Short answer: fit the DC choke whenever the drive has the terminals for it. It lives on the drive's own DC bus, so a factory-fitted unit adds nothing to your backplate or your heat budget, and it takes input-current THDi from roughly 95% at full load down to 35-45%. Fit the AC line reactor when the drive exposes no DC connection, or when the supply sees surges and capacitor inrush, because the reactor sits ahead of the rectifier where that work happens. Both do the same harmonic job, and most of it arrives by 3% impedance on the AC side or 5% on the DC side. What the reactor charges instead is cabinet space and heat: a 6 x 3 x 4 in [150 x 80 x 100 mm] footprint and 20-40 W, close to a 7 K rise inside a 24 x 20 x 10 in stainless box.
The two parts, side by side
A DC link choke is one wound assembly inside the drive, between the input rectifier and the bus capacitors. An AC line reactor is three coils in the supply leads, ahead of the drive's input terminals. The table carries the comparison; the sections after it carry the decisions.
| DC link choke | AC line reactor | |
|---|---|---|
| Sits | Inside the drive, on the DC bus | In the supply leads, before the drive terminals |
| Impedance that does the work | 5% | 3% |
| Input THDi at rated load | 35-45%, from roughly 95% unfiltered | 35-45%, from roughly 95% unfiltered |
| Backplate area | None beyond the drive, or at its DC terminals | 6 x 3 x 4 in [150 x 80 x 100 mm] for a 10 hp class drive |
| Heat added to the cabinet | 0 W factory-fitted; a field-added choke adds its own watts | 20-40 W at rated current |
| Voltage drop at full load | None at the terminals | 3% of line voltage, about 14 V on 480 V |
| Surges and inrush | Behind the rectifier: no help | First impedance the spike and the inrush meet |
| Wiring | Two leads onto the bus studs | Three in, three out: six terminations |
| Drive prerequisite | DC bus terminals or a fitted choke | Any drive |
What the impedance does to the input current
A diode front end with bus capacitors draws current in narrow recharge pulses near the voltage peaks, not in a sine wave. THDi counts the harmonic part of that current against the fundamental, and a bare front end of this type runs near 90-100% THDi at rated load. An inductance in the path stretches the pulses; an AC reactor reaches it from the line side, a DC choke from the bus side.
The useful range is narrow. A drives data bulletin on chokes versus reactors puts the majority of the achievable THDi reduction at or below 3% impedance on the AC side and 5% on the DC side; past those values the reduction flattens while the voltage drop keeps growing. A drive maker's harmonics application note lands the DC link choke's cut at roughly 40-60% of the distortion. Either part brings a drive of this class to 35-45% THDi at rated load, the number the worked example uses, and engineering guide to AC line reactors and DC link chokes walks the same ground in more depth. One boundary while you specify: a line reactor is not an EMI filter and does nothing for the radio-frequency story, as the AC line reactor vs RFI filter article separates out.
Where the DC choke wins
Read the drive's rating plate before ordering anything. If the choke is fitted, the harmonic job is done and an added reactor buys almost nothing unless a project target is still missed. When the drive exposes bare DC bus studs, a field-added 5% choke needs two leads inside the drive, shares the drive's own footprint, and calls for no new cutouts, so the box leaves the shop exactly as drawn. Its watts still join the cabinet heat budget, but one assembly at the drive's side beats a separate three-coil unit on the plate for space. In a washdown panel you order a 316L box small on purpose, and this is the difference between a spare DIN row and a bigger door. For the plate itself, the backplate and DIN rail layout guide sets the duct and rail spacing around whichever part you choose.
Where the AC line reactor wins
Three cases hand the decision to the reactor. The drive has no DC connection: compact and older frames expose no bus, and the reactor is the only passive part that bolts on without opening the drive. The supply is rough: the reactor is the first impedance a line spike meets, and it softens the capacitor inrush at power-up, which eases the breaker and contactor arithmetic in the servo drive inrush article. The box is full or hot: indoors you bolt the reactor to the wall beside the cabinet and its 20-40 W stays out of the heat budget, while outdoors it needs its own weather cover.
The drop is part of the deal. Percent impedance is percent voltage drop at rated current, so a 3% reactor takes about 14 V off a 480 V supply at full load and pulls the DC bus down with it. On a stiff supply that is harmless. On a feeder that already sags 5% at motor starts, the drive terminals sit near 442 V and the bus margin thins with them.
The worked example: amps, watts and box rise
Take a 10 hp (7.5 kW) drive on 480 V three-phase, 95% efficient at 0.98 displacement power factor, in a 24 x 20 x 10 in [610 x 510 x 254 mm] 316L box:
- Fundamental input current: 7500 W / (1.732 x 480 V x 0.95 x 0.98) = 9.7 A.
