Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Earth bar or one earth stud for ten panel earth cables

Use an earth bar and give each of the ten branch earths its own terminal, with the incoming earth on its own screw. Eleven lugs under one stud nut share a single clamping operation, and lifting any one of them releases the lot; cap a shared stud at three lugs. IEC 60947-1 rates a screw terminal for one conductor unless its marking says otherwise.

NEMA4 Enclosure engineering team · Published November 12, 2026 · 6 min read

Short answer: fit an earth bar and give every cable its own terminal. Ten branch earths plus the incoming earth is eleven conductors meeting at one clamping point, and a single brass stud gives them one nut, one torque value and eleven contact interfaces. Keep a stud for one to three lugs — the incoming earth alone, a door bond, a backplane bond. The ten branch earths go on a bar, one screw each. Three lugs is the working ceiling most panel shops put on a shared point, and the rule behind it is written down: IEC 60947-1 rates a screw terminal for one conductor unless its marking says otherwise. Eleven sits past both numbers.

What the earth point carries in a fault

Walk the fault path first, because the path decides the hardware. A ground fault on a drive frame travels through that branch earth, across its lug, along the bar or the stud stack, into the incoming protective conductor and back to the source. Every interface in that chain carries the full fault current for the clearing time. At a 5 kA prospective current, each 10 mΩ of extra path resistance holds 10 mΩ × 5,000 A = 50 V during the fault. That is the conventional touch-voltage limit, so milliohms matter. Those are example inputs; scale them to the prospective fault current at your panel.

The standards put the earth point inside that event. IEC 61439, the low-voltage assembly standard, makes the protective-bonding circuit part of the assembly's construction: jointed and sized to carry fault current until the overcurrent device clears, with a marked PE terminal for the incoming conductor. The NEC sizes the equipment grounding conductor from the rating of the overcurrent device ahead of it, using Table 250.122 — 10 AWG copper at a 60 A breaker. NEC 250.96(A) adds that every metal part in the path is bonded to carry the fault current imposed on it. Both come back to one question about your earth point: will all eleven joints still be tight in five years? The enclosure grounding and bonding guide covers the path itself; the question here is how many conductors one termination may share.

Bar and stud at a glance

Same cabinet, same copper, very different maintenance arithmetic:

Earth bar Earth stud
Terminations 10-20 screw or box terminals, one conductor each One stack, every lug under one nut
Best count 4 or more earth conductors 1-3 lugs
Torque Printed at each terminal One value for the whole stack
Lifting one circuit Its screw only; the rest stay clamped Clamp releases on every lug
Spare capacity Empty screws, landed later Restack the pile
Inspection Every joint visible and reachable Inner lug faces stay hidden
Typical jobs Branch earths, incoming PE, enclosure and door bonds Incoming PE alone, single bond point, welded boss

Where the bar wins

Every lug you add to a stud divides one nut's clamp force across one more interface. A lug 0.2 mm out of flat, a burr or a washer in the wrong order leaves a high-resistance joint buried in the middle of the stack while the outer nut still reads at torque. Brass narrows the margin further, because its threads carry less clamp load than steel at the same torque, and tall stacks relax fastest under heat cycling and vibration.

Maintenance settles it. Undo one screw on a bar and the other ten conductors keep their torque. Undo one lug on a shared stud and the clamp releases on all eleven; putting the panel back means a restack, fresh contact faces and a retorque of ten circuits to service one. The three-lug ceiling exists because three is about the stack a person can assemble and retorque identically every time. Any restack happens with the panel isolated and proved dead.

A bar also gives each conductor its own printed torque, its own visible joint and empty screws for the next earth. UL 508A panel practice lands field wiring the same way: one conductor per terminal, marked for the size. When the count keeps growing, that is the moment to ask whether two ground bars in one enclosure serve the panel better than one crowded bar.

Where a stud is the right answer

A stud earns its place whenever the count is small or the part is metal. The incoming earth alone — one ring lug, flat washer, spring washer, nut — is a clean, inspectable joint, and the grounding conductor enclosure entry decisions happen upstream at the connector or gland. A door-bond jumper with one lug each end is a stud job when the door carries nothing else, and grounding enclosure doors sets the jumper size and routing. The backplane bonding vs ground bar point, backplate to enclosure, is another single-lug stud.

On a stainless body the stud often arrives as a welded or through earth boss: threaded, unpainted, already part of the bonding path. On a custom body you put that boss on the drawing before anything is cut. When you do share a stud, stack in order — heaviest lug against the stud shoulder, lighter lugs after, flat washer, spring washer, nut — torque once and mark it.

