Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Load reactor overheating at high carrier frequency: size it right

Raising the carrier from 4 kHz to 12 kHz multiplies a load reactor's high-frequency core loss by about nine while copper loss stays flat: the example reactor went from an 82 C to a 150 C surface and failed. Return to 4 kHz, split the motors between reactors, or size the replacement from measured fundamental current and the maker's carrier derating curve at 12 kHz.

NEMA4 Enclosure engineering team · Published November 12, 2026 · 10 min read

An output reactor that ran cool for months can cook itself in a week after one drive setting changes. The carrier frequency is the usual culprit: tripling it from 4 kHz to 12 kHz multiplies the reactor's high-frequency core loss by about nine while the copper loss from the motor current stays exactly where it was. The worked case below is a 10 hp drive feeding five 1.5 hp motors through one 0.8 mH reactor rated 18 A fundamental and 27 A maximum; its surface climbed from 82 C (180 F) to 150 C (about 300 F) and two units failed. The fix is the carrier setting, a split of the motor load, or a replacement sized from measured amps and the maker's carrier derating curve, never from the headline carrier figure on the datasheet.

Why does a load reactor overheat after the carrier frequency goes up?

The carrier change is the cause: tripling it multiplies the reactor's high-frequency eddy-current loss by about nine, because eddy loss grows with the square of frequency, while the copper loss from the motor current never moved.

A VFD chops its DC bus thousands of times per second to build the 25-30 Hz output the motors turn at, and every chopping edge drives a pulse of high-frequency flux through the reactor core (how PWM carrier frequency differs from the motor's fundamental frequency). Eddy currents in the laminations grow with the square of that switching frequency, and hysteresis loss grows roughly in proportion to it. The copper I²R loss follows the fundamental current alone, which a carrier change never touches.

Read the symptoms first, because each one points at one of the three causes:

  • Browning varnish or a hot-varnish smell within days of a carrier change points to core loss, the cause in this case.
  • A core measurably hotter than its winding points to ringing between the reactor and the motor cables.
  • A melted or discolored terminal block means heat is leaving through the connections, and the wire on those terminals is already past its insulation rating.
  • Overload relays that trip once the reactor comes out point to cable charging current, which the reactor was suppressing.
  • A cool drive beside a cooked reactor is expected: the drive's derating curve and the reactor's thermal budget are two separate budgets.

Rank the causes in order: carrier-driven core loss first, ringing second, plain fundamental overload third. The third clears itself here, because five 1.5 hp motors at 460 V draw about 2.4 A each, some 12 A together, against an 18 A fundamental rating (values from the NEC full-load current tables). The winding ran at two-thirds of nameplate current, so motor load never melted anything.

How do you split copper loss from high-frequency core loss?

Measure the fundamental current and the winding resistance, compute copper loss as 3 × I² × R with R corrected for winding temperature, and the difference between that and the heat the surface throws off is the high-frequency loss you have to control.

Four example inputs stand in for measurements of your own: 0.018 Ω per phase measured cold at 20 C, a 95 C winding in service, 0.10 m² of exposed surface on an 18 A frame, and 12 W/m²K of combined natural-convection and radiation coefficient at modest rise in still air. Replace each with your numbers; the method is the point.

Copper first, identical at both carriers. Copper resistance rises 0.39 % per kelvin, so the winding at 95 C reads 0.018 × (1 + 0.0039 × 75) = 0.023 Ω per phase. With the measured 12 A through the winding, copper loss is 3 × 12² × 0.023 = 10 W.

Next comes the surface balance, the same arithmetic used to estimate a box's thermal resistance from its heat load. At the original carrier the case surface read 82 C in a 35 C cabinet, so ΔT is 47 K and the reactor rejects 12 × 0.10 × 47 = 56 W. At thermal equilibrium that equals the heat generated, which puts the core and ringing share at 56 - 10 = 46 W.

The higher-carrier measurement pins the verdict. At 150 C the same balance gives 12 × 0.10 × 115 = 138 W, and subtracting the 10 W of copper leaves about 128 W of core heat, some 2.8 times its earlier value. The square-law screen predicts 9 × 46 = 414 W and overshoots, because radiation climbs with the fourth power of absolute temperature and a constant coefficient reads low at 115 K of rise. Treat the screen as the ceiling and the measurement as the verdict; either number cooks the unit.

