Short answer: ground the motor cable shield at both ends — a 360-degree clamp on the drive cabinet's entry plate, and a braid bond to the motor frame at the motor end. A PWM waveform at a carrier of 2 to 20 kHz pushes a pulse of charging current into the shield at every switching edge, and one ground connection cannot drain that pulse train. The far end floats up at induced voltage and the cable turns into a radiator that scatters noise into your sensors and screens. Drive installation manuals and cable makers' VFD termination notes agree on both ends, so the one-end habit you learned on instrument wiring retires here. On a typical cabinet the job is about an hour: a clamp, a gland, a scraper for the paint and a meter to prove the result.
Why the open end floats at a voltage
A drive output is not a sine wave. Every PWM edge swings a motor phase from zero to the DC bus voltage in about 100 ns, thousands of times a second, and every edge couples capacitively into the braid wrapped around the conductors. That current has one sensible destination: back to the drive's DC bus along the shield itself.
Worked example — edge current in a 20 m motor cable. Take 200 pF/m of conductor-to-shield capacitance (an illustrative value; your cable's datasheet states its own), a 400 V supply, and a 100 ns edge (fast drive edges run 50 to 200 ns):
| Quantity | Value |
|---|---|
| Cable capacitance C | 200 pF/m × 20 m = 4 nF |
| DC bus on a 400 V supply | 400 V × √2 ≈ 570 V |
| Edge rate dv/dt | 570 V ÷ 100 ns = 5.7 kV/µs |
| Edge current I = C × dv/dt | 4 nF × 5.7 kV/µs ≈ 23 A for about 100 ns |
| Edges per second at a 4 kHz carrier | 2 per cycle × 4,000 Hz = 8,000 |
Both ends grounded, the shield carries those 23 A pulses straight home to the drive, where its own filters deal with them. Motor end open, the braid charges a little more at every edge until stray capacitance balances the pulses, and an open shield end on a running axis sits at tens to hundreds of volts above ground. That is the surprise waiting in a cable grounded at the drive only.
Keep one wiring rule straight while you work: the braid is an EMC return, and the equipment grounding conductor is a separate connection. The motor's EGC is sized from the rating of the overcurrent device ahead of it, per NEC Table 250.122, and lands on its own terminal — enclosure grounding and bonding covers that side.
A pigtail or a 360-degree clamp
A twisted braid tail feels like a termination and behaves like an antenna lead-in. A straight conductor carries roughly 1 nH of inductance per millimetre (the usual rule of thumb for a wire near its return path), so a 100 mm pigtail is about 100 nH. At 10 MHz, a frequency well inside the spectrum of a 100 ns edge, that pigtail impedes the shield current at X = 2πfL = 2π × 10 MHz × 100 nH ≈ 6.3 Ω.
A 360-degree clamp holds the braid all round against bare plate, a few millimetres from its return path: roughly 5 nH, under 0.3 Ω at the same frequency. The edge spectrum at 10 MHz carries far less current than the 23 A peak, so the pigtail drop is not 23 A × 6.3 Ω — but the ratio stands. The same shield current sees about 20 times more voltage across a pigtail than across a proper clamp, and that voltage is what re-radiates into your analog channel 75 mm [3 in] away. For the wider picture of keeping drive wiring quiet inside a steel box, see shielding VFD motor and remote wiring in a steel enclosure; the landing points at the cabinet entry are detailed in cable shield termination at enclosure entry.
What you need
- A shielded motor cable with a braid shield and its own earth conductors. Braid clamps well; foil alone needs a drain wire and still ends poorly at high frequency.
- An EMC gland or saddle clamp matched to the cable's outside diameter, one for the cabinet entry and one for the motor terminal box.
- A scraper or stainless brush, because the clamp must bite bare metal.
- A torque screwdriver, side cutters and a sharp knife.
- A multimeter for the continuity check and a meter rated for the drive's DC bus voltage for the lockout check.
- Optional: a high-frequency current clamp or an oscilloscope to watch the shield current, and a pocket AM radio, which remains an honest EMI detector.
Steps at the drive end
- Lock out and verify. De-energize the drive, wait the bus-discharge time its manual states, and measure 0 V at the DC bus with a meter rated for the bus voltage before you open anything. A charged bus and a charged shield are the two surprises here.
- Choose the entry. Bring the cable through the plate nearest the drive's output terminals — the gland plate or a cutout beside the drive. Keep motor-cable entries 100 mm [4 in] or more from control-cable entries, and cross the two at 90 degrees where routing forces them close. Where the plate has no opening yet, we cut it to your drawing and deliver in 10 business days, counted from your approval of the drawing — see custom stainless enclosures with factory cutouts.
- Strip for the clamp. Cut the jacket back just far enough to expose about 20 mm [3/4 in] of braid inside the plate. Leave the braid round and untwisted.
- Clamp 360 degrees. Fit the EMC gland or saddle clamp so the braid bears all round on bare metal. Where the plate is painted, scrape back to bare metal under the clamp and at the screws: NEC 250.12 requires paint, lacquer and enamel to be removed from contact surfaces at grounding and bonding connections. Torque the clamp hardware to its marking.
