Short answer: wire the conditioner's + to the channel terminal and its − to COM. Terminate the shield at the module end — the shortest practical path to ground — and put a fuse in the loop at that end, even when the example drawing leaves the fuse out. The shield takes one bond, never two. And read 0/4-20 mA as two ranges: confirm the conditioner output and the channel configuration both sit on the live-zero range before anything is energized. The steps below carry a worked 24 V loop budget and the checks that prove the loop reads true while the power-hungry equipment beside it runs.
What you need before you touch a terminal
- The conditioner's datasheet page: output type (two-wire, powered from the loop, or four-wire with its own supply), configured output range, and the marked + and − output terminals. Take its power wiring from its own diagram; the output labels say nothing about supply terminals.
- The input module's channel data: supported current range, input resistance, and the maximum input current if the datasheet states one.
- Shielded twisted pair for the run, one small fast-acting fuse per loop, and a panel ground bar bonded to the enclosure wall. In our stainless NEMA 4X enclosures (rated NEMA 4X / IP66 by the manufacturer; not UL listed) that bond is part of the build, and the grounding and bonding guide shows the stud and paint details.
- A meter for the checks below.
A two-wire transmitter powers itself out of the loop, so supply, transmitter and input all sit in series. A four-wire conditioner drives the loop from its own supply; the input sees the same current either way.
Match the ranges before you energize
A spec that reads 0/4-20 mA covers two ranges, and they scale differently. The live-zero channel maps a 16 mA span onto 0-100% of the process. If the conditioner outputs the zero-based range into a channel scaled with a live zero, zero reads 25% of span below the live zero (4 mA ÷ 16 mA) and half reads 37.5%. Only full scale lands right. The usual choice is the live-zero range — why 4-20 mA is selected over 0-20 mA and 0-10 V signals — so set both ends to it.
Where the shield lands, and why only there
Land the shield at the module end, on a shield bar bonded to the panel ground bar by the shortest practical path. That is the one end of the loop with solid ground behind it. Keeping the shield bar separate from the protective-earth bar while both belong to one grounding system is the arrangement in panel earth and shield earth: one grounding system, separate bars.
Two bonds on one shield make it a parallel conductor between two chassis. Any potential difference between them drives a circulating current, and its noise couples straight into a milliamp signal. The familiar advice to ground at the source assumes the source sits on bonded metal. A transmitter strapped to a plastic tank has no ground to offer. A rod driven beside the tank is only an auxiliary electrode under NEC 250.54: it may sit alongside the equipment grounding conductor, never in place of it. And the earth itself is not an effective path for current to return through (NEC 250.4(A)(5)). The panel end is the one place the shield can actually drain.
At the bond point, NEC 250.12 wants paint and enamel removed from threads and contact surfaces, so take the clamp or stud down to bare metal. The drain wire is a signal part, not a ground conductor: green stays reserved for equipment grounding conductors of 6 AWG and smaller (NEC 250.119), so the shield lands on the shield bar. Tape or heat-shrink the transmitter-end shield so it cannot touch conduit or the tank.
Two neighboring questions have their own pages. Draining to earth versus the supply negative is answered in cable shield to earth ground or power supply negative. If your loop shares a tray with drive output cables, read how VFD control cable shields are bonded before carrying this rule over to them. For temperature sensors, the decision is thermocouple and RTD shield grounding: sensor end or cabinet.
Wire the loop, step by step
- Lock out the panel feeder and confirm absence of voltage before opening the terminal covers. The loop voltage is tame; the feeder feeding the supply is not.
- Match the ranges: conditioner output and channel configuration both on the live-zero range, as above.
- Route the shielded pair along the signal side of the panel, away from power conductors and drive cables. Where they must cross, cross at right angles.
- Land conditioner + on the channel terminal (CH1 here) and conditioner − on COM. Loop-powered conditioners are polarity sensitive, so read the labels against the module terminals before you tighten anything.
- Install the fast-acting fuse in the + lead right at the channel terminal, so whatever the field wiring does has to pass through it before reaching the input. Rating: see the budget below.
- Terminate the shield on the shield bar at the module end by the shortest practical path, and tape the far end.
- Bond the shield bar to the panel ground bar over bare metal, as described above.
- Walk the labels once more — + on CH1, − on COM, fuse in, one shield bond — then re-energize and run the checks.