Value Original carrier Tripled carrier
Measured surface temperature 82 C (180 F) 150 C (about 300 F)
Copper loss at 12 A 10 W 10 W
Total heat rejected 56 W 138 W
Core and ringing loss 46 W about 128 W
Square-law screen for core loss 46 W baseline 414 W

Ambient moves the margin too: in a 45 C cabinet the same 82 C surface rejects about 44 W, some 20 percent less, before the carrier even changes. A reactor divides its heat the way a transformer does, copper in the winding and iron in the core, and transformer heat loss in a sealed enclosure at partial load works that split from the cabinet side.

Is ringing between the reactor and the motor cables heating the core?

Compare core and winding temperatures first: a core running hotter than its winding points to ringing between the reactor and the cable network, and the tripling feeds that ringing three times as many switching edges per second as before.

Run each setting for about twenty minutes, then aim an IR thermometer at the laminations and at the winding wire. Each switching edge makes the cable network and the reactor trade energy, and the iron takes its toll as heat; longer motor cables feed the exchange. Ringing has a cousin at the cabinet wall, covered in induced heating at enclosure cable entries.

To see the exchange directly, wind a few turns of wire around one leg as a measurement loop and watch the loop voltage on a scope. Heavy oscillation after every edge, at a frequency above the switching itself, confirms it. Tripling the carrier then triples the excitation cycles per second, which is why the core ran away at the higher setting and sat still at the lower one.

A resistor across the reactor can damp the exchange, and reactor makers sell units with damping built in. Its resistance, its pulse energy per edge and its continuous watts come from the measured ringing or from the filter maker; a guessed 10 Ω at 25 W is a question to ask them, never a rating to install. Lock out the drive and let the DC bus discharge before probing a unit that has already smoked; a VFD bus holds a lethal charge for minutes after power-off.

Can you run the five motors without the reactor?

Leave it in place: without the reactor, a 460 V five-motor group tripped its overload relays on cable charging current, and a scope on a 1 hp branch showed about 10 A peak-to-peak less current with the reactor in circuit.

The charging current is capacitance at work: every switching edge charges and discharges the motor cables, and the drive supplies that current on top of the motor current. On long runs the overload model reads high and trips, and drive makers' application notes warn that per-motor overload protection turns unreliable below about 3 hp in multi-motor groups for exactly this reason. The case reactor earned its place three ways at once: it cut voltage overshoot at the motor terminals, it cut the charging current the relays kept counting, and the scope comparison put a number on both. Remove it and the overheating stops, but the trips arrive in its place.

What carrier frequency should the drive run at?

Run it back at the original 4 kHz setting, and step upward only with a thermometer on the reactor: the square law puts high-frequency heating at 4 times the baseline per doubling and 9 times it per tripling.

An 82 C surface is warm but sustainable. Magnet wire comes in standard thermal classes, Class F for 155 C and Class H for 180 C, and an 82 C skin leaves the winding inside real margin. A 150 C surface has none: add the 10-15 K hot-spot allowance reactor designers work to, and a Class F winding sits at or past its limit, which is how the two case units died.

Noise, the reason the carrier moved, mostly goes quiet at the first doubling as the switching tone leaves the ear's most sensitive band, and the next step buys little. So test one step instead of three: set 8 kHz, hold the load steady, and read the reactor surface after an hour. The screen puts that step at 4 × 46 = 184 W of core heat, overstated the same way the top setting was, so the thermometer decides; about 100 C (212 F) is the line to hold.

Carrier Core-loss screen from 46 W Screen total with copper Case outcome
4 kHz 46 W 56 W Ran indefinitely at an 82 C surface
8 kHz 184 W 194 W Untested here; thermometer decides, hold under 100 C
12 kHz 414 W 424 W 150 C surface, two reactors failed

The case curve allowed the higher carrier at this load; that curve sized the drive's transistors and left the reactor's iron to fend for itself. The rise in the case took minutes to an hour rather than days, and estimating how long an enclosure takes to overheat runs the same heat-capacity arithmetic for a box and its contents.

How do you size a replacement reactor for 12 kHz?

Keep the 0.8 mH (0.30 Ω per phase at 60 Hz) and size the replacement from the measured fundamental current plus the maker's carrier-frequency derating curve at that carrier, never from the headline 20 kHz figure on the datasheet.

