Short answer: put panel earth and shield earth on one grounding system. Inside the cabinet, two labeled bars are fine — a protective-earth bar for the supply earths, a shield bar for the cable screens — as long as a short strap joins them. Outside the cabinet, every rod and pit joins the same bonded network. Two pits left unbonded are the arrangement that breaks communication: at 10 Ω of soil between them and 2 A of leakage, they sit 20 V apart, outside the −7 V to +12 V window an RS-485 receiver tolerates. A 6 AWG bond across 30 m cuts that difference to 0.08 V. One system, two labeled bars, and an intentional bond between every cabinet — that is the whole answer.
Two duties, one system
The panel earth has one job: carry fault current back to the source so the breaker or fuse clears fast. NEC 250.4(A)(5) calls that path the effective ground-fault current path and rules the soil out of it — metal conductors carry fault current, earth does not. The shield earth has a quieter job: give interference picked up on a cable screen a low-impedance way into the cabinet earth, so it never reaches the receiver's input stage.
The two currents differ by orders of magnitude. A fault pushes hundreds to thousands of amps for a few cycles; a healthy shield carries milliamps. Both currents end at the same place — one bonded grounding system — and they differ only in conductor size and connection detail.
| Panel earth (PE) bar | Shield bar | |
|---|---|---|
| Job | Fault-current return | Interference drain |
| Current | Hundreds to thousands of amps during a fault | Milliamps in a healthy install |
| Conductor size | NEC Table 250.122, from the overcurrent device | Screen cross-section, clamp-terminated |
| Connection | Bolted to the plate and the enclosure | On standoffs, one short link to the PE bar |
| Earth pit | One bonded system | The same bonded system |
What the standards call for
The NEC builds one system, not two. NEC 250.96(A) extends the fault-carrying duty to raceways, equipment and enclosures: bond the metal parts together so they can safely conduct any fault current likely to be imposed on them. NEC Table 250.122 sizes that conductor from the rating of the overcurrent device ahead of it. NEC 250.54 treats a spare rod as an auxiliary electrode: you may connect it to the equipment grounding conductor, and the conductor back to the source still does the fault-clearing job. NEC 250.6 aims to keep neutral current off the metal parts, so neutrals land on an isolated neutral terminal and grounds on the ground bus — which also keeps load current off the shields.
On the IEC side, IEC 60364 covers low-voltage installations in commercial, industrial and residential buildings, and it reaches the same destination through protective equipotential bonding: exposed metal parts and electrodes join one bonded network, so no two earthed points drift apart in normal or fault operation. Neither body asks for an isolated shield pit. A specification that demands one is asking the signal cable to do a bond's job, and the worked example below puts numbers on that.
The grounding and bonding guide works through conductor sizing and bonding hardware in detail.
How two pits put voltage on the link
Soil is a resistor, and two rods are two terminals of it. In average soil the resistance between two pits sits in the tens of ohms; the NEC's own benchmark allows up to 25 Ω for a single made electrode. Meanwhile every cabinet leaks: EMC filters, drive capacitance and instrument supplies push tens of milliamps to a few amps into the earth system, and that current returns to its source through the lowest-impedance path it can find — sometimes the soil between two pits. Ohm's law converts that current into a standing voltage between two points you both called "earth".
| Source of pit-to-pit voltage | Typical size | What the link shows |
|---|---|---|
| Filter and drive leakage | Tens of milliamps to a few amps, continuous | Retries, CRC errors, slow drift |
| Motor start or switching surge | Hundreds of amps for a few cycles | Dropped frames at the same moment each time |
| Lightning | Tens of kiloamps | Destroyed ports and screens |
The signal cable is then the only other metal joining the cabinets, so it becomes the equalizer: its screen carries the current and its transceivers see the leftover voltage as common-mode stress. Symptoms follow events, not the calendar — links drop when a nearby motor starts, errors cluster on one run, one port fails repeatedly. Stray current on an equipment grounding conductor chases the same mechanism on the power side, and a floating PLC 0 V with a USB fault is the small-scale version inside one panel.
