Fit a 3% line reactor once the drives on a transformer pass 10-15% of its kVA, or when the utility holds your service to harmonic limits. Fit a load reactor only when the motor cable passes the drive's length limit: about 50 ft [15 m] on small 460 V drives with a standard motor, 60 ft [18 m] at 10 hp and 250 ft [76 m] at 100 hp on a NEMA MG1 Part 31 winding. Shorter than that, the motor side needs nothing, and a drive with a built-in DC link choke usually covers its own line side. What reactors always add is heat and plate space in the enclosure, and those two numbers decide the box. Here is the selection by condition, with the arithmetic that lands on your backplate.
The decision by condition
Work down this table before you order anything:
| Condition on the installation | What to fit |
|---|---|
| Drives pass 10-15% of the feeding transformer's kVA | 3% line reactor |
| Utility enforces harmonic limits, or several drives share one supply | 3-5% line reactor |
| Drive ships with a DC link choke | Nothing extra on the line side |
| Motor cable under 50 ft [15 m], 460 V, up to 7.5 hp | Nothing on the load side |
| MG1 Part 31 motor, 60 ft [18 m] at 10 hp to 250 ft [76 m] at 100 hp | Nothing on the load side |
| Cable past those limits, out to about 300 ft [90 m] | 3% load reactor |
| Cable from 300 to 1000 ft [90-300 m] | dV/dt filter, possibly at a lower switching frequency |
| Drive runs on 230 V | Nothing on the load side |
| Motor predates inverter duty, any cable length | 3% load reactor |
A line reactor and a load reactor are the same machine: copper on an iron core, rated in percent impedance. The two sides differ in what the winding is built for, so buy the part rated for its position. A reactor costs a small fraction of the drive and motor it protects, so the question is never whether to spend it — it is which side earns it.
When the line side needs the reactor
The six-pulse rectifier at the front of a drive draws current in pulses, rich in the 5th and 7th harmonics. That current heats the transformer feeding it and distorts the bus for everything sharing it. Once the drives add up to 10-15% of that transformer's kVA, a 3% impedance reactor is the standard fit; where several drives share the supply or the supply voltage is already distorted, move to 5%.
Run the share with your own numbers. A 2 hp 460 V drive draws 3.4 A at full load, which is 3.4 A × 460 V × 1.732 ≈ 2.7 kVA. On a 45 kVA transformer that is 6% — skip the reactor. Alone on a 25 kVA unit it is 11% — fit the 3%.
IEEE 519 is the harmonic standard utilities write into connection conditions; it sets the distortion allowed where your service meets the grid. When it applies to you, the line reactor is the first move toward meeting it. The reactor also buffers line-side transients before they reach the drive's front end, and it isolates drive noise from the supply. When the target is conducted EMI rather than harmonics, the part choice differs — read line reactor vs RFI filter for VFD EMI before you order.
Many compact drives now ship with a DC link choke fitted as standard. It does about the 3% job inside the case, with none of the heat landing on your backplate; the DC choke vs AC line reactor comparison covers that trade. A 3% reactor drops about 3% of supply voltage at full current, and a drive sized with headroom shrugs that off.
When the motor side needs the reactor
To the switching edge, the motor cable is a transmission line, and the open end at the motor roughly doubles the wave. A 460 V drive holds its DC bus near 650 V, so the motor terminals can see 2 × 650 ≈ 1.3 kV peaks — above the roughly 1000 V a winding built before inverter duty takes. NEMA MG1 Part 31 defines the inverter-duty winding. One published lead-length rule for those motors runs 60 ft [18 m] at 10 hp and 250 ft [76 m] at 100 hp, with linear interpolation between. Check the motor's plate for the marking; what an inverter-duty nameplate must show under MG1 Part 31 lists what to look for.
For standard motors, one drive maker's application table allows about 50 ft [15 m] of unfiltered cable for 1-7.5 hp at 460 V. A 3% load reactor stretches the allowed run to the 300 ft [90 m] class. Past that, a dV/dt filter carries 300-1000 ft [90-300 m], per a drive maker's application note — which also warns you may have to set the drive to a lower switching frequency to use one.
There is a second reason for the load reactor on a critical axis. A drive's short-circuit protection is built to limit collateral damage downstream; it is not built to save the drive's own transistors. The reactor's inductance slows the rise of a bolted fault on the motor cable, giving that protection time to trip first. For a motor mounted where you cannot reach it, that alone earns the part.
On a 230 V system, leave the load reactor out. The reflected peak is about 2 × √2 × 230 ≈ 650 V, under what a standard winding takes, so the part only adds watts.
Sizing and mounting carry their own numbers. A load reactor overheating at high carrier frequency is usually mis-sized, and mounting and grounding a VFD output reactor in an enclosure sets where it sits on the plate and how its core bonds.
The heat the reactors add to the enclosure
A sealed stainless box sheds about 3.7 W per square metre per kelvin (painted steel 5.5, plastic 3.5 — the enclosure heat calculator uses these). Inside rise = total watts ÷ (k × surface area), so every reactor watt lands in the same pot as the drive's.
Worked example — treat the inputs as replaceable assumptions:
- 2 hp [1.5 kW] 460 V drive, 35 W datasheet loss at rated load
- one 3% load reactor, 25 W from its datasheet
- plant at 25 C [77 F], drive rated to 40 C ambient
In a 20 × 16 × 8 in [508 × 406 × 203 mm] box the surface is 0.78 m², so k × A = 3.7 × 0.78 = 2.9 W/K. Total heat is 35 W + 25 W = 60 W, the rise is 60 ÷ 2.9 ≈ 21 K, and the inside air sits at 25 + 21 = 46 C — past the drive's 40 C. The reactor's share alone is 25 ÷ 2.9 ≈ 9 K [16 F]: one part turned a passing box into a failing one.
A 24 × 20 × 12 in [610 × 508 × 305 mm] box has 1.30 m², so k × A = 4.8 W/K and the rise is 60 ÷ 4.8 ≈ 12.5 K — 37.5 C inside, with 2.5 K in hand. Every 5 K of extra ambient eats the same margin: at 30 C [86 F] this box reads 42.5 C, and you then need cooling or a drive whose datasheet allows 50 C.
For one drive in one box, VFD enclosure rating, size and cooling walks the rating choice with the same arithmetic, and sealed enclosure heat load calculation traces where each watt goes.
You can also keep the reactors out of the drive box: small units mount in an enclosure of their own beside it, and their heat stops counting against the drive's. Remember why the line side stays live in a separate enclosure — the reactor box is energized whenever the disconnect ahead of it is closed, so kill and lock the supply before you open either one.
Fitting reactors on the backplate
Give the reactor air: its maker's installation sheet calls for 4 in [100 mm] of side clearance and 6 in [150 mm] of vertical clearance for heat dissipation and access. It is the hottest passive part on the plate, so keep those clearances to the drive and the duct as much as to the wall.
Lay the plate top-down: disconnect and breakers at the top, line reactor beside them on short leads, drive next, load reactor between the drive and the motor gland. Duct spacing and rail placement follow the backplate layout guide. Run the motor cable in shielded VFD cable, bonded at both ends per VFD motor cable shield grounding, and route it away from control wiring the whole way.
Bond the reactor core and the enclosure to the ground bus, with paint off the contact surfaces — NEC 250.12 requires paint, lacquer and enamel removed at grounding and bonding connections. Leave bending room at the line terminals: NEC 312.6 sets wire-bending space at terminals by conductor size for cabinets and cutout boxes. The glands that carry the cables hold the enclosure's rating, and cutouts and glands planning covers their sizes and placement. Our boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.
What to put on the order
| On the order | What to write |
|---|---|
| Size | The box that passes the heat arithmetic — 24 × 20 × 12 in [610 × 508 × 305 mm] in the example |
| Material | 304 stainless for general plant air; 316L where washdown and chlorides reach the box |
| Backplate | Drilled and tapped for drive, reactors and duct, keeping the 4 in [100 mm] side and 6 in [150 mm] vertical clearances |
| Cutouts | Gland positions for line, motor and control cable, taken from the finished layout |
| Rating | NEMA 4X / IP66 by the manufacturer; not UL listed |
Carry your inside dimensions and module count through the enclosure selector, and send the layout with the order. You set the material, the three dimensions and every cutout, and the box is cut from one piece — delivered in 10 business days from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 12 in | 304 stainless | 24 x 20 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a 230 V drive need a load reactor?
No. The reflected-wave peak is about twice the DC bus: 2 × √2 × 230 ≈ 650 V at the motor terminals, under the roughly 1000 V a standard winding takes. A load reactor there only adds watts to your enclosure and degrees to the heat arithmetic, so leave it out and spend the plate space on shield grounding instead.
Can the same 3% reactor serve the line side and the load side?
Buy the part wound for its position. A line unit carries the harmonic-rich input current; a load unit carries PWM current at the carrier frequency and dissipates more for the same impedance. A line reactor moved to the output runs hot and ages early, and its losses land in your box either way.
Do I need a line reactor if the drive has a DC link choke?
Not for harmonics. The built-in choke does about the 3% job inside the case, and its heat is already inside the drive's own rating. Add a line reactor anyway when several drives share one transformer, when the utility enforces harmonic limits, or when the supply throws switching transients at your equipment.
How much heat does one small reactor add to a sealed enclosure?
Take the watts from the reactor's datasheet; the small current classes run in the tens. In a 20 × 16 × 8 in [508 × 406 × 203 mm] stainless box, 0.78 m² at 3.7 W/m²K, a 25 W reactor alone lifts inside air about 9 K [16 F]: 25 ÷ 2.9 W/K. That is often the margin between a passing and a failing box.
The motor cable is 40 ft and the motor is 30 years old, so do I fit the load reactor?
Yes. The 50 ft [15 m] limit assumes a winding built for inverter peaks; a motor from before that era takes the full 1.3 kV reflected edge on a 460 V drive, and it fails in the winding, where you cannot reach it. The 3% reactor trims that peak for the cost of its watts.