Impedance first, because the 0.8 mH per phase sets both the overshoot protection and the charging-current relief: X = 2π × 60 Hz × 0.0008 H = 0.30 Ω per phase. Same mH, same protection, whatever frame you buy.

Current second. The copper side was never the problem here, 12 A measured against 18 A of fundamental rating, so the same frame works; a step up buys copper mass and surface area along with the amps, and a cooler core at the same load.

Third comes the number that decides: a written carrier derating for continuous duty at 12 kHz at the measured fundamental and the cabinet ambient. The 20 kHz datasheet line is a capability the maker measured under its own conditions; the curve, or a statement for the operating point, is the rating you can build around. One enquiry with 0.8 mH, 12 A measured, 18 A nameplate, continuous duty at the higher carrier and a 35-45 C cabinet gets that answer in writing.

If the derating declines, split the motors instead: four on the existing 18 A reactor, about 10 A of the total, and the fifth on a second 0.8 mH unit rated about 3 A. Every motor still sees 0.8 mH, each branch carries a fraction of the old heat, and the screening rule applies branch by branch with that branch's amps. A sine-wave filter is the remaining single-reactor path when the maker declines the carrier.

Write the pairing into the panel record, reactor model, mH, carrier setting and steady-state surface temperature, so the next reader knows why the carrier sits where it sits. Any future carrier change gets the square-law screen first and a one-hour thermometer check after.

When does the enclosure need a bigger cooling budget?

Count the reactor in the cabinet heat budget from day one: about 56 W at the original carrier and 138 W measured at the tripled one, on top of a 10 hp drive's own 150-220 W, all of it heat a sealed cabinet has to reject.

Drive losses run about 2-3 percent of rating, which is where the 150-220 W for the 10 hp unit comes from, and the reactor adds its operating share from the table above. Size the cabinet from the sum, at the carrier you intend to run, because the same box that holds the original budget fails the tripled one.

Layout keeps the loss from concentrating: mount the reactor low where the cooler air sits, leave open air above the laminations, and keep terminal blocks out of the heat plume. A block at 150 C sits far past the 90 C rating of THHN or the 105 C rating of MTW landed on it, so in this case the wiring was failing before the reactor was.

In a washdown or outdoor cabinet the honest fix is sealed cooling. A filter fan would move air cheaply and drop the rating at the same opening, because the weakest part sets what the assembly holds. An air-to-air heat exchanger or an enclosure air conditioner sized from the total watts keeps a stainless cabinet, rated NEMA 4X / IP66 by the manufacturer and not UL listed, at its rating while it rejects the heat. Run the sum through the enclosure heat calculator, and sizing the VFD cabinet from heat loss instead of horsepower works the same budget for bigger drives.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
30 × 24 × 10 in304 stainless30 x 24 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

The reactor datasheet says 20 kHz carrier — why did it still fail at 12 kHz?

The 20 kHz line is a switching capability measured under the maker's own test conditions, and it carries no statement about temperature rise at your load. In the worked case, core heating went from 46 W at the original setting to about 128 W implied at the tripled one, with the surface at 150 C. The rating you can build around is a written derating for your current, your carrier and your cabinet ambient.

Is 8 kHz a safe middle step for quieter motors?

The screen puts the mid-step at about 184 W of core heat against 414 W at the top setting, under half the core heating for most of the quieting. The screen overstates, as the top-setting comparison showed, so read the reactor surface after an hour at steady load and hold it under about 100 C (212 F).

What should the order for a replacement load reactor specify?

Keep 0.8 mH per phase, 0.30 Ω at 60 Hz, and the 18 A fundamental frame over the measured 12 A; keep a maximum-current rating that still covers the starting surge, like the case nameplate's 27 A. Above all, require a written carrier derating for continuous duty at the higher carrier at the cabinet ambient, or split the motors across two 0.8 mH reactors of about 10 A and 3 A.

Does a damping resistor across the reactor stop the ringing heat?

It can, once the values come from measurement or from the reactor maker: a resistance matched to the ringing, pulse energy per switching edge, and continuous watts from the observed oscillation. The often-quoted 10 Ω at 25 W is a starting question rather than a rating, and an undersized damping resistor fails by the same heating that failed the reactors.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 16 × 12 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job

Keep reading

More on outdoor, heat and moisture

All articles

Buying guides

The guides behind this answer

All guides