Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

VFD location: long supply cable or long motor cable

Put the VFD next to the motor and let the supply feeder take the distance. Keep an unfiltered motor lead under about 15 m (50 ft), the point where drive manuals start calling for an output reactor or dV/dt filter, and size the feeder to hold voltage drop at or under 3% of nominal at rated input current. A 40 ft motor lead with a 200 ft feeder on 12 AWG copper passes both limits.

NEMA4 Enclosure engineering team · Published November 13, 2026 · 9 min read

Short answer: mount the drive near the motor and let the supply feeder carry the distance. Keep the unfiltered motor lead within about 15 m (50 ft), the planning figure many drive manuals work to before they call for an output reactor or dV/dt filter. Size the feeder so voltage drop stays at or under 3% of nominal at the drive's rated input current. The motor cable carries PWM edges that distance turns into reflected peaks and charging current. The supply feeder carries 50/60 Hz current, and its only real cost is a few volts of drop. A 40 ft (12 m) motor lead with a 200 ft (61 m) feeder on 12 AWG copper passes both limits; the arithmetic follows.

Why distance hurts on the motor side

A VFD builds its output by switching the DC bus thousands of times per second, with edges that rise in 100 ns or less. At those speeds the motor cable acts as a transmission line. The motor's impedance sits far above the cable's, so each edge reflects at the terminals with the same polarity and stacks on the incoming pulse. Past the length where the reflection builds fully, the peak at the motor terminals approaches twice the incident voltage. A 480 V drive rides a DC bus of about 650 V (1.35 × 480 V), so the terminal peak lands near 1,300 V; a drive maker's application report on long motor leads records peaks around 1,500 V.

The length that matters comes from edge rise time against round-trip travel time. Voltage runs down a power cable at roughly 150 m per microsecond, about half light speed. A 100 ns edge fully doubles past about 7.5 m (25 ft) of cable; a slower 400 ns edge needs about 30 m (100 ft). Modern drives switch faster than the ones those long cable limits were written for, which is why the motor-cable table in your drive's manual is the number that counts.

Cable capacitance adds a second cost. Shielded 4-core motor cable runs on the order of 200 pF per metre, and the drive charges it at every edge. At 15 m that is 3 nF, and forcing 650 V across 3 nF in 100 ns pulls a peak of C × dV/dt = 3 nF × 6.5 V/ns, about 20 A per switching instant. The figure scales linearly with length: a 60 m lead asks the output stage for spikes near 80 A that the nameplate never shows. Common-mode voltage rides the same cable, feeding bearing currents and radiated noise into controls. That closes the case for a short motor lead.

Why the supply side takes distance better

The input side of the same drive draws 50/60 Hz current with light harmonic content, and copper carries that for hundreds of metres when you size it. There are no fast edges on the feeder to reflect and no capacitance effect worth naming. The costs are voltage drop, conductor area, and housing the disconnect and overcurrent device where the installation wants them.

Hold feeder drop at or under 3% of nominal at the drive's rated input current. The 3% feeder figure is the NEC's informational design guidance, which pairs a 3% drop in feeders and branches with 5% total to the load, and it leaves most of the drive's input-voltage band in reserve for supply swings. Work the drop from round-trip length and resistance; the standard copper values at operating temperature are 1.93 Ω per 1,000 ft for 12 AWG, 1.21 Ω for 10 AWG and 0.764 Ω for 8 AWG.

Size the equipment grounding conductor from the feeder's overcurrent device using NEC Table 250.122, and when drop pushes the phases up a size, take the grounding conductor up with them. Bond the drive box into that path as the enclosure grounding and bonding guide describes. Where line-side harmonics or RFI are the issue, the AC line reactor vs RFI filter comparison points you at the input-side tool; feeder length is not the lever.