- Add the tail the manual shows. Many drive manuals terminate a second, short braid tail, under 100 mm, from the clamp region to the drive's PE terminal. The clamp does the high-frequency work; the tail lands the rest and keeps the drive's internal filters honest.
Steps at the motor end
- Clamp at the box. Fit an EMC gland or braid clamp on the motor terminal box entry so the braid lands 360 degrees on the metal box, or run a short, wide strap from the clamp to the box's earth stud.
- Bond the frame separately. The motor frame bonds to the EGC on its own stud, as your wiring diagram shows. Two connections, two jobs, one box; grounding a motor junction box with the motor ground wire walks the frame side.
- Crimp or clamp. A soldered braid joint cracks on a vibrating frame; a crimped ferrule or a clamp joint survives the vibration.
- Respect the bend. On a moving axis, use cable rated for cable-chain service and dress it to the chain's specified minimum bend radius. A rigid cable fails its jacket first, then the braid under it.
Checks when done
- Continuity. With the drive still locked out, measure from a scraped spot on the braid at the motor end to the cabinet's PE bar. A 20 m run reads about 1 Ω or less; the exact figure follows the braid construction. This proves the connection exists, and the clamp geometry decides the high-frequency performance.
- Shield current. With the drive enabled, a high-frequency current clamp around the braid near the drive shows carrier-frequency current, typically from tens of milliamps up to a few amps depending on run length — an order-of-magnitude check, not a pass/fail figure. A shield carrying current is a shield doing its job.
- The symptoms. Run the speed range and watch whatever chattered before: analog inputs, proximity sensors, encoders. On one packaging line the false proximity triggers stopped once every motor-cable shield landed at both ends; your own symptom list is the pass/fail list.
- Heat at the entries. After 15 minutes under load the clamp and gland areas should be warm, not hot. A jaw gripping through paint, or a clamp left loose, turns shield current into heat; anything too hot to rest a thumb on (roughly 50 °C) gets reworked. Induced heating at enclosure cable entries covers the other causes.
- The radio test. An AM radio that hashed near the cable at speed goes quiet once the shield carries its current home from both ends.
Mistakes that defeat the shield
- A pigtail where a clamp belongs. 100 mm of tail is about 100 nH and roughly 20 times the impedance of a full-circle clamp at 10 MHz.
- One-end grounding carried over from instrument practice. Low-level instrument shields often bond at one end to block hum loops; the same habit on a PWM power shield recreates the open end from the worked example above. Control cables are a third case — VFD control cable shield grounding: bond one end explains that one — and the loop argument for signal cables is compared in instrumentation cable shield grounding, one end versus both ends.
- A taped-back braid at a mid-run pull box. Cut-and-tape restarts the problem at that box; keep the braid continuous through the box or bond it through the box wall. Our stainless junction boxes suit splices and pulls on wall-mounted motor runs.
- Paint under the clamp. Enamel between jaw and braid raises the joint impedance; scrape to bare metal first.
- Foil-only cable on a motor run. Foil needs a drain conductor and gives a poor high-frequency termination; specify braid.
- Loose entries elsewhere. A locking connector or conduit hub that leaves the braid unclamped rebuilds the pigtail you kept out of the plate — VFD motor cable entry: locking connector or conduit covers the hardware.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does grounding a VFD motor cable shield at both ends create a ground loop?
A loop exists, but on a PWM power cable that loop is the return path, not a fault. The shield's job is to carry the common-mode charging current back to the drive that produced it, so the current returns to its own source instead of circulating. Because the current is pulse-shaped and closes at the drive, the loop behaves nothing like a 50/60 Hz hum loop: it does not overheat the braid and does not trip protection. The one-end habit belongs to low-level instrument shields, where hum-loop currents corrupt millivolt signals.
Can I ground the shield at the drive end only on a short motor cable?
Bond both ends on every run. A 5 m cable still collects edge current: 200 pF/m × 5 m = 1 nF, which at a 570 V bus and 100 ns edges is about 6 A per edge, and the motor end still floats. If the motor-end work waits for a shutdown, tape the open end insulated until then; a short cable radiates less, but the touch hazard at the motor box stays the same.
Which gland or clamp size fits a shielded motor cable?
Size the gland by the cable's outside diameter, not by its conductor count. Typical EMC gland clamping ranges are about 6-12 mm for M20 threads, 13-18 mm for M25 and 18-25 mm for M32; the datasheet's clamping range is the number to match. The plate hole takes the gland's thread size, and the braid must sit inside the clamp's sealing area, not merely under the outer grip.
What cable suits a VFD driving a moving axis?
Use a shielded cable made for continuous flexing and cable-chain service, with a braid shield and integrated earth conductors; the datasheet states the cycle life and the minimum bend radius, and both beat any rule of thumb. For short, static runs, armored or steel-braided cable works well, terminated the same way: braid clamped 360 degrees at both ends. Either way the shield geometry at the two ends decides the EMC result more than shield coverage percentages do.