Short answer: unbolt it from the bench and put it in the panel. Bond the reactor's frame to the equipment-grounding path with its own green conductor — 12 AWG copper on a 20 A branch — landed on bare metal, and give it 4 in [100 mm] of free air above and below inside a grounded metal enclosure. The reactor sits between the drive and the motor, it adds real heat to the box, and its terminals carry line-voltage wiring, so it belongs inside the enclosure with the drive. Below are the placement, the bond, the clearances, the heat arithmetic and the checks, in the order you meet them.
Does the reactor go before the drive or after it?
After it: a reactor between the drive and the motor is an output reactor, sometimes called a motor choke, and it works on the drive's pulsed output; the same part ahead of the drive is a line reactor working on input harmonics.
Sellers use "line reactor" for both jobs, so wire to the circuit, not the label. On the motor side, the inductance sorts the frequencies for you: reactance rises with frequency, so the switching edges meet tens of times the impedance the working current sees. The motor terminals get a slower voltage edge and lower peak stress, which is why small high-speed spindles and long motor cables benefit most. Many drive manuals allow a longer motor cable with an approved output reactor fitted; your drive's document prints that length, and it is the cable limit to respect.
The mounting and bonding steps below are the same on either side of the drive. Choosing between input reactors and RFI filters on the line side is a different argument — see the line reactor versus RFI filter comparison.
Does the reactor frame need its own ground wire?
Yes — bond the frame to the panel's equipment-grounding path with a dedicated green conductor, 12 AWG copper on a 20 A branch, because a bolt through a painted bench gives you a loose joint exactly where a fault needs a low-impedance path.
NEC 250.96(A) requires metal parts serving as equipment grounding conductors — raceways, cables, equipment, enclosures — to be bonded so they safely conduct any fault current likely to be imposed on them. A winding-to-lamination failure inside the reactor puts line voltage on the frame, and the bond is the metallic route back to the source that lets the breaker clear. The earth carries none of that fault: NEC 250.4(A)(5) names the effective ground-fault current path and leaves the earth out of it. A bolted bench joint through paint is nobody's fault path — the same physics that makes welding return paths need a dedicated low-resistance bond.
Size the conductor from the rating of the overcurrent device ahead of it, using NEC Table 250.122, copper column:
| Breaker or fuse ahead | Copper equipment grounding conductor |
|---|---|
| 20 A | 12 AWG |
| 60 A | 10 AWG |
| 100 A | 8 AWG |
| 200 A | 6 AWG |
Insulated grounding conductors of 6 AWG and smaller are green, or green with yellow stripes, under NEC 250.119. At the frame, NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces unless the fitting is designed to bite through. Long-standing VFD practice is one continuous copper grounding conductor from the drive's PE terminal to the motor frame; tie the reactor bond to that conductor or to the bus it lands on. Never land the bond under a phase terminal — use the frame lug or a mounting foot. The enclosure grounding and bonding guide walks the rest of the system.
What enclosure should the reactor live in?
A grounded metal box carrying the rating the location demands: Type 12 for a clean, dry indoor panel, or Type 4X stainless steel wherever hose-directed water, washdown or outdoor weather can reach it.
Our stainless wall-mount NEMA 4X enclosures are rated NEMA 4X / IP66 by the manufacturer and not UL listed, and the builder carries a manufacturer rating for the type you set — Type 1, 3R, 4, 4X, 6P, 12 or 13. Indoors, Type 12 keeps out dust and dripping water. Washdown walls and food plants take 4X stainless: 304 for most indoor washdown and general outdoor duty, 316L where salt air, brine or chlorides reach the steel.
The box joins the grounding system through bonded conduit hubs or a bonding jumper, and the door needs its own bond so the fault path survives the hinges — enclosure door bonding has its own rules. Order the gland holes when you order the box: we punch and seal cutouts to UL 50's Table 71-1A knockout and fitting dimensions, which beats a field-drilled hole. The cutouts and glands guide covers hole sizes. Custom enclosures built to your width, height, depth and cutout list are delivered in 10 business days, counted from your approval of the drawing.
How much clearance does the reactor need?
Give it 4 in [100 mm] of free air above and below, and about 2 in [50 mm] sideways to the drive and neighbouring parts — the same space most drive installation sheets demand around the drive, because both parts shed their losses into that air.
A convection-cooled reactor dumps its heat from the laminations and the case, so the column of air above it is the heat sink. Keep it out of the drive's exhaust stream where the drive is fan-cooled, so each part breathes cooler air, and let the reactor's own sheet win if it prints a bigger number. Wire needs room too: NEC 312.6 sets the minimum bending space at terminals in cabinets and cutout boxes, with Table 312.6(A) applying where the conductor does not enter the wall opposite its terminal. Hold wiring duct to 50% of its cross-section, the ceiling NFPA 79-2012 section 13.5.2 puts in its fill tables. The backplate and DIN rail layout guide places rails and duct across the whole panel.
How hot will the box get with a reactor in it?
About 30 C above the room inside a 20 x 16 x 8 in stainless enclosure carrying a 2 hp drive and its reactor: 71 W of losses against a 3.7 W/m²K stainless wall, which lands you at 60 C inside on a 30 C day.
Work a small build end to end. Assume a 2 hp [1.5 kW] 230 V drive, single-phase input, three-phase output, sharing one sealed box with its output reactor, and take two datasheet values: drive efficiency 97% at full load, reactor loss 25 W at rated current. Replace both with your sheets before ordering.
- Drive output: 2 x 746 W = 1492 W; input = 1492 ÷ 0.97 ≈ 1538 W; drive loss ≈ 46 W.
- Reactor loss: 25 W (datasheet assumption).
- Heat into the box: 46 + 25 = 71 W.
- Box surface: 2 x (20 x 16 + 20 x 8 + 16 x 8) = 1216 in² ≈ 0.78 m²; assume 80% of it works on a wall mount, 0.63 m².
- Wall transfer for stainless: k = 3.7 W/m²K, this site's reference value.
- Temperature rise: 71 ÷ (3.7 x 0.63) ≈ 30 K, so 30 C ambient puts 60 C inside — and drives and most electronics are built for 40 C ambient unless a named datasheet allows more.
Holding 40 C at 30 C ambient allows only a 10 K rise, so this heat needs 71 ÷ (3.7 x 10) ≈ 1.9 m² of effective surface, about 2.4 m² total — roughly a 36 x 30 x 12 in box, which lands exactly on the line. At 35 C ambient that box sits at 45 C, over the limit.
The decision follows the room. Clean and dry indoors, a filtered fan on a Type 12 box moves 71 W easily and keeps the panel small. Washdown or outdoors, the box stays sealed: go up a size, or fit a sealed-loop cooler — an enclosure air conditioner or air-to-air heat exchanger rated for 71 W at a 10 K difference. A fan-filter kit drops a Type 4X assembly to the kit's own rating, so it belongs on the indoor build only. The drive half of this arithmetic is walked through in sizing a VFD enclosure from heat and clearance.
How do you mount and bond it, step by step?
Nine steps, one lockout first: kill and lock the branch, read the nameplate against the drive, dress the bond point to bare metal, run the green bond to the bus, mount with air around it, wire, measure under 0.1 Ω, then run it hot.
You need the enclosure with its backplate and a ground bus or lug, green bonding wire sized from Table 250.122, ring lugs and a crimp tool, a file or abrasive for the bond point, a torque driver, a micro-ohmmeter, and EMC glands for the motor cable.
- Open the breaker ahead of the drive, lock it out, and prove absence of voltage at the drive input terminals before you touch anything.
- Read the reactor nameplate against the drive: an output-duty part, rated for the drive's voltage class, with rated current at least equal to the output — motor full-load tables put a 2 hp, 230 V three-phase motor at 6.8 A, so that build needs 7 A or more.