A 60 A panel worked through

Take a 480 V three-phase panel on a 60 A main breaker, ten branch circuits at 10 A each:

  • Incoming equipment grounding conductor: 10 AWG copper, the NEC Table 250.122 value at 60 A. On the IEC side, IEC 60364-5-54 sets the protective-conductor minimum: equal to the phase up to 16 mm², then 16 mm² for phases up to 35 mm², half above — so 16 mm² phases take a 16 mm² protective conductor.
  • Branch earths: ten conductors at 2.5 mm² [14 AWG], green or green with a yellow stripe; NEC 250.119 sets that marking for insulated grounding conductors of 6 AWG and smaller.
  • Bar: 14 positions — ten branch, one incoming, one enclosure and door bond, two spare — with terminals spanning 2.5-10 mm², so the same bar lands the 10 AWG incoming at about 5.3 mm².
  • The stack it replaces: eleven palms at about 2 mm each, 11 × 2 mm ≈ 22 mm of shared clamping under one M6 nut.

Fault check at 5 kA: hold the whole protective path in single-digit milliohms. Ten milliohms would hold 10 mΩ × 5,000 A = 50 V for the breaker's clearing time, while a fresh bolted lug joint sits well under 1 mΩ. The risk concentrates in the relaxed shared stack, not in a torqued bar.

The decision by conductor count

Earths at one point Termination to use
1 Stud or bar screw; one lug, one nut
2-3 Stud with a documented stack, or one bar screw each
4-9 Bar, one terminal per conductor
10 and up Bar with spare positions; split the panel when it crowds

A customer spec that reads "earth bar with individual connections" is standard European wording, and it follows EN 61439 practice plus the one-conductor rule. The bar ends that discussion. Fitting one costs less than the argument, and eleven conductors at a single point sit outside the one-conductor rating every screw terminal carries.

What to specify

  • Bar: tinned copper, screw or box terminals, count = conductors + incoming + bonds + 2 spare; terminal range from 2.5 mm² [14 AWG] up to the incoming conductor size.
  • Mounting: bolted to the backplate with paint removed under both feet; NEC 250.12 requires paint, lacquer and enamel removed from contact surfaces at grounding and bonding connections.
  • Incoming earth: its own terminal, sized from the overcurrent device rating, with the gland or connector entry bonded to match.
  • Branch earths: one per terminal. Two earths at one point go on two terminals — the single-conductor rule behind two wires on one terminal applies to protective conductors too.
  • Torque: each screw to its printed value, recorded, and revisited on the schedule in control cabinet terminal torque inspection.
  • Body: on a washdown line that means a 316L stainless cabinet — ours are rated NEMA 4X / IP66 by the manufacturer, not UL listed — with the earth boss and gland plate on the drawing you approve. A custom body is delivered in 10 business days, counted from that approval, through the custom stainless cutout process.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
6 × 6 × 4 in304 stainless6 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
8 × 6 × 4 in304 stainless8 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
10 × 8 × 4 in304 stainless10 x 8 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

How many earth conductors can share one stud?

Treat one lugged conductor per stud as the rule, two or three with a documented stacking order as accepted shop practice, and anything above that as a bar job. IEC 60947-1 rates a screw terminal for one conductor unless its marking says otherwise, so eleven lugs under one nut sits outside any terminal rating. Ten branch earths plus the incoming earth is 11 conductors; a 14-position bar covers them with spares.

Can two earth wires go into one terminal opening?

Only when the terminal is marked for two conductors of those sizes; a typical 2.5 mm² [14 AWG] screw terminal carries one. At a bar, the fix is two terminals side by side. The clamp geometry in a screw terminal is designed around a single conductor, and a second wire wedged beside it leaves both under-clamped, which is the same reason power terminals take one conductor each.

Does the incoming earth get its own terminal on the bar?

Yes, and it is the largest one. Land it at the end nearest the bar's mounting bolt, so fault current reaches the enclosure bond over the shortest path. Size it from the overcurrent device ahead of it: 10 AWG copper at a 60 A breaker under NEC Table 250.122, or 16 mm² where the phase conductors are 16 mm² under IEC 60364-5-54. One conductor only in that terminal.

Can the earth bar sit straight on a painted backplate?

No. NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding and bonding connections, and the bar feet are exactly that surface. Strip both feet to bare metal or use mounting points prepared by the enclosure maker. On a stainless backplate you are already on bare metal; keep the threads clean and torque the mounting bolts to the bar's printed value.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start a junction box from 6 × 6 × 4 inRequest a custom quote

Stainless junction boxes: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides