Short answer: the shield is an earthed conductor wrapped around every core, so shielded motor cable stores several times more charge per metre than the same run unshielded, and the drive pays that charge on every switching edge. Typical drive instructions put the output-reactor limit at about 50 m [164 ft] shielded and 100 m [328 ft] unshielded. What flows is charging current, i = C × dv/dt, and it flows with healthy insulation all day. The fix lives in your enclosure — a reactor or a filter — fitted without giving up the shield. The values below are typical ones from drive documentation and cable practice; your drive's manual holds the table for its model.
Why does shielded cable hit the reactor limit at half the length?
Because the shield sits millimetres from each core and ties it to earth: shielded VFD cable typically runs 200-600 pF per metre per core to the shield, against well under 100 pF per metre to earth for unshielded cable in tray.
A drive output is a stream of square voltage edges, not a sine wave, so the cable is part of the load even when the motor idles. Every edge charges the cable's capacitance, and the closer the return conductor sits to the core, the more charge the edge moves. Drive manuals turn that into a length table. One family's operating instructions require an output reactor above about half the unshielded limit when the motor cable is shielded; another family allows roughly 300 m unshielded once a motor choke is fitted. The 2:1 pair is that maker's charge budget with margin on top, and cable geometry sets the real ratio for your run. To sort which reactor belongs on which side of the drive, see line reactor or load reactor: which one your VFD needs.
| Cable construction | Capacitance that matters | Typical published value | Reactor threshold, typical manuals |
|---|---|---|---|
| Shielded symmetrical VFD cable, shield bonded both ends | core to shield | 200-600 pF/m per core | about 50 m [164 ft] |
| Unshielded in tray or conduit | core to tray and earth | under 100 pF/m | about 100 m [328 ft] |
How much charging current does the shield add?
Work one run at 400 pF/m per core over the shielded example length on a 480 V drive: the cable moves about 13.6 µC per core on each edge, averaging near 110 mA per core at a 4 kHz carrier and spiking toward 11 A briefly.
Here is the arithmetic, with every input you would replace from your own datasheets:
- 480 V drive, so the DC bus sