Bonding an RTD cable shield to the enclosure ground bar should never move the reading. When it swings from 72 F to 240 F, the shield point is not the fault: the cabinet's protective-earth bond is missing, or a lead has shorted into the shield. A 168 F [93 C] jump is about 36 ohm on a Pt100, and no lead length explains that. Work it in this order: prove the cabinet bond under 1 ohm to a known good earth, run the 24 V rail as a grounded PELV system when the supply documentation allows it, then land the instrument shield once, at the cabinet end, with the field end insulated.
What does the jump from 72 F to 240 F tell you?
A 168 F [93 C] swing on a Pt100 is a changed circuit, not a changed temperature, and when the unshielded RTD on the same inputs drifts too, from 72 F to 60 F in one test, the fault sits in the shared reference rather than in one damaged cable.
Read the three connections as one experiment:
- Shield to the ground bar. The shielded RTD runs 72 F to 240 F and the unshielded one sags 72 F to 60 F. Both circuits move at once, so the bar is not a quiet reference; suspect the bond before the cable.
- Shield to the 24 V rail. Both readings sit at 72 F and the shielded one runs steadier. This is the tell: the drain wire has become the floating system's only tie to earth, and the improvement is real but accidental.
- DC common bonded to the bar, then shield to the bar. The result matches the rail test. Once the common and the bar are one node, the reading stops caring where the shield lands, which is how a sound bond behaves.
The pattern says the cabinet earth is floating or high-resistance, and the wiring changes were moving the reference the RTD input measures against.
Why can a shield bond move an RTD by 168 F?
An RTD input reports temperature from resistance, so 168 F [93 C] of error is a 36 ohm change in what the module measures, and 36 ohm would take 680 m of #22 AWG lead wire to build.
Here is the arithmetic for a Pt100 on the standard IEC 60751 curve, which moves 0.385 Ω per C near room temperature:
| Step | Arithmetic |
|---|---|
| 72 F = 22.2 C | R = 100 Ω + (0.385 Ω/C × 22.2 C) = 108.6 Ω |
| 240 F = 115.6 C | R = 100 Ω + (0.385 Ω/C × 115.6 C) = 144.5 Ω |
| Display shift | 144.5 Ω - 108.6 Ω = 35.9 Ω |
| Extra lead that implies | 35.9 Ω / 0.053 Ω/m = about 680 m [2200 ft] |
#22 AWG copper runs about 0.053 Ω/m (16 Ω per 1000 ft) in standard wire tables. No sensor lead is 680 m long, so the extra ohms came from the circuit, not the copper. Three places they come from:
- A drain touching an RTD terminal. The module then sees the shield in series with the element.
- Two leads swapped on a 3-wire hookup. The module's lead compensation subtracts lead resistance by assuming both leads match; a swapped pair makes the subtraction add error instead of removing it.
- A floating reference. A drain bonded to an unearthed cabinet becomes the return for every leakage and coupled current in the panel. That current lifts the bar's potential, and an input referenced to the bar reads the shift as resistance.
The third explanation fits the three-connection sequence above best, because it moves both RTDs together.
How do you test the cabinet earth bond?
With the panel locked out, run a known-good lead from the service's main ground bus to the cabinet and read ohms between them: a bond you can build on measures under 1 ohm, and tens of ohms or an open reading is the fault itself.
Lock out and verify absence of voltage before any resistance check. Then work down the path:
- Bar to known good earth. The service ground bus or the grounding electrode conductor is the trusted end. The receptacle's equipment ground is not, because it can be a long #12 run through old joints.
- Bar to cabinet. A bar bolted over paint reads open no matter how tight the screw. NEC 250.12 requires nonconductive coatings such as paint to be removed from threads and contact surfaces at grounding connections, so scrape to bare metal and re-torque. Treat the bar-to-box joint as its own check; the steps in bonding a ground bus to the panel enclosure apply here.
- Cabinet to door and gland plate. NEC 250.96(A) requires metal parts serving as equipment grounding conductors to be bonded so they can carry fault current. The joint that quiets noise and the joint that clears a fault are the same joint.
NEC 250.4(A)(5) settles the role of the rod outside: the earth is not considered part of the effective ground-fault current path. The conductor bond does the work; the rod is a test reference here, never a fix. The grounding and bonding guide walks the chain from bar to service.
What if the bond is good and the reading still moves?
Then the cable or the terminations carry the fault, and a quarter-hour at the terminal blocks finds it: megohms from drain to every conductor, lead pairs matched within about 0.1 ohm, and zero continuity between shield and any RTD terminal.
- Drain to each conductor, with the field cable isolated at both ends. A dry shielded cable reads megohms on a standard ohmmeter; near 0 Ω means the drain has fused to a lead inside the jacket or been crushed by a gland or a cable tie.
- Lead pairs on a 3-wire RTD. The two lead-pair readings should match within about 0.1 Ω, because 3-wire compensation assumes equal leads. A 1 Ω mismatch on its own reads about 2.6 C [4.7 F] high on a 0.385 Ω/C element.