The numbers that set the layout

Four values settle the layout before any conductor is cut:

Decision Planning value Basis What moves it
Motor lead, unfiltered and shielded 15 m (50 ft) or less the planning figure used across drive manuals before a filter is called for edge rise time: a 100 ns edge doubles past 7.5 m (25 ft), a 400 ns edge past 30 m (100 ft)
Motor lead with output reactor or dV/dt filter tens to hundreds of metres one drive maker's filter application note covers leads over 300 ft (90 m) up to 1,000 ft (300 m) filter type and the manual's cable table
Feeder voltage drop 3% of nominal or less at rated input current NEC informational guidance: 3% feeder, 5% total to the load length and size: 12 AWG at 8 A holds 3% to about 270 ft (82 m)
Charging current at the output about 200 pF per metre of shielded cable cable-maker tables; peaks grow linearly with length 15 m gives about 20 A of peak per edge at 650 V; 60 m gives about 80 A
Motor insulation inverter-duty for long leads NEMA MG-1 definite-purpose inverter-fed motor construction standard-duty insulation is not built for repeated doubled edges

Worked example: a 40 ft motor lead and a 200 ft feeder

The setup: a 5 hp (3.7 kW) motor on a 480 V three-phase drive. Take the rated input current as 8 A, a typical figure at this size; read the exact number from the nameplate. The plan puts the drive box 200 ft (61 m) from the supply panel and the motor 40 ft (12 m) from the box.

Motor side: 12 m sits inside the 15 m (50 ft) planning limit, so the lead runs shielded and unfiltered, with the shield clamped 360 degrees at the drive end. No output reactor on this layout.

Feeder side, 12 AWG copper, 400 ft round trip:

  • Drop = 1.732 × 8 A × (400 ft × 1.93 Ω/1,000 ft) = 1.732 × 8 × 0.772 Ω = 10.7 V
  • 10.7 V ÷ 480 V = 2.2%, inside the 3% target
  • Ampacity check: the NEC's copper ampacity table at 75 °C gives 12 AWG 25 A, far above the 8 A load

Stretch the same feeder to 300 ft (91 m) and the drop becomes 1.732 × 8 × 1.158 Ω = 16.0 V, or 3.3%, over target. One size up, 10 AWG at 1.21 Ω per 1,000 ft, brings it back to 1.732 × 8 × 0.726 Ω = 10.1 V, or 2.1%. That is the trade in one line: the supply side buys distance with conductor area, the motor side buys it with filters and insulation ratings.

What the drive manual covers and what it leaves to you

The manual's motor-cable table is the drive's own tested envelope at its switching speed. If the table stops at 50 m and the run is 90 m, the fix is the filter the manual names for the next band. The table covers the drive side only. It says nothing about your feeder length, which is your voltage-drop calculation, nothing about your cable's capacitance per metre, which varies by construction, and nothing about whether the motor insulation is inverter-duty. Where the manual gives a limit, the manual wins; where it is silent, the 15 m (50 ft) planning value above decides.

What the near-motor location changes in the enclosure

Heat decides whether the near-motor box works. Budget the drive's watts loss from its manual; for the example, assume 130 W, roughly 3.5% of the 3.7 kW shaft rating. Sealed stainless sheds heat through its walls at k = 3.7 W/m²K, the value this site's heat guides use for 304 and 316L. Count the four walls plus the top, with the back against the wall, and the internal rise is ΔT = P ÷ (k × A).

The 20 x 16 x 8 in wall-mount box presents 896 in² (0.58 m²) of that surface, so ΔT = 130 ÷ (3.7 × 0.58) ≈ 61 K. At a 25 °C shop that puts the air around the drive near 86 °C, far past the 40 °C (104 °F) ambient standard for drives. Holding the rise to 15 K takes A = 130 ÷ (3.7 × 15) ≈ 2.3 m².

The 48 x 36 x 12 in box presents 3,744 in² (2.42 m²) and lands at ΔT ≈ 15 K. A 25 °C shop then sits right at the drive's 40 °C limit, so take the next size up or plan cooling. Painted steel moves k to 5.5 W/m²K and trims about a third off the rise, which still leaves a small box far too hot. Run your own load and ambient through the enclosure heat calculator, and use the fuller method in sizing a VFD enclosure from heat and clearance.