Worked example: a 30 m link between two 10 Ω pits
The inputs, each with its source:
- Cabinets 30 m [100 ft] apart, each earthed to its own rod — an example case, typical of a skid-to-control-room run.
- 10 Ω of soil between the rods — an example figure; the NEC's 25 Ω benchmark for a single made electrode makes 10 Ω a fair average-soil value.
- 2 A of combined filter and drive leakage returning through the soil — an example figure for a small panel with two drives.
- RS-485 link, whose receivers tolerate −7 V to +12 V of common-mode voltage (TIA/EIA-485).
- Feeder protected at 60 A, so NEC Table 250.122 sets the bond at 6 AWG copper.
The rule: voltage between two earths equals current times the resistance between them (Ohm's law, V = I × R). A conductor's resistance is resistivity times length over area, R = ρ × L / A.
- Unbonded: V = 2 A × 10 Ω = 20 V between the two cabinet earths. That is 8 V past the +12 V top of the RS-485 window — retries first, then corrupted frames, then dead transceivers.
- Bond resistance: R = 1.72 × 10⁻⁸ Ω·m × 30 m ÷ 13.3 × 10⁻⁶ m² = 0.039 Ω (copper at 20 °C; 6 AWG is 13.3 mm²).
- Bonded: the 0.039 Ω copper runs parallel to 10 Ω of soil and takes essentially all 2 A: V = 2 A × 0.039 Ω = 0.08 V — two orders of magnitude inside the window.
- Ratio check: 10 Ω ÷ 0.039 Ω ≈ 260, so the bond cuts the standing difference about 260-fold.
- Hot check: copper resistance rises about 0.39 % per K, so at 70 °C the bond reads 0.039 Ω plus 19 % ≈ 0.046 Ω and still drops under 0.1 V.
- Fault check: a 500 A ground fault across the bond drops 500 A × 0.039 Ω = 19.5 V for the instants before the breaker clears — the bond is carrying the fault so the shield does not have to.
- Ampacity check: the NEC's copper ampacity table gives 6 AWG 65 A at 75 °C, so it covers the 60 A feeder with margin.
Decide against the receiver window, because that is the threshold that fails: keep the standing voltage between any two cabinet earths inside −7 V to +12 V with wide margin, and size the bond from the feeder overcurrent device, not from the screen's milliamps. The 6 AWG bond here delivers 0.08 V where the unbonded pits delivered 20 V. Any pair of pits with amps of leakage between them breaches that window; the bond is what holds it.
Laying out the bars inside the cabinet
Build it so the next person keeps it. Bolt the protective-earth bar to the mounting plate and bond the enclosure walls to the plate. Bond the door with a strap across the hinge — the gasket seals water, not electricity. Mount the shield bar on standoffs beside it, join the two bars with one short link, and label both bars. Neutrals land on the isolated neutral terminal and grounds on the ground bus, so load current stays off the screens.
Land every screen through a metal clamp at the bar, and keep the exposed pigtail under about 30 mm [1 in]. Straight wire is roughly 1 nH per millimetre, so a 25 mm pigtail is about 25 nH — near 16 Ω at 100 MHz, high enough to block the very currents the shield exists to drain. A clamp needs no pigtail at all.
Two ground bars in one enclosure tests whether the back plate alone can carry the bonding duty, earth bar versus one earth stud sorts the hardware for ten earth cables, and AC and DC grounds in one enclosure settles the same question for a DC 0 V reference.
Terminating each shield
One bonded system still lets each screen follow its own rule. Bond a VFD motor-cable shield at both ends — the both-ends article explains why the motor end matters as much as the cabinet end. Low-level analog differs: thermocouple and RTD shield grounding weighs the sensor end against the cabinet end. Inside a metal box, grounding an RS-485 shield inside a metal enclosure covers the clamp geometry. For cabinet-side hardware, the page on terminating shielded cable shields in PLC control cabinets walks through clamp types and where each fits.
