Land every thermocouple and RTD cable shield at one point: on an insulated shield bus inside the receiving cabinet, close to the analog input cards. The sensor end of each shield stays insulated unless the receiving input's wiring diagram calls for a field bond. Two bonds join two earths that typically sit 10-200 mV apart (the spread analog-input application guides report), and the loop current that follows lands as offset and noise on a signal measured in millivolts. A type K pair carries 24.9 mV across a 0-600 °C span, so one stray bond can put four times the full span into your measurement. The steps below cover the termination, the exceptions, the arithmetic and the checks.
Where the shield bond goes
The bond lives in the receiving cabinet, at an insulated bus or terminal strip, and it never lands on the enclosure wall or a nearby stud. Three reasons decide it. The earth at the sensor is somebody else's reference: it floats, or it carries currents from mixers, heaters and welders, so its potential against your cabinet sits anywhere in that 10-200 mV spread. Every cable in the plant ends at one set of analog cards, so a bus beside them gives your shields the shortest clean drain. And when the grounding scheme changes, solid, floating or isolated, one bus moves once and the whole panel follows.
Installation manuals for large control systems spell out the same split as three separate grounds: measurement ground for the signal reference, shield ground for the drains, protective earth for safety. Keep the jobs apart. A shield drain carries interference in milliamps, while the earth is no part of the effective ground-fault current path under NEC 250.4(A)(5), so no shield scheme replaces the green wire. If the cabinet's own bonding is unsettled, the enclosure grounding and bonding guide sets the foundations first.
The ISA guidance on instrumentation and computer grounding grew up around transmitter loops, and a transmitter loop is also where a second bond hurts least. The rule still reaches thermocouples, because the argument gets stronger as the signal gets smaller. A 4-20 mA receiver weighs an offset against a 16 mA span; a thermocouple input weighs the same offset against a 24.9 mV span. The one-end-versus-both-ends trade across instrumentation, signal and VFD cable gets a fuller treatment on the page instrumentation cable shield grounding: one end vs both ends.
| Circuit | Shield bond | Basis |
|---|---|---|
| Thermocouple pair | Cabinet bus, one point | 24.9 mV span (type K, 0-600 °C); a 100 mV loop offset is 4x the signal |
| RTD direct to the input | Cabinet bus, one point | A PT100 moves 0.385 Ω per °C (IEC 60751), so induced current reads as temperature |
| 4-20 mA transmitter | Cabinet bus unless its manual says otherwise | 16 mA span across 250 Ω; the offset shrinks, the one-point rule holds |
What you need
- An insulated shield terminal strip or copper bus on insulated standoffs, one terminal per cable shield
- One insulated link, 16 AWG (1.5 mm²), from the bus common to the ground bar
- Heat-shrink caps for the field-end shield tails
- Green insulated wire for field device case grounds: NEC 250.119 colors insulated conductors 6 AWG and smaller green or green with yellow stripes
- A DMM with millivolt DC and AC ranges plus an ohms range
- The receiving input module's wiring diagram, with the shield termination marked before you strip anything
Bonding the cabinet end, step by step
- Mark the bond point on the input module's wiring diagram. Every later choice hangs off that mark: one bus, one link, one earth.
- Mount the bus on insulated standoffs in the same section as the analog cards, within about 20 in [500 mm] of them. Short gland-to-terminal runs keep the drain away from local fields.
- Strip about 1 in [25 mm] of each shield drain, land one shield per terminal, and number each terminal by cable. What belongs at the gland and what waits for the bus is its own subject; cable shield termination at enclosure entry walks that first stretch.
- Bond the bus common to the ground bar with the 16 AWG link at one point. Scrape any paint to bare metal at both ends; NEC 250.12 keeps nonconductive coatings off grounding contact surfaces.
- At the field end, cap the bare tail in heat-shrink and tape it back clear of the enclosure wall and any metallic braid.
- Run case grounds on their own conductors: green wire from the ground bar to each field device case. The case bond and the shield bond are different jobs, so keep them on different wires even when they meet at the same housing.
- Mark the link and the bus on the drawing, so the next person counts one bond per shield before changing anything.
When the sensor end is the right answer
Two cases override the cabinet default. First, the receiving equipment's own diagram: some isolated input systems and some safety-rated loops specify shield treatment at the field device, and the terminal that diagram names wins over habit. You will also meet field transmitters with a housing ground stud; when the transmitter's instructions take the shield on that stud, a green case-ground wire runs out from the cabinet to meet it. The two connections stay separate jobs even at a shared stud.
A grounded-junction thermocouple looks similar and is not. Its sheath is welded to the thermowell, so the signal itself references the process, the input must be built for that reference, and no shield choice changes it. Bonding the shield at the cabinet coexists with a grounded junction, because the sheath bond and the shield bond are different paths.
If the sensor end sees frequent service, keep the shield out of the connector pair and land it where the cable arrives; thermocouple connector wiring for frequent service covers the contact and retention side.
What a 100 mV offset does to a 0-600 °C type K loop
This is the arithmetic behind the one-bond rule, worked for a common case: one type K thermocouple, a 0-600 °C span, feeding a non-isolated input in the receiving cabinet.
