Intrinsically safe ground bar: separate bar, one earth

Yes: put the intrinsically safe circuits on their own clean ground bar, keep every power and non-IS ground off it, then bond that bar to the site grounding system at exactly one point. ISA 12.06.01 asks for a dedicated conductor isolated from the power system except at that point, so a separate earth rod is not required. Measure 1 Ω or less between bar and main earth, the pass mark IEC 60079-14 guidance and barrier makers use.

NEMA4 Enclosure engineering team · Published November 13, 2026 · 8 min read

Yes — give the intrinsically safe circuits a ground bar of their own. Land only barrier earths and IS cable screens on it, and bond that bar to the site grounding system at exactly one point. ISA 12.06.01 defines an intrinsic safety ground system as a conductor dedicated to the IS circuits, isolated from the power system except at that single connection, so ground currents normally have nowhere to flow in it. A separate earth rod under the IS bar is not part of the definition, so skip it. What follows is what the standard asks for, the 20 V lift a shared bar creates, where flameproof grounds belong, and how to build and prove the one bond.

Do intrinsically safe instruments need their own ground bar?

Yes: give the IS circuits a bar of their own, land only barrier earths and IS cable screens on it, and bond it to the main earth at one point, so no power-system current can ever flow through the IS grounding conductor.

The standard's object is the conductor, and the bar is the hardware that keeps it dedicated. When your drawing shows one rail for instruments and one for power, it is drawing exactly this rule: the IS stud rail touches nothing but IS earths. Panel builders call the pair clean earth and dirty earth; the names help on the shop floor, and the physics underneath is the one-connection rule. A backplate carries both without conflict — two ground bars in one enclosure are a normal arrangement — as long as each conductor goes where its system says.

What does ISA 12.06.01 require of an IS earth?

ISA 12.06.01 defines an intrinsic safety ground system as a conductor dedicated to the IS circuits, isolated from the power system everywhere except a single connection, and carried reliably to a grounding electrode installed under NEC Article 250.

The definition has three parts, and each tells you what to build:

  • Dedicated. Barrier earths and IS screens only. A motor frame, a panel corner post and a surge-arrester lead all stay off it.
  • One connection. Exactly one conductor joins the IS earth to the power grounding system. It is deliberate, labelled, and sized like any equipment grounding conductor.
  • Reliably connected to an electrode. The electrode is the plant's existing system: mat, ring or rod field. NEC 250.4(A)(5) treats the soil itself as no part of the fault-current path, so this connection exists to hold everything at one potential, not to drain current into the ground.

On the IEC side, IEC 60079-14 sets the installation rules and lands in the same place: one earth connection for the IS system, tied into the plant earthing arrangement. Where the barriers, the conduit seal and the bar live inside the cabinet is a layout question of its own — see where the conduit seal goes in a barrier enclosure.

What happens when fault current shares the IS path?

A shared bar is how fault current gets into the IS path: 2,000 A through 0.010 Ω of common conductor lifts the IS bar by 20 V, so every barrier earth on it rides up with the fault until the breaker clears.

Worked example — the lift a shared leg creates. Take a 480 V panel behind a 100 kVA transformer; a bolted ground fault on its secondary reaches roughly 2,000 A. Suppose the fault finds 2 m [6.6 ft] of 12 AWG copper common to the IS bar and a motor-starter earth. That leg's resistance is R = ρL/A = 1.7 × 10⁻⁸ Ω·m × 2 m ÷ 3.31 × 10⁻⁶ m² = 0.010 Ω. The lift on the IS bar is V = I × R = 2,000 A × 0.010 Ω = 20 V, held until the breaker clears — six cycles at 60 Hz is about 0.1 s. Scale the fault down and it still hurts: 200 A through the same leg lifts the bar 2 V, enough to spoil a millivolt-level thermocouple signal sharing the rail.

Two kinds of current can touch an IS earth, and only one belongs there. A barrier fault is the designed one: the barrier's fuse clears in milliseconds, and the current it dumps must get back to the source through a low-resistance connection — that is what the 1 Ω figure is for. A motor-starter fault is the wrong kind, and the bar arrangement is what keeps it off. With the single bond in place, a fault lifts panel, bar and barriers together, so an IS loop sees a shift, not a difference across itself.

Does the IS bar need its own earth rod?

No: the definition asks for one reliable connection to the site grounding electrode system, and a rod driven beside the panel is an auxiliary electrode under NEC 250.54 — allowed only alongside the equipment grounding conductor, never instead of it.

Rod fields reserved for instruments turn up on older plant drawings, and they add risk rather than margin. Bond the IS rod to the site grid and you already have one system, so the rod is spare copper. Leave it unbonded and the IS electrode floats: a lightning strike or a nearby fault then drives a kilovolt-scale difference between barrier earth and the field device's earth, the exact failure the clean-earth habit was meant to prevent. Soil alone also carries no meaningful fault current at power frequency, so a lone rod protects nothing.

Run one insulated conductor from the IS bar to the main earth bar and stop there. The grounding and bonding guide covers electrodes, bonding and conductor sizing when you want the fundamentals underneath.

Where do flameproof instrument grounds land?

On the standard earth bar with the power grounds: a flameproof housing contains an explosion inside its joints, so its earth is ordinary fault bonding for the housing, sized like any equipment grounding conductor, and it never lands on the IS bar.

The two protection methods need different things from an earth. Flameproof (Ex d) containment has no energy limit to protect: the housing is built to contain an internal explosion, so its earth is a fault path. Intrinsic safety limits the spark energy in the circuit, so its earth is the reference the barriers clamp against. Mixing them puts fault current where only a reference belongs.