Read the interface's own instruction where one exists: some transceivers want the screen on a functional-earth terminal through a specified network, and that terminal belongs on the shield bar, inside the bonded system. What no interface wants is a screen floating between two unbonded earths, or a screen pressed into service as a fault conductor.
If the site already has two pits
Retrofit in this order:
- Draw what exists. Trace every electrode, bar and cabinet bond onto one drawing, and mark where each shield terminates at each end.
- Make it safe first. De-energize, lock out and check for absence of voltage before opening any cabinet.
- Bond the pits. Bury bare copper between pits and back to the service earth, sized from the overcurrent device — a 60 A feeder needs 6 AWG copper under NEC Table 250.122. The spare rods stay connected as auxiliary electrodes under NEC 250.54.
- Bond the cabinets to that conductor, not through their signal cables.
- Measure the result. A clamp meter on each drain should read milliamps; amperes mean the screen is still equalizing. Between cabinet earth studs under full load, expect millivolts. Restart the link during a motor start and watch the error counter hold.
The decision, and what to order
| Your situation | The grounding answer |
|---|---|
| New cabinet, one location | One system: PE bar plus shield bar, one short link, both labeled |
| Two or more interconnected cabinets | An intentional bond sized from the feeder overcurrent device — 60 A calls for 6 AWG copper |
| Two pits already in the ground | Bond the pits with buried copper; the rods stay as auxiliary electrodes |
| One-end screen terminations | Fine per interface — build the bonded cabinet earth first, then follow the device manual |
If the panel serves a washdown or outdoor line, our stainless wall-mount boxes suit it, rated NEMA 4X / IP66 by the manufacturer; not UL listed, with a removable mounting plate that carries both bars and a gland plate cut to your layout. Custom enclosures take your cutouts from one piece, delivered in 10 business days from your approval of the drawing; stainless junction boxes cover the remote splice and terminal points; stainless NEMA 4X wall-mount enclosures list the standard sizes and the 3D builder. The NEMA enclosure types guide maps which type fits which environment.
One system, two labeled bars, and a bond between every cabinet and every pit — the shields stay at milliamps and the data stays up.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can the panel earth bar and the shield bar be one and the same?
Yes. A single bar is the simplest correct build: every earth and every screen lands on it. Two labeled bars work identically when a short strap joins them — make the strap at least as heavy as the panel's protective conductor, which the NEC sizes from the overcurrent device ahead of the panel. One bonded system is what matters; the count of bars is layout, not physics.
Does the shield earth need its own earth pit?
No. A second pit adds resistance, not cleanliness: two 10 Ω pits carrying 2 A sit 20 V apart, and the signal cable becomes the equalizing path that voltage rides on. Extra rods are welcome as auxiliary electrodes connected to the equipment grounding conductor — the buried conductor back to the source still does the fault job. Bond every electrode into one network.
How short should a shield drain pigtail be?
Keep it under about 30 mm [1 in]. At roughly 1 nH per millimetre, a 25 mm pigtail is about 25 nH — near 16 Ω at 100 MHz, enough to block the interference currents the screen is supposed to drain. Clamp the screen in metal at the bar and the pigtail disappears.
What size conductor bonds two cabinets or two pits?
Size it from the overcurrent device ahead of the run, as NEC Table 250.122 sets out. A 60 A feeder calls for 6 AWG copper, which carries 65 A at 75 C on the NEC's copper ampacity table. Never size a cabinet bond from the screen's milliamps: the bond carries faults, the shield carries interference, and the two duties use different conductors.
Why did the network work only after a heavy cable was run between the two cabinets?
Because the signal cable was the only metal joining two unbonded earths, so it carried equalizing current instead of data: 10 Ω of soil at 2 A of leakage puts 20 V against a −7 V to +12 V window, and a copper bond cuts that difference to millivolts — which is why the retries stopped.