Inputs. Signal: 0 to 24.9 mV across the span, from the NIST ITS-90 reference tables for type K, an average of 24,900 µV ÷ 600 °C = 41.5 µV/°C. Disturbance: 100 mV, the middle of the 10-200 mV spread between earthed points that analog-input application guides report. Budget: the loop must read within 2 °C.
Rule in words. A shield bonded at two points joins two earths. The difference drives current around the shield, the current generates noise in the signal conductors, and with a grounded source and a non-isolated input, part of the difference lands on the input as offset.
Arithmetic.
- Offset against span: 100 mV ÷ 24.9 mV = 4.0. The disturbance is four times the whole signal.
- Offset as EMF: 100,000 µV ÷ 41.5 µV/°C = 2,410 °C of equivalent EMF. The input saturates long before it displays that; the number shows the scale.
- Budget: 2 °C × 41.5 µV/°C = 83 µV, about 0.08 mV.
- Disturbance against budget: 100,000 µV ÷ 83 µV ≈ 1,200. One stray bond spends twelve hundred times the loop's noise allowance.
Contrast. The same 100 mV across a 4-20 mA receiver on a 250 Ω resistor is 100 ÷ 4,000 = 2.5% of the 1-5 V span, about 5 °C on a 0-200 °C transmitter loop. That is why transmitter examples read calm: a transmitter shrugs off what buries a thermocouple.
Decision. Give the shield exactly one earth, at the cabinet bus. When the reading moves by more than about 80 µV of equivalent EMF, your 2 °C budget, suspect the shield before the controller: pull the field-end tail, re-insulate it, and re-trend.
Checks before you close the door
- Count the bonds. If you inherit a cabinet, start here: one shield takes one bond, and the bus takes one link. Two on any shield means the loop is live, and the field-end tail is the place to look first.
- Measure the isolation. Ohmmeter from every shield terminal to the cabinet and to its neighbours: expect open or megohms. A reading near 0 Ω means a stray bond or a bare drain touching the wall.
- Confirm the shield actually arrived. With the far-end tail bared, read ohms from each bus terminal out along the shield, then re-cap the tail. This catches the shield a gland crew trimmed off at the wall.
- Trend with the plant running. Log the input for an hour and watch the step when a nearby 30 kW motor starts; a step that follows plant load points at coupling or a second bond. The control signal ground loop checks page gives the fuller sequence.
- Inject a known value. A calibrator at 10.000 mV reads as about 241 °C equivalent on this span; accept it within 0.08 mV, the 2 °C budget. Out of range, and analog output ground offset inside a grounded enclosure is the next read.
Five mistakes that undo a clean shield
| Mistake | What you see | The fix |
|---|---|---|
| Shield bonded at both ends | Offset and noise that follow plant load, worst when big motors start | Remove the field bond, cap the tail, keep one bond at the bus |
| Shields daisy-chained through the strip | One loose screw drags several shields into one loop | One terminal per shield, numbered by cable |
| Shield shared with the negative lead | Reading shifts when you touch the shield | The pair carries the EMF, the shield carries interference; keep them separate |
| Bond made through paint or an anodized standoff | Reading drifts with humidity and washdown days | Scrape to bare metal at the link, then bond |
| Shield trimmed back at the gland | Clean drawing, noisy input; the drain ends at the wall | Pull the shield through and land it on the bus |
Digital buses run their own shield scheme; grounding an RS485 shield inside a metal enclosure takes that case.
What to order
The cabinet carries the bus, so order it with the shield hardware in mind. Pick a stainless wall-mount junction box with a hinged gasketed door and a removable mounting panel: the standoffs for the shield bus bolt to the panel without extra drilling, and the gasketed door keeps the rating once everything is landed. The nine wall-mount sizes in our stainless junction boxes come in 304 or 316L stainless; for washdown or outdoor duty choose 316L, rated NEMA 4X / IP66 by the manufacturer; not UL listed, and delivered in 10 business days. The box's own bond to the ground bar is a separate connection with its own fastener; bonding an enclosure to a ground bus covers that joint.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a splice in thermocouple extension cable corrupt the reading?
Yes, when the two sides of a joint sit at different temperatures. The error equals sensitivity times the difference across the splice: 10 °C across a type K splice at 41.5 µV/°C adds about 0.4 mV, close to 10 °C of reading error. Keep splices where both halves share temperature, and land the shield on the bus rather than through the splice.
Does an RTD cable shield follow the same one-bond rule?
Yes: bond it once at the cabinet bus. The measurement is a small resistance change, 0.385 Ω per °C on a PT100 (IEC 60751), and module excitation runs about 0.25-1 mA to limit self-heating, so induced shield current reads as temperature almost directly. Treat RTD pairs exactly like thermocouple pairs.
What size conductor links the shield bus to ground?
Shield drains carry interference in the milliamp range, so a 16 AWG (1.5 mm²) insulated link covers the bus-to-ground-bar bond. Size the equipment grounding conductors separately, from the rating of the overcurrent device ahead of them, using NEC Table 250.122; the EGC carries fault current, the shield never does.
Is bonding a shield at both ends ever correct?
Yes, in designs that call for it: VFD motor cables and some high-frequency digital buses bond both ends deliberately to cut radiated emissions, and their coupling differs from a microvolt analog pair. Analog temperature circuits have no such margin, since a type K span is 24.9 mV over 0-600 °C; follow the equipment diagram and keep exactly one bond when nothing specifies otherwise.