- Wiring against the module diagram. An element leg landed on the compensation terminal reads plausibly wrong all day, shield or not. Confirm the module is set for the actual sensor and wiring mode, a 3-wire Pt100 in this example.
Do you land the shield on the DC common or on the ground bar?
Land the drain on the ground bar you proved under 1 ohm; the rail test looked better only because the shield became the floating system's sole tie to earth, which turns a shield into a current-carrying conductor, the one job it must not have.
Decide the 24 V system on purpose, from the supply's own wiring diagram:
- Industrial DIN-rail supplies ship as SELV, a floating separated output, and the diagram states whether a grounded-output (PELV) arrangement is permitted.
- If the diagram permits it, bond the 0 V output to protective earth once, at the supply terminals. Bar and common become one node, and the drain lands on the bar as the neater point of the same joint. The trade-offs are set out in grounding the 0 V of a 24 VDC supply.
- If the supply is documented SELV only, leave the rail floating and put the drain on the bar anyway; the shield goes to the structure, never into the DC distribution.
- Power off, lift the common pigtail at the supply, and read it to PE. A dead short means something already bonds the rail, a filter or an earlier jumper; an open reading confirms a floating SELV rail.
Where does the shield actually land?
Once, at the cabinet, on a shield bus or the bonded ground bar, with the field-end drain trimmed to a short insulated tail, about 4 in [100 mm], so it can touch nothing.
Then the habits that keep it that way:
- Terminate the drain where the cable enters; what to bond when a shield reaches the enclosure covers that entry decision.
- Heat-shrink the sensor end. In a field pull box the drain passes through unbroken and insulated, with the splices made up in a gasketed stainless box from the stainless junction boxes range, manufacturer-rated NEMA 4X / IP66 and not UL listed.
- Motor and drive cable shields are the exception that bonds at both ends, because that shield carries the drive's high-frequency current and the motor frame becomes the screen; bonding a VFD control cable shield at one end sets out which end and why.
- The single-point rule carries across analog and serial links; the same choice for network cable is worked through in how an RS-485 network picks its shield bond.
- On a custom gland plate, keep signal entries about 12 in [300 mm] from drive and contactor entries; capacitive and inductive coupling both fall fast with distance.
How do you prove the fix held?
Repeat the original three connections in order and hold every result to the same number: 72 F steady within 1 F [0.5 C] with the shield on the proven bar, no shift when the drain is touched to the bar and released, and the same steadiness an hour later.
- Shield bonded, 10 minutes. 72 F ± 1 F. If the reading wandered with the drain open and sits still bonded, you have found the noise floor and removed it.
- Drain lifted again. A few F of indoor wander is normal for an open shield; bonded, the reading returns and holds. A bonded reading that still moves more than 2 F sends you back to the lead-pair match.
- Common to PE, power off. Dead short for a PELV rail, open for a deliberate SELV rail; record which one the panel runs, so the next change starts from a fact.
- Lead-pair match after re-termination. Within 0.1 Ω, unchanged from the bench check.
Leave the terminations as built and photographed, so the shield point reads as a decision rather than an accident.
When do you re-specify the enclosure?
Re-specify when the bond cannot be made sound: no ground bar at all, paint baked over the weld studs, or a box too shallow for a shield bus. Order the features that make the bond permanent, starting with a bus position for every drain plus two spares.
On a custom build you set the material, the depth and every cutout, so the drawing carries the fix: a ground bus with room for the drains, signal gland entries spaced from power entries, and depth, 6 in [150 mm] being enough to clear a bus below a terminal row. Bare 304 stainless bonds through its brushed finish; pick 316L where brine, salt air or chemical washdown attacks 304. The custom enclosures page takes the layout straight from your drawing, delivered in 10 business days, counted from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Should I bond the RTD shield at both ends like a motor cable?
Bond both ends on motor and drive cables, where the shield carries amperes of high-frequency current and the motor frame becomes the screen. An RTD pair carries under 1 mA of excitation in typical input modules, so a second bond adds a ground loop without adding shielding. Bond the drain once at the cabinet and insulate the sensor end.
My floating 24 V output reads about 12 V to earth: is that the fault?
No. Two equal Y capacitors in the supply's input filter, one from each output terminal to earth, split the voltage, so a high-impedance meter shows roughly half the rail, about 12 V on a 24 V output. That half-reading is filter leakage, not a failed supply, and it says nothing about whether the DC common is bonded; read ohms with the panel off for that.
How much temperature error does 1 ohm of extra resistance make on a Pt100?
About 2.6 C [4.7 F], because a Pt100 element moves 0.385 Ω per C and 1 / 0.385 = 2.6. That is why a drain wire touching one RTD terminal wrecks a reading: the 35.9 Ω shift in the worked example equals 93 C [168 F] on the display.
Is bonding the 24 V 0 V to earth the compliant choice?
Bonding the 0 V common to PE turns a floating SELV rail into a PELV system, and the supply's documentation must show the output is designed to be grounded; the bond lands once, at the supply. Our enclosures are manufacturer-rated NEMA 4X / IP66 and not UL listed, so the panel listing decision rests on the panel build, not on the shield point.