 metal). In washdown areas, choose a gland material that tolerates your cleaning chemicals.

The NEMA4 Enclosure mini PC configuration, for example, adds two cable glands for power and network in 20.5 mm holes.

Pushbuttons, pilot lights and selector switches

Operator devices come in two mounting sizes:

  • 22 mm (IEC style): one major maker's datasheet calls for a 22.3 mm hole, +0.4 / -0 mm, with 22.5 mm recommended, and an anti-rotation feature for selector switches and E-stops. Its minimum centre spacing is 40 x 30 mm for screw-clamp terminals.
  • 30 mm (NEMA style): about 30.5 mm; one major maker specifies 1-13/64 in (30.6 mm). Panel thickness is covered by the gasket choice, up to 1/4 in (6.4 mm) for that range.

Check each device's own rating. In the same 30 mm family, one range is rated Type 4 and 13 while its corrosion-resistant counterpart is rated Type 4, 4X and 13, and the maker notes that devices keep their type ratings only when properly mounted in an enclosure with the same rating. For a washdown door, specify 4X operators. Our cutout designer places 22.5 mm and 30.5 mm operator holes directly.

HMI and panel PC cutouts

A touch panel, HMI or panel PC seals against the front of the door with its own gasket, clamped by mounting clips or studs from behind. Three numbers from the device's installation manual decide whether it will seal:

  • Cutout size and tolerance. Typical HMI manuals give the cutout with a tight, one-sided tolerance, for example +1 / -0 mm (or +0.5 / -0 mm on some models). Too small and it will not fit; too large and the gasket may not cover the edge.
  • Panel thickness range. Mounting clips work over a stated range, for example 1.6 to 5 mm in one HMI manual, or 1.5 to 4.8 mm for another maker's adapter. Compare it with the door's sheet thickness, which on our wall-mount enclosures is 1.2 to 2.0 mm (18 to 14 gauge) depending on size and is listed on each product page.
  • Clamp torque and flatness. One maker specifies 2.3 to 2.6 N·m on the clip screws "to provide a proper seal" and warns that the gasket is a compression seal, so sealing compounds must not be used; another warns that a thin installation wall can warp and may need strengthening.

HMI front ratings apply only when the unit is installed as instructed: one manual states its IP65 and Type 4X/13 front rating applies "on the front panel when properly installed in an enclosure". Gaskets age, and HMI makers recommend replacing them on a schedule; one says at least once a year.

IMD panel PCs. If you choose the panel PC configuration of a wall-mount enclosure, the door is laser-cut to the exact panel opening of that IMD panel PC, deburred and fitted with mounting studs before it ships. For a panel PC on its own, our HMI enclosures are slim 304 stainless housings cut for one IMD panel PC, with an IP65-type front seal with the display installed (manufacturer rated). For any other HMI, send us its cutout drawing.

Viewing windows

A window lets operators read meters or indicators without opening the door. Windows are gasketed into the door and, like every other opening, need a rating that matches the enclosure. The glazing choice:

  • Polycarbonate: very high impact strength and good heat resistance, but UV light yellows it over time, and its chemical resistance depends on the chemical: some solvents cause stress cracking.
  • Acrylic: lower impact strength than polycarbonate, but resists UV and scratching better.
  • Glass: hard and scratch resistant; glass inspection windows in 316 stainless frames are sold with NEMA 4X ratings for washdown use.

Check the window material against your cleaning chemicals as well as the sun.

Placement rules that keep the seal

  • Keep clear of the gasket, hinge and latches. The door gasket needs an unbroken landing; holes near it weaken the seal and get in the way of the door collar.
  • Mind the inside. A device on the door must clear the mounting panel and its components when the door closes, and glands need room for the cable bend inside.
  • Large cutouts on thin doors may need stiffening so the door stays flat against its gasket.
  • Cable entries from below where you can, in outdoor and washdown locations, so water runs off the entries.
  • Work stainless with stainless tools. Fabrication guidance is to use tools dedicated to stainless steel: iron from carbon-steel drills, punches or files causes rust spots. Deburr every hole, and keep cutting edges sharp to avoid work hardening.