The loop budget: a worked example
Size every two-wire loop as a voltage budget before ordering anything. These inputs are a typical installation; replace each with your own datasheet values:
- 24 V DC panel supply
- transmitter minimum voltage across itself: 12 V (its datasheet states its own)
- channel input resistance: 250 Ω
- run: 500 ft [150 m] of 20 AWG shielded pair, about 10 Ω per 1000 ft per conductor at 20 C
- fuse cold resistance: about 5 Ω
At full scale, 20 mA:
| Element | Arithmetic | Drop |
|---|---|---|
| Input burden | 0.020 A × 250 Ω | 5.0 V |
| Wire, 1000 ft of conductor | 0.020 A × 10 Ω | 0.20 V |
| Fuse | 0.020 A × 5 Ω | 0.10 V |
| Total | 5.0 V + 0.20 V + 0.10 V | 5.3 V |
The transmitter keeps 24 V − 5.3 V = 18.7 V, which is 6.7 V above its minimum. Decision: the loop works, and wire length is almost never what kills it — each extra 500 ft [150 m] of this pair costs 0.2 V. What eats headroom is another series device. A loop indicator or a second conditioner must fit its burden voltage inside that 6.7 V, the rule for series-connecting anything into an existing loop.
Fuse rating, same loop: land the supply + on the channel terminal by mistake and the input sees 24 V ÷ 250 Ω ≈ 96 mA. A 50 mA fast-acting fuse carries the normal full-scale loop at 40% of its rating and opens on the miswire current. Where the module datasheet states a maximum input current, keep the fuse rating at or below it.
Checks that prove the loop
Energize and compare a known process input against the channel value. You can read the loop without breaking it: measure DC volts across the input resistor. Across that same resistor, 1 V is 4 mA, 3.0 V is 12 mA and 5 V is 20 mA.
| What you see | Most likely cause | The fix |
|---|---|---|
| 0 mA with the process above zero | Open loop: fuse open, broken conductor, reversed pair or dead conditioner supply | Isolate; check fuse and continuity, confirm polarity and the conditioner's supply terminals |
| Every reading a quarter-span low, full scale correct | Conditioner on the zero-based range into a channel scaled with a live zero | Align the ranges at the device, then retest at zero and span |
| Value shifts when the big supply runs | A second shield bond or a route shared with power cables | Find and insulate the far-end shield contact, restore separation, retest with the load on |
| Raw milliamps right, engineering value wrong | Scaling in the controller | Correct the scaling endpoints; the wiring stays as it is |
| Around 14 V between supply negative and earth | The DC output floats relative to earth | Normal in many panels — the shield references the bonded structure; what the 14 V reading means |
Take the final reading with the neighboring load running. A loop quiet at idle can still pick up noise, and the reading under load is the one that counts.
What costs you a good loop
- An unfused loop because the example drawing looks clean. The note under those examples calls for fusing every current loop; the symbols were left out to keep the drawings legible, and the note outranks the drawing.
- A shield bonded at both ends because the diagram ties every shield to COM. Drawings simplify the return path; the copper takes one bond, at the module end.
- Rescaling to chase an offset. A 25%-of-span shift at zero is a range mismatch to fix at the device, and scaling maps milliamps into engineering units without repairing either.
- Ordering against the two milliamp ranges as if they were one. Make the conditioner and the channel each say which.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
I swapped + and − at the module: is the conditioner damaged?
Almost certainly not. Loop-powered conditioners are polarity sensitive, and the common designs protect themselves internally from a reversed connection, so the result is a dead channel rather than a repair order. Swap the pair, confirm the loop returns to 4 mA at zero output, then rerun the checks with the neighboring load on. A four-wire conditioner follows its own datasheet for reverse polarity.
How far can a 4-20 mA loop run?
Much further than the wire suggests. In the worked loop, each extra 500 ft [150 m] of 20 AWG pair costs about 0.2 V at full scale. The 6.7 V of headroom therefore buys roughly 16,000 ft [5 km] of additional run (6.7 V ÷ 0.2 V × 500 ft). The binding limit is the transmitter's minimum voltage across itself — 12 V in the example — after the input burden and any series device are paid for. On long runs, shield routing and noise pickup matter more than ohms.
Why 4-20 mA rather than 0-20 mA?
The 4 mA live zero. A healthy loop at zero process output still carries 4 mA, while a broken wire, an open fuse or a dead transmitter carries none. On the zero-based range, zero output and a dead loop look identical. Current signaling also shrugs off the cable resistance that would drag a 0-10 V signal down, which is why the live-zero current loop became the default analog standard.
Does the series fuse shift the 4-20 mA reading?
No. The transmitter regulates current, so anything in series shifts only the voltage budget, never the milliamps — the 5 Ω example fuse costs 0.10 V and the full-scale reading stays put. The same regulation is why terminal resistance and long runs drag down a 0-10 V signal but leave a current loop alone.