Drawings sometimes show three bars — power, Ex d housings, IS. Three labelled bars are tidy wiring practice; three separate electrodes are not. Every bar ends at the same electrode system, each system with its single bond. For ten instrument housings and one stud rail, earth bar versus one earth stud is the same termination question either way.

How do you build the IS bar inside the enclosure?

Mount a labelled copper bar on insulated standoffs, feed it with one insulated conductor sized as an equipment grounding conductor — 12 AWG copper under a 20 A breaker, per NEC Table 250.122 — and keep every power earth, screen tail and saddle off it.

Build it so the one-connection rule survives the next panel modification:

  • Bar. A 10 × 3 mm [0.4 × 0.12 in] copper bar carries the fault duty of a 20 A feed many times over and leaves room for eight to twelve studs, one per circuit.
  • Standoffs. Insulated and rated 600 V, so the bar touches nothing conductive except its one bond and a stray jumper is visible at a glance.
  • Bond conductor. Sized per NEC Table 250.122, insulated and green, or green with yellow stripes, as NEC 250.119 requires for insulated conductors 6 AWG and smaller.
  • Separation. IEC 60079-14 asks for 50 mm [2 in] between IS and non-IS wiring, or an earthed metal partition between them; a divided wire duct or a partition plate meets it inside the box.
  • Marking. Engrave IS EARTH on the bar, keep IS cable in its usual light-blue sheath, and label both ends of the single bond.
  • Painted boxes. On a powder-coated carbon steel enclosure, cut through the coating at the bond point; NEC 250.12 requires nonconductive coatings off grounding contact surfaces unless the fitting is designed to bite through.

Where the bar sits is covered in ground bar placement: enclosure wall vs mounting plate, and the same bond-or-isolate logic settles AC and DC grounds in one enclosure.

How do you prove the earth before the panel goes live?

Measure one thing and count one thing: 1 Ω or less from any barrier earth terminal to the main earth bar with a low-resistance ohmmeter, and exactly one conductor between the IS bar and the power grounding system, traced end to end.

Work with the panel dead and verify absence of voltage before you loosen a lug. Then two checks settle it:

  1. Continuity. Measure from the farthest barrier earth stud to the main earth bar. The 1 Ω pass mark comes from IEC 60079-14 installation guidance and the barrier makers' instructions; a clean stud adds milliohms, so a reading near an ohm means corrosion or a loose lug, and the fix is cleaning and re-torque.
  2. One bond. Trace the green conductor end to end and label both ends. Then look for the parallels that creep in: a screen tail run to the enclosure wall, an instrument earthed through its tray saddle, a DIN rail jumper fitted for a test and left in place.

The box arrives with its rating; the bond is your work, and it is what the loop's certified safety description rests on. Record the reading and the date on the panel drawing so the next technician re-measures instead of guessing.

What goes on the order for a barrier cabinet?

Order a stainless wall-mount box with a removable mounting panel — rated NEMA 4X / IP66 by the manufacturer; not UL listed — with depth enough that the bar sits clear behind the wire duct, about 4 in [100 mm] more than the plate layout needs.

The barrier cabinet sits in the safe area, so a standard industrial box does the job. Our stainless steel junction boxes come with a hinged gasketed door, a removable mounting panel and wall-mount feet, and every cutout is cut to your drawing; they are delivered in 10 business days, anywhere in the world. Pick 304 stainless for an indoor instrument room and 316L for washdown, salt air or chemical plant air. If a standard size does not fit the barrier rail and the duct, the custom enclosures line takes your width, height, depth and every cutout as one part.

Whatever the box, the earth scheme does not change: one clean bar, every power and Ex d ground on the standard bar, one labelled bond to the main earth, 1 Ω or less across it. Build that, measure it, and the IS rating in the loop design rests on an earth you have proven.

Questions

What size conductor runs between the IS bar and the main earth?

Size it from the overcurrent protection ahead of the panel, using NEC Table 250.122: 12 AWG copper under a 20 A breaker, 10 AWG under 60 A. Many barrier cabinets end up with a single 10 AWG insulated green conductor for the whole IS bond; label both ends and keep it one unbroken length so the one-connection rule stays visible on the next modification.

Does an Ex d instrument housing need a separate clean earth?

No. A flameproof housing contains the explosion inside its joints, so its earth is plain fault bonding for the housing, sized like any equipment grounding conductor — 12 AWG copper under a 20 A breaker per NEC Table 250.122. It lands on the standard bar with motor and panel grounds; only barrier earths and IS screens belong on the clean bar.

Where does the IS cable screen terminate?

On the IS bar, at the barrier end as a rule. The screen is part of the IS earth, and a tail run to the enclosure wall or the cable tray creates a second earth path that spoils the one-bond check. Bond both ends only where the loop design calls for it, and count that tray path as part of the same single earth, not a second system.

Can a barrier cabinet be a standard stainless box?

Yes, when the cabinet sits in the safe area, which is where barriers belong. A stainless wall-mount box with a removable mounting panel takes the bar and the barrier rail, and the cutouts come to your drawing. We build no explosion-proof or NEMA 7/9 enclosures, so a panel that stands inside the hazardous area needs equipment approved for that zone instead of a plain industrial box.

How often does the IS earth bond get re-checked?

Measure it on every shutdown round, and IEC 60079-17 caps the detailed-inspection interval for Ex installations at three years. The pass mark is the same each time: 1 Ω or less from IS bar to main earth bar with a low-resistance ohmmeter. A reading above that means corrosion or a loosened lug — clean it and re-torque; a second bond is not the fix.