Rating follows the location as well. A drive box bolted to a washdown machine wants 316L stainless, manufacturer-rated NEMA 4X / IP66 — not UL listed — and every penetration has to hold that rating with it, because one gland below IP66 drags the whole assembly down. Enter the supply feeder and the motor lead at separate points, and keep motor output conductors out of the feeder's raceway; VFD output cables in the same conduit is a failure mode of its own. Clamp the motor cable shield 360 degrees at the gland plate; the termination details live in VFD motor cable entry: locking connector or conduit and shielding VFD motor and remote wiring in a steel enclosure.

If the box holds its own disconnect or breaker, keep the centre of the operating handle no higher than 2.0 m (6 ft 7 in) above the floor, the height NEC 240.24(A) sets for overcurrent handles. Leave room for the door to swing and for the service space the enclosure mounting guide shows.

The decision, case by case

  • Motor within 15 m (50 ft) of a sensible drive spot. Drive at the machine, feeder sized to 3%. The worked layout — 200 ft (61 m), 12 AWG, 8 A — is the standard answer.
  • Motor lead that must run 15 to 90 m (50 to 300 ft). Keep the drive near the motor and add the output reactor or dV/dt filter sized for the run; the output reactor and dV/dt filter cable-length sizing guide walks that selection.
  • A feeder that cannot hold 3% at workable conductor sizes. Once 8 AWG copper, good for about 680 ft (207 m) at 8 A, runs out, flip the layout: drive back at the supply panel and a filtered motor lead instead.
  • Washdown, brine or salt air. 316L, sealed, sized on heat, with active cooling rather than a filter fan, which would set the assembly's rating to the fan's own.
  • Before ordering anything, read the drive manual's motor-cable table and the nameplate input current; they set the filter decision and the feeder size.

Commissioning check: lock out, tag out and verify absence of voltage before wiring, then measure the input voltage at the drive terminals under load and compare it with the nameplate band. Recurring undervoltage trips point at the feeder; overcurrent trips at speed, or noise in controls, point at the motor side.

What to put on the order

Enclosures in this article

EnclosureMaterialOutside H x W x D / displayRating
48 × 36 × 12 in304 stainless48 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 12 in316L stainless48 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

How long can the motor cable be before the drive needs an output filter?

Plan on 15 m (50 ft) unfiltered. Past that, fit the output reactor or dV/dt filter the manual names; with filtering, one drive maker's application note covers motor leads from over 300 ft (90 m) up to 1,000 ft (300 m). The manual's motor-cable table governs, because it is written for that drive's switching speed, and faster switches shorten the unfiltered limit.

How long can the supply cable to a VFD be?

As long as the drop stays within 3% of nominal at rated input current. For the 8 A, 480 V drive in the article, 12 AWG copper holds 3% to about 270 ft (82 m), 10 AWG to about 430 ft (131 m), and 8 AWG to about 680 ft (207 m). Past that, compare bigger copper against moving the drive.

Can I mount the drive and motor side by side in one small enclosure?

Heat decides, not cable length. In the article's example, 130 W of drive loss in a 20 x 16 x 8 in stainless box raises the internal air about 61 K over ambient; two such drives double that to roughly 122 K. Sealed stainless needs about 2.3 m2 of surface per 130 W for a 15 K rise, which is the 48 x 36 x 12 in class, or active cooling in a smaller box.

Does the 15 m motor-lead limit apply to the supply side too?

No. The 15 m (50 ft) figure is a PWM edge limit that exists only on the motor cable; the supply side carries 50/60 Hz current with nothing fast to reflect. A 100 m (328 ft) feeder at 8 A on 10 AWG drops 11.0 V, about 2.3% of 480 V, and drop is its only limit.

Does an inverter-duty motor remove the motor cable length limit?

It removes the insulation part of the limit, not all of it. Inverter-duty insulation is built for the doubled edges, but cable charging current still scales with length: at 60 m the spikes run about 80 A per edge, and bearing-current exposure grows with the cable too. Keep the manual's table in charge, and filter past the 15 m (50 ft) planning value.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides