Short answer: on a two-genset system with a 3-pole transfer switch, 8 A on the equipment grounding conductor (EGC) is neutral unbalance current that found a second way home. A 3-pole switch ties both genset neutrals together, so the system has one source, one neutral and one bond. Any amp that leaves the neutral has to come back through a stray bond downstream or through the mesh of raceway, tray, shields and earth. That mesh also explains the 3 A that survives with the wire EGCs lifted. The 30 mA RCDs stay closed because current balanced inside their sensing cores never trips them. Work the checks in order, and hold the rule that settles the whole arrangement: one bond, at the source that owns the neutral.
What the readings already tell you
Each reading in the pattern rules a cause in or out:
- 8 A on the EGC back to the running genset, zero on the idle one. Every diverted amp returns to the single bond, which lives at genset 1. The idle genset's EGC is a dead-end spur: with no neutral-to-frame bond at genset 2, no loop closes through that machine.
- The genset EGC reading climbs as each feeder EGC lands. Every conductor adds a parallel branch and lowers the impedance of the ground mesh. One faulty conductor does not read this way; a network does.
- About 3 A survives with all eight feeder EGCs lifted at the main distribution panel (MDP). The current is riding conduit, cable tray, shield drains or the earth, not the wire EGCs.
- 30 mA RCDs in the subpanels stay closed. The diversion bypasses their sensing cores or sits on their line side; the next section spells out why.
- The EGC reading rises and falls with neutral unbalance. That signature belongs to a second neutral-to-ground bond, the most common cause on systems shaped like this one.
Why the 30 mA RCDs stay closed
An RCD sums every line and the neutral through one sensing core and trips on the difference. A load's current crosses that core twice, out on the line and back on the neutral, so it cancels to zero no matter what it does after it leaves the panel. The EGC bypasses the core entirely.
The diversion in this pattern is balanced through the core. A trailer load's amps leave on the line and return on the neutral, both inside the core, and the split toward the second bond happens later, at the neutral bar on the line side. The trip coil reads zero. A bond downstream of an RCD is the one that trips it: current leaves through the core on the line and part of it returns outside the core, and 30 mA of that residual is the trip point.
For scale, 30 mA is the IEC personal-protection trip level, set below the region where ventricular fibrillation begins, and a North American Class A GFCI sits lower at 4-6 mA. The closed RCDs are a measurement in themselves: they place the diversion upstream of the trailers, at the sub-distribution panels (SDPs) and the transfer switch, exactly where the clamp readings point.
Clear the transfer switch and the idle genset
A 3-pole switch moves the three phases and leaves the neutral solid. Both genset neutrals stay tied through the switch, so neither genset is separately derived and the single bond serves whichever unit runs. That is why the diverted current always walks back to genset 1. A 4-pole switch breaks the neutral as well and would give each genset its own bond; the one-bond principle and where the bond belongs are covered in why a power system keeps exactly one neutral-to-ground bond.
The continuity check at genset 2 proves something only when it is done isolated. Lock out both gensets and the switch, lift genset 2's neutral at the switch so you read that machine alone, then meter neutral to frame at its output breaker and again at the junction box by the engine. Bonds hide behind terminal blocks and controller connections, so look for a strap or jumper by eye as well. Keep insulation testers off the AVR and controller electronics; the genset manufacturer's documentation carries that method.
Causes in order of likelihood
- A second neutral-to-ground bond. A misplaced bonding jumper or screw in an SDP or trailer panel, or a neutral landed on a ground bar. Misplaced jumpers have already turned up on systems like this, so assume there are more.
- A resistive bond. A neutral pinched behind a lug or resting on an enclosure wall makes a connection of a few tenths of an ohm, enough to divert 0.5-1 A per panel at these unbalance levels.
- Parallel metal. Conduit and fittings between MDP and SDPs, cable tray, building steel touching an enclosure, and the shields or drains of control cable. This mesh carries the 3 A survivor; the EGC-versus-plant-grid comparison at the enclosure shows how such paths share current.
- An auxiliary electrode loop. A driven rod at a trailer or pole closes a loop through the earth back to the genset electrode. NEC 250.54 lets such a rod connect to the EGC as an auxiliary electrode, and it never replaces the EGC.