- Bare front end at 95% THDi: total RMS input = 9.7 A x √(1 + 0.95²) = 13.4 A.
- With the 5% DC choke at 40% THDi: 9.7 A x √(1 + 0.40²) = 10.4 A. The choke strips 3 A, about 22% of the heating current, off the input conductors before anything else changes.
- Reactor route: the same 35-45% THDi, plus 30 W of reactor loss, the midpoint of the 20-40 W that reactor catalogs list for this frame. When a reactor datasheet shows impedance and amps but no watts, the device heat loss article shows how to land on a number.
The box has 1.19 m² of outside surface. With the wall coefficient for stainless this site's guides use, k = 3.7 W/m²K, 30 W lifts the inside air by 30 / (3.7 x 1.19) ≈ 7 K [12 °F] over ambient. A 35 °C (95 °F) plant plus that rise settles near 42 °C (107 °F), past the 40 °C (104 °F) ambient this site's guides use for drives and most electronics. At that point you are into a heat exchanger or a larger box, not a bigger reactor. Run your own box through the enclosure heat calculator, and size the enclosure from heat and clearance the way the VFD enclosure size article walks through. A reactor inside changes the cooling budget, never the rating: our 304 and 316L enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed.
The decision, by situation
| Your situation | Order this | Why |
|---|---|---|
| Choke factory-fitted | Nothing | The 5% job is done; spend the effort on the heat check |
| Bare DC bus studs on the drive | 5% DC link choke | Full harmonic cut with no backplate area |
| No DC connection, clean supply | 3% AC line reactor, 12 A frame for a 9.7 A input | Same 35-45% THDi; budget 20-40 W and the footprint |
| Surge-prone supply or shared feeder | 3% AC reactor, or the choke plus the drive's MOV kit | The reactor meets the spike first |
| Box small, hot or sealed for washdown | The choke route wherever the drive allows | Saves the 6 x 3 x 4 in footprint and about 7 K in a 24 x 20 x 10 in box |
| Target still missed after the choke | Add a 3% reactor in front | The documented stack gains about a further 10% THDi reduction |
What goes on the order
- Impedance and type: 3% for the AC line reactor, 5% for the DC link choke, matched to the drive manual's parts list.
- Current frame: one size above the drive's rated input. A 12 A frame covers the worked example's 9.7 A input with 24% headroom, at the supply's voltage class.
- Backplate: 6 x 3 x 4 in [150 x 80 x 100 mm] plus lead room for the reactor, with duct fill held at or below 50% of the duct's interior cross-section, the cap wiring-duct fill tables set citing NFPA 79.
- Heat: add the reactor's watts to the heat check before the box size is fixed; at 35 °C ambient and 7 K of rise, plan the cooling in the same order.
- The box: send the cutout drawing and we build the stainless enclosure to it, delivered in 10 business days from your approval of the drawing.
Choke when the drive allows it, reactor when it does not or the line is rough, and let the 30 W decide the box size rather than the other way round.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 24 × 20 × 10 in | 304 stainless | 24 x 20 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I add an AC line reactor to a drive that already has a DC choke?
Yes. The data bulletin behind the numbers in this article documents the stack: a 3% impedance AC reactor ahead of a drive running a 5% DC choke adds about a further 10% reduction of input-current THDi. The combination also adds the reactor's voltage drop and its 20-40 W of heat to the cabinet, so reach for it when a harmonic target is still missed after the choke alone.
Can the AC line reactor live outside the enclosure?
Yes, indoors. A bracket on the wall beside the cabinet keeps the 20-40 W and the 6 x 3 x 4 in [150 x 80 x 100 mm] footprint out of the box, and the enclosure rating is untouched. Outdoors the reactor needs its own weatherproof cover, because a bare reactor on a wall is no enclosure at all.
Does a DC choke protect the drive against supply surges?
No. The choke sits on the DC side, behind the input rectifier, so a line spike reaches the semiconductors before it reaches any inductance. That is why drives specified with a 5% DC link choke are paired with MOV surge protection on the input. A 3% AC line reactor meets the spike first, which is the second reason to choose one.
What impedance should I order for each part?
Order 3% for the AC line reactor and 5% for the DC choke. The published curves flatten past those values, so deeper impedance mostly buys voltage drop: a 5% AC reactor would drop 24 V of a 480 V supply at full load for little further THDi cut. Match the value to the drive manual's own parts list.
Will the choked drive meet an IEEE 519 distortion limit?
For a single small drive, usually yes. IEEE 519 sets its allowances as total demand distortion at the point of common coupling, scaled to the supply. The worked example's choked drive emits about 3.9 A of harmonic current; against a 500 A plant demand that is under 1% TDD, inside even the tightest 5% band. A bank of drives or a soft generator supply is a different measurement.