Our cutout designer marks overlaps and cutouts that are too close to the gasket, hinge, latch or an edge in red, in plain words, before you send anything.

How to send a layout we can quote

  1. Start from a catalog size. Find the closest enclosure, or an HMI enclosure for one display.
  2. Name the face: door, top, bottom, left, right, back or the inside mounting panel.
  3. Give a datum: positions measured from the centre or from a stated corner of that face, in mm or inches.
  4. List every opening: type, size and tolerance (round, rectangular, gland thread and size, 22 or 30 mm operator, display cutout), and the part number of the device that fits it.
  5. Material and quantity: 304 or 316L, and how many.

The fastest way is the cutout designer: pick the enclosure and a face, place round and rectangular holes, 22.5 and 30.5 mm pushbuttons, metric and NPT cable glands, IMD display openings, fan and filter openings and windows, then download the layout as a dimensioned PDF or DXF and request a quote. Or upload your own drawing (PDF, DXF, DWG or STEP). Custom work is quoted, not priced online.

About the rating after cutouts. Wall-mount enclosures are manufacturer-rated NEMA 4X-type / IP66 - not UL listed. Once cutouts are added, the rating of the finished enclosure depends on properly rated components and cable glands being installed in every opening.

Frequently asked questions

Can I drill my own holes and keep the NEMA 4X rating?

Only if every new opening is closed by a fitting or device rated Type 4X or better, installed per its instructions; the assembly is only as good as its least-rated component. Use stainless-only tools and deburr every hole.

What size hole does an M20 cable gland need?

About 20.0 to 20.5 mm, just over the thread diameter. Use the hole size on the drawing of the gland you will fit, and choose the gland for your cable's outside diameter.

What hole size is a 22 mm pushbutton?

22.3 to 22.5 mm; one major maker specifies 22.3 mm +0.4 / -0 mm with 22.5 mm recommended. 30 mm operators take a hole of about 30.5 mm.

What is the knockout size for 1/2 in conduit?

0.875 in (22.23 mm) nominal, per NEMA Bulletin 71. 3/4 in conduit takes 1.109 in and 1 in conduit takes 1.375 in.

Can you cut an enclosure for an HMI that is not an IMD panel PC?

Yes. Send the HMI maker's cutout drawing with your quote request, or place a rectangular cutout in the designer; we check it against the door and quote it.

Sources

  1. NEMA, "NEMA FAQs: Enclosures" (Q15, fittings and the weakest-link rule)
  2. NEMA Engineering Bulletin No. 71, Knockout Diameters and Fitting Dimensions (Table 71-1A)
  3. UL 50, 13th ed. (historical copy): filling openings to maintain environmental integrity; Annex D knockouts
  4. nVent HOFFMAN, Technical Information (IP rating maintained only with rated components in cutouts)
  5. Lapp, T21 thread dimensions and tightening torques for cable glands (EN 60423, DIN 40430, NPT)
  6. Lapp, mounting-hole dimensions for metric cable glands
  7. Lapp, SKINTOP instruction sheet (clamping range, IP68 test conditions)
  8. Bär, "Threads in cable glands" (metric vs PG vs NPT)
  9. Schneider Electric, Harmony XB5 22 mm operator datasheet (hole size, spacing)
  10. Rockwell Automation, Bulletin 800T/800H 30 mm operators installation (hole size, type ratings)
  11. Pro-face GP4000 series hardware manual (cutout tolerance, panel thickness, warping, gasket replacement, front rating)
  12. Rockwell Automation, PanelView 5510 / Plus 7 stainless installation (clip torque, compression gasket)
  13. Rockwell Automation, adapter kit installation (panel thickness range, Type 4X torque)
  14. Polymershapes, polycarbonate vs acrylic and Covestro, chemical resistance of polycarbonate
  15. McMaster-Carr, enclosure inspection windows (glass, stainless frame, NEMA 4X)
  16. Aalco, Stainless steel fabrication (dedicated tools, sharp edges, contamination)