- Induction. Current induced into a loop formed by an EGC and a nearby metal path. The reading tracks phase current instead of neutral and changes when you regroup conductors.
Clamp each feeder three ways
Lock out and confirm the absence of voltage before lifting any conductor. Lifting an EGC on a live feeder strips every enclosure on that feeder of its fault-return path, so clamp first and lift only where you control the exposure.
At a steady load, read each feeder three ways:
- All conductors in the jaws: phases, neutral and EGC together. Near zero means every amp returns inside the feeder. A real reading means current is leaving through conduit, structure or earth.
- Phases and neutral, EGC out of the jaws: the load and its neutral unbalance, the number the EGC reading gets compared against.
- The EGC alone: the stray current riding that feeder.
Step loads off one at a time and log the three readings together:
| Reading at steady load | Mechanism | Next move |
|---|---|---|
| EGC tracks neutral unbalance | Neutral diverted through a second bond | Hunt the bond on that feeder |
| EGC tracks phase current, neutral near zero | Induction into a conductor loop | Regroup the conductors; separate the EGC from parallel metal |
| EGC constant at any load | Leakage or a standing loop | Clamp shield drains; look for a rod at the panel |
| Net of all five conductors non-zero | Current leaves through raceway, steel or earth | Clamp the raceway joints and shields to find the exit |
Add the per-feeder EGC readings as phasors, not arithmetic. The currents sit at different angles, so eight magnitudes rarely sum to the 8 A at the genset. Trust the genset-side clamp for the total and the per-feeder clamps for the map.
What the numbers say
The arithmetic behind the 8 A, on example inputs you replace with your own feeder length, conductor size, load set and bond resistance:
Take one SDP 80 ft [24 m] from the MDP, wired in 6 AWG copper on both the neutral and the EGC over the same route. Copper at 75 °C runs about 0.5 Ω per 1000 ft [1.6 Ω per km], so each conductor is 0.04 Ω. The panel feeds 120 V line-to-neutral loads of 12 A on L1, 8 A on L2 and 4 A on L3. The neutral current is the phasor sum: x = 12 - 4 - 2 = 6, y = -3.46, so √(6² + 3.46²) = 6.9 A, call it 7 A.
With one bond and a clean neutral, all 7 A returns on the neutral conductor and the EGC reads milliamperes. Fit a neutral-to-can bond of 0.3 Ω, what a pinched neutral or a loose jumper gives, and the return splits between 0.04 Ω of neutral and 0.34 Ω of bond plus EGC. The EGC takes 7 × 0.04 ÷ (0.04 + 0.34) = 0.74 A and the neutral keeps 6.3 A. Eight panels like that put about 6 A on the EGC mesh, and raceway, shields and earth make up the rest of the measured 8 A. The can sits 0.74 A × 0.34 Ω = 0.25 V above the genset bond.
The per-panel reading grades the bond. A dead-short jumper splits the 7 A evenly, about 3.5 A per path, while 0.74 A from the same unbalance points to a resistive connection. Double the run to 160 ft and the same 0.3 Ω bond diverts 7 × 0.08 ÷ (0.08 + 0.38) = 1.2 A: conductor length moves the share, the bond's resistance dominates it.
The fix
- Remove every bond except the one at genset 1. Lock out all sources, lift the genset 1 bond jumper for the test only, and lift load neutrals so a load resting on metal cannot mislead you. Read neutral bar to enclosure at the transfer switch, the MDP, all eight SDPs and every trailer panel; each reading should be open. Look for bonding screws, neutrals on ground bars and pinched neutrals. Restore the genset 1 bond afterwards and re-measure the genset EGC after each correction. The walk-through is the same one in removing a stray neutral-to-ground bond from an outdoor subpanel, and separating neutral and ground in a subpanel shows the landing that prevents a repeat.
- Keep neutral current off metal. Neutrals land on isolated terminals; grounds land on the ground bus. NEC 250.6 states the intent in one line: keep neutral current off metal parts.
- Bond shields at one end. Control and communications shields are quiet members of the 3 A mesh until both ends land; bonding drive and control cable shields at one end covers the practice.
