Short answer: fit neither device first. VFD EMI is common-mode current from the inverter's switching edges, and it leaves the panel on the motor cable, so a braided-screen cable bonded at both ends removes more noise than any line-side part. After that the two devices split the job. An AC line reactor cleans the supply at 60 Hz: on a 6-pulse drive it cuts input current distortion from roughly 80% without added impedance to about 45% with 3%. An input RFI filter strips conducted RF noise from the supply across the 150 kHz to 30 MHz band. Pick the reactor for harmonics, inrush and supply disturbances, the filter for interference on radios and instruments, and plan for the filter's 10-30 mA of earth leakage before you wire the earth bar.
Which one fixes VFD EMI first?
Neither device is the first fix: VFD EMI is common-mode current from the inverter's switching edges, circulating on the motor cable, so a braided-screen cable bonded 360 degrees at both ends removes more noise than any line-side component.
The noise starts at the output bridge. Behind a 240 V input sits a DC bus near 340 V (240 × √2), chopped with edges of 0.1-0.3 µs. Stray capacitance from the motor windings to the frame turns each edge into a pulse: i = C × dv/dt. With 3 nF of winding-to-frame capacitance and a 2 kV/µs edge, that pulse peaks near 6 A, and it needs a path back to the drive.
With no screen, the path runs through the protective earth wire, conduit and building steel. A wide loop radiates; a tight coaxial return barely does. A line reactor sits on the input side and cannot touch this loop, because the pulse circulates between drive and motor without crossing the supply. Reactors work below about 3 kHz, while switching edges carry energy from tens of kilohertz up into the megahertz range.
Build the return first, then buy components. The page on VFD motor cable entry: locking connector or conduit covers the gland choice, shield termination at enclosure entry shows what to bond where the screen lands, and shielding VFD motor and remote wiring in a steel enclosure covers the walls' share of the return. The enclosure's steel joins the screen only through a circumferential bond; a pigtail leaves the current loose in the panel.
A ferrite ring over all three phase conductors at the drive end trims what remains. Pass the phases through together so the differential currents cancel, and keep the screen outside the ring so its bond stays continuous.
Do not bond the screen at one end only: between a drive and its motor, both ends terminate on bare metal.
What does an AC line reactor actually do?
A line reactor is series inductance on the drive's input terminals, sold as 3% or 5% impedance, and it cuts supply-side harmonics and input inrush in the band below about 3 kHz; it cannot touch the motor cable's noise.
A 6-pulse diode front end draws current in narrow pulses at the crest of each wave. The accepted figures for that topology at rated load put input current distortion at 80-100% with no added impedance, about 45% with a 3% reactor and near 30% with 5%. A DC bus choke inside larger drives does similar work from the rectifier's other side.
Reactors also blunt the input inrush that pops undersized fuses at power-up, and they shield the rectifier from dips, spikes and capacitor-switching events on a stiff supply.
The cost shows on two meters. Voltage: a 3% reactor drops the input 3% at rated current, a 5% reactor 5%, so the drive needs its minimum supply voltage to still hold at full load. Heat: a 10 A unit typically dissipates 10-20 W into the panel, on top of the drive's own losses.
What does an input RFI filter actually do?
An input RFI filter is a low-pass network of common-mode chokes and X and Y capacitors that strips conducted RF emissions from the drive's supply terminals across the CISPR 11 test band of 150 kHz to 30 MHz.
Inside are common-mode chokes and two capacitor families: X capacitors line-to-line, Y capacitors line-to-earth. Datasheets quote 30-60 dB of insertion loss across the band, and the share you keep depends on the high-frequency quality of the earth path at the filter case.
A filter delivers its rating only inside the arrangement the manufacturer measured. The drive manual names the EMC category (C1 to C4 under EN 61800-3), the filter it was tested with, the maximum motor cable length and the bonding conditions. Swap in another filter or an unscreened cable, and the stated class no longer describes the panel.
Mount the filter hard against the drive on the same metal backplate, with the paint scraped from under the case: NEC 250.12 requires nonconductive coatings removed from contact surfaces at grounding and bonding connections.
For the measurement split between RF and harmonics, the page on troubleshooting RFI and harmonics in three-phase drives walks the disabled-versus-enabled comparison.
How do the two compare side by side?
The two devices share almost nothing: the reactor works below about 3 kHz on the supply side, the filter works from 150 kHz to 30 MHz at the drive terminals, and only the filter adds earth leakage that changes your panel wiring.
| Property | AC line reactor | Input RFI filter |
|---|---|---|
| Band it treats | Below about 3 kHz, supply side | 150 kHz to 30 MHz, CISPR 11 conducted band |
| What it fixes | Harmonics, inrush, dips and spikes at the input | Conducted RF at the supply terminals |
| Effect on radio and instrument interference | Nearly none | The line-side fix once cable and bonds are right |
| Effect on input current THD, 6-pulse drive | 80-100% down to about 45% (3%) or 30% (5%) | Almost none |
| Standard sizes | 3% and 5% impedance | Current classes such as 6, 10, 16, 25 A |
| Earth leakage current | None | 10-30 mA typical per filter |
| Earth wiring consequence | Standard protective earth | Above 3.5 mA AC: two protective conductors or one of 10 mm² minimum (EN 61800-3) |
| Voltage drop | 3-5% at rated current | Negligible |
| Heat added | 10-20 W on a 10 A unit | A few watts |
| GFCI interaction | None | Trips a 4-6 mA Class A GFCI |
| Mounting | Anywhere on the line side | Hard against the drive, case on bare metal |
The leakage row decides the earth work and the band rows decide the purchase; everything else is fitting.
When does a line reactor earn its place?
Fit a 3% reactor when harmonics, nuisance bus-overvoltage trips or input inrush are the complaint; step up to 5% when the supply transformer is large, the feeder is long, or a harmonic limit such as IEEE 519 applies at the meter.
Harmonics leave fingerprints: transformers and neutrals run warm, capacitors fail early, and power-factor metering suffers. Utilities hold customers to harmonic limits at the point of common coupling under IEEE 519, and a 3% reactor is the usual first step toward those limits. Step to 5% on a stiff supply, a large transformer nearby, where the source impedance alone smooths little.
Feeders carry impedance too. Add the reactor's 3-5% drop to a long or light feeder and confirm the drive's undervoltage margin at full load before ordering.
Inrush and bus trips round out the case: drives that blow input fuses at power-up or trip on bus overvoltage at light load often settle once 3-5% of series impedance sits ahead of the rectifier.
When does an input RFI filter earn its place?
Fit an input RFI filter when the complaint is interference on radios, sensors or network gear, or when a specification names a conducted-emission class, and pick its rated current one standard step above the drive's nameplate input current.
If a specification names a conducted-emission class, the filter is part of the recipe the drive manual states; fit the named filter, cable length and bonds as one package.
If the complaint is interference after the cable fix, measure before buying: compare the same receiver with the drive output disabled and enabled. Noise that follows the output points back at the cable and its bonds; noise left on the supply wiring points at the line side, which is the filter's territory.
Size the frame by current. Read the drive's nameplate input current, not the horsepower, and take the next standard class above it; common steps run 6, 10, 16 and 25 A. The filter adds negligible voltage drop and a few watts of heat.
How much leakage current does the filter add to the earth path?
A typical input filter leaks 10-30 mA to earth at rated voltage, and once the value passes 3.5 mA AC, EN 61800-3 asks for a reinforced earth: two protective conductors, or a single one of at least 10 mm².
One caution before the wrenches come out: lock off the supply and wait the drive manual's bus-discharge time before opening the panel, because a 240 V input drive holds about 340 V on the bus for minutes after power-off.
The grounding and bonding guide covers the fault path the panel already needs; leakage current is a second, continuous flow on top of it.
The numbers for a 1 hp drive on a 240 V feed
Take a nameplate input current of 10 A (the example's assumption; replace it with the label value), a 240 V feed, a 15 ft [4.6 m] protective earth run in 14 AWG copper, and a filter datasheet quoting 20 mA of leakage at rated voltage.
- Filter class: 16 A covers a 10 A nameplate with margin.
- Leakage: 20 mA sits far past the 3.5 mA AC threshold, so the reinforced-earth rule applies — two protective conductors sized from the overcurrent device ahead of the drive using NEC Table 250.122, or a single conductor of at least 10 mm², which 6 AWG copper (13.3 mm²) covers.
- Breaker interaction: 20 mA dwarfs the 4-6 mA trip of a Class A GFCI, so a filtered drive on a GFCI branch trips at power-up; the drive manual names the RCD class it allows.
- High-frequency view: 4.6 m of 14 AWG is about 38 mΩ of resistance, but at roughly 1 µH per metre the run is 4.6 µH, and 2π × 1,000,000 Hz × 4.6 × 10⁻⁶ H ≈ 29 Ω of reactance at 1 MHz. The same wire looks about 760 times more obstructive to the switching noise than to a fault current, which is why the 360-degree screen bond, not the earth conductor, is the radio-frequency return.
Sizing those protective conductors is the same bonding work the grounding and bonding guide walks through, sized from the overcurrent device ahead of the drive. The 10 mm² provision serves fault safety and 50/60 Hz leakage; the screen bond serves the megahertz. A filtered panel needs both.
What goes on the order?
Order the parts in the sequence the noise dictates: screen cable and EMC glands for the motor run, a filter one current class above the nameplate, a 3% reactor only if harmonics are in the picture, and a box deep enough to hold both.
- Interference on radios, sensors or network gear: screened cable with both-end bonds first, an input RFI filter second, and almost never a reactor.
- Harmonics, a warm neutral, poor power factor or inrush trips: a 3% reactor, upgraded to 5% on a stiff supply.
- Both complaints together: reactor on the supply side, filter hard against the drive, earth built for 10-30 mA of leakage.
- No symptom and no specification: fix the cable and the bonds, and buy nothing line-side yet.
Cable and entry: braided-screen VFD cable for the motor run, an EMC gland or a 360-degree screen clamp at the enclosure wall, and stripped tails under 50 mm [2 in] at both ends. Device mounting: the filter on the bare-metal backplate beside the drive, the reactor upstream if harmonics made the list, with power wiring kept at least 4 in [100 mm] from control wiring.
Depth decides the enclosure. The filter wants to sit within about 8 in [200 mm] of the drive terminals, and a 20 x 16 x 8 in [508 x 406 x 203 mm] wall-mount box leaves that room with space for the glands. We build the 304 stainless version and the 316L twin to order, rated NEMA 4X / IP66 by the manufacturer; not UL listed. Delivery is 10 business days anywhere in the world, counted from your order, or from your approval of the drawing when you send cutouts.
Heat check for that box: about 15 W of reactor and filter loss raises the skin by roughly 5 C [9 F] at a 25 C [77 F] ambient. The skin is 2 × (20 × 16 + 20 × 8 + 16 × 8) = 1216 in² [0.79 m²], and 15 W ÷ (3.7 W/m²K × 0.79 m²) ≈ 5 C. Small on its own, but it stacks on the drive's losses; the wall-mount drive heat and humidity checklist carries the full budget.
Before you energize, walk the VFD enclosure wiring checklist: supply off, bonds proven, filter leakage accounted for, then power.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 316L stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a line reactor reduce EMI from a VFD?
Only at the low end. A reactor acts below about 3 kHz on the supply side, where harmonics and inrush live. The interference that upsets radios and instruments sits from 150 kHz to 30 MHz and travels on the motor cable. Fit the screened cable and both-end bonds first, then decide: reactor for harmonics, RFI filter for RF.
Will an RFI filter trip a GFCI breaker?
Expect it to. Typical input filters leak 10-30 mA to earth at rated voltage, while a US Class A GFCI trips at 4-6 mA. For a filtered drive, the drive manual names the RCD class or dedicated feed it allows; and above 3.5 mA of AC leakage, EN 61800-3 wants two protective conductors or one of at least 10 mm².
What filter current rating suits a 1 hp drive on 240 V?
Size by nameplate input current, not horsepower. A 1 hp drive on a 240 V single-phase feed typically draws about 8-10 A, so the next standard class, usually 16 A, is the pick. Read the leakage value from the filter datasheet at 240 V and keep the filter within about 8 in [200 mm] of the drive terminals.
Does a screened motor cable still matter once a filter is fitted?
Yes, and it matters more. The motor cable is the antenna and its screen is the return path for the common-mode pulse, which reaches about 6 A on a small motor with 3 nF of winding capacitance at a 2 kV/µs edge. A filter cleans the supply terminals; it leaves the output loop untouched. Bond the screen at both ends.
Can a line reactor and an RFI filter run together?
Yes, and it is the normal combination for a plant with both complaints. Put the reactor on the supply side, the filter hard against the drive on the same bare-metal backplate, and keep their leads apart from control wiring. The reactor drops the input 3-5%; confirm the drive still sees its minimum supply voltage at full load.