- Find the frame's bonding point, a ground lug if it has one, otherwise a mounting foot, and dress it to bright metal as NEC 250.12 requires.
- Crimp a ring lug on the green conductor, land it on the dressed spot, and land the far end on the panel ground bus; wall or mounting plate for that bus is its own argument.
- Mount the reactor on the backplate with 4 in [100 mm] clear above and below and 2 in [50 mm] to the drive, out of its exhaust stream, hardware torqued to its marks.
- Run drive to reactor, reactor to the motor gland, three phases together and away from line-side and control wiring, any duct held to 50% fill.
- Clamp the motor cable's shield 360 degrees in an EMC gland at the wall; routing VFD output cables matters when drives share a raceway.
- Record the micro-ohmmeter reading from reactor frame to ground bus, then close the door.
- Run an hour of real duty and read the intake air temperature at the drive.
For the drive-side order of operations — stop, bond, filter — the VFD enclosure wiring checklist finishes the job.
What readings prove the job is done?
Two numbers prove it: under 0.1 Ω from the reactor frame to the ground bus on a micro-ohmmeter, and 40 C or lower at the drive's intake air after an hour of real work.
IT-equipment safety standards prove protective bonds with a 25 A test current and pass in the tens of milliohms; in the field, a micro-ohmmeter reading under 0.1 Ω frame-to-bus is a sound pass for a bolted joint. A reading that climbs when you wiggle the frame points at paint or an undertorqued fastener, so dress the joint and re-torque. Then run the panel at real duty and read the air where the drive draws it: 40 C passes, 45 C sends you back to the heat arithmetic. On the motor, a few volts AC from frame to ground is normal stray on a VFD system; tens of volts says the common-mode return is weak, so re-clamp the shield's 360-degree termination before blaming the reactor. When the symptom is bearing noise instead, the shaft grounding brush route takes that current out around the bearing.
Which mistakes break the bond or the rating?
Four cause nearly every failed reactor install: a bond lug sitting on paint, a bond landed under a phase terminal, a fan-filter on a washdown box, and a field-drilled hole left without a gland — each defeats the thing you built.
- A lug on paint. Coatings insulate; file the spot bright, torque the lug, and the sub-0.1 Ω reading follows.
- A bond under a phase terminal. That terminal carries load current and heat; the frame lug or a mounting foot is the bond point.
- A fan-filter on a washdown box. The assembly takes the kit's rating, so save filtered fans for clean, dry Type 12 rooms.
- A field-drilled hole with no gland. Burrs and an open hole leak water and break the type; order the cutouts with the box and let the enclosure builder punch them.
Get those four right and the reactor does its job quietly: bonded, breathing, and inside a box rated for the room it stands in.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 36 × 30 × 12 in | 304 stainless | 36 x 30 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does an output reactor turn the drive output into a sine wave?
No. A reactor is series inductance, and reactance is 2πfL: a 3 mH choke presents about 1.1 Ω at 60 Hz but about 75 Ω to a 4 kHz component, roughly 66 times more. It slows the voltage edges and trims peak stress at the motor terminals; the motor still sees a pulsed waveform, so vector-rated winding insulation and a shielded motor cable stay on the list.
Can the mounting screws ground the frame through paint?
Only where the coating is gone. NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding connections, unless the fitting is made to bite through. Screws through paint can read open on a micro-ohmmeter, while a ring lug on a filed spot reads well under the 0.1 Ω pass number to the ground bus.
Do you still need a shielded motor cable with an output reactor?
Yes. The reactor slows the differential voltage edges; common-mode current still flows from drive to motor and back, so keep the shielded VFD cable with its shield clamped 360 degrees in an EMC gland at the enclosure wall, plus one continuous copper grounding conductor between drive and motor frame.
How much does shortening the motor cable matter?
Less than you would hope. Cutting a 13 ft [4 m] run down to 10 ft removes about a quarter of the cable's charging current, and the reactor already limits the edge rate that charges it. The drive's stated maximum motor cable length is the number that counts, so measure the actual route and compare it with that limit.