- Test the auxiliary rod. Lift it for a test and watch the residual 3 A. NEC 250.4(A)(5) counts the earth out of the effective ground-fault current path, so any amps returning through a rod are amps on a parallel path.
- Size from the breaker, worry about the connections. Each feeder keeps its own EGC sized from the overcurrent device ahead of it, per NEC Table 250.122. Eight amps continuous on a 6 AWG copper EGC is 12% of its 65 A ampacity at 75 °C from the NEC's copper ampacity table, so heat is not the problem; a resistive bond that runs warm and must carry hundreds of amperes during a real fault is. When several EGCs share one raceway, multiple equipment grounding conductors in one conduit covers the arrangement.
Keep it from coming back
- Clamp every feeder EGC at commissioning and once a year, at a known steady load. A clean feeder reads tens of milliamps.
- Re-clamp anything above 100 mA at a different load: on these feeders that is 1-2% of a 5-10 A unbalance, small enough to be induction and worth a second look. Treat 1 A as diverted neutral, a 10-20% share, and hunt the bond before the panel ships.
- Label neutral bars "neutral - no grounds" and record the one bond location on the one-line drawing.
- Torque-check neutral and ground bars at each service interval; an IR camera finds a resistive bond as a warm lug before the clamp does.
- Repeat the neutral-bar-to-enclosure reading after any panel swap, before the panel is energized.
When to re-specify the enclosure
The enclosure is a member of this mesh, so the build decides whether it carries stray current.
Bare stainless removes the paint problem. NEC 250.12 requires paint, lacquer and enamel off the threads and contact surfaces at grounding and bonding connections, and paint gets missed around gland plates and mounting feet. Our 304 and 316L wall-mount enclosures, rated NEMA 4X / IP66 by the manufacturer; not UL listed, leave bare stainless at every thread and stud, so a ground bar or bonding jumper lands on metal that needs no stripping. Bolt the ground bar to the enclosure wall, bond the removable mounting plate with its own labeled jumper, and pick sizes on the stainless wall-mount enclosures page.
Non-metallic breaks metallic loops. Where the clamp shows induction rather than diversion, a fiberglass or polycarbonate enclosure takes the box out of the conductive mesh entirely; the EGC and the back panel still need bonding, as grounding a fiberglass enclosure and its back panel lays out.
On the order, ask for a ground bar sized to the EGC count, cutouts where the EGCs enter, and the mounting-plate bonding jumper. The enclosure grounding and bonding guide carries the fundamentals this article builds on.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Will a 30 mA RCD trip when stray current flows on the EGC?
Only when the current is unbalanced through its core. The EGC bypasses the sensing core, and a load's own current crosses it out and back, so a diversion on the line side reads zero. A load-side bond shows up as residual: a 30 mA device holds below roughly 15 mA and must trip by 30 mA. The 8 A in this pattern is about 270 times the trip level, so a load-side bond takes those circuits down quickly.
How much stray current on an EGC is dangerous to touch?
Judge it by touch voltage, not by the amps. In the worked example the enclosure sits 0.25 V above the source bond, so a 1 kΩ hand-to-hand path draws about 0.25 mA. The danger is conditional: if the neutral upstream of a bonded panel opens, that bond rises to line potential, and 120 V across 1 kΩ is about 120 mA, far past the 10-16 mA let-go band. That is why diverted neutral current gets removed.
Why does the genset EGC current climb as each feeder is re-landed?
Each landed EGC adds a parallel branch and drops the resistance of the ground mesh, so the mesh carries a larger share of the neutral unbalance. Eight 6 AWG feeder EGCs of 0.04 Ω each come to about 5 mΩ in parallel, which is why the genset-side reading climbs from 3 A toward 8 A as the feeders go back. The climb maps a network of parallel paths, so keep hunting bonds and metal until the residual sits at zero.
Should each generator have its own neutral-to-ground bond?
With a 3-pole transfer switch, no. The switch ties the neutrals together, so the system is one source with one bond. A 4-pole switch breaks the neutral too, gives each source its own system, and then each one needs its own bond. Moving the single bond from genset 1 to the MDP is the common hardening on a two-genset system: whichever genset is down, the bond and the neutral reference stay in service at the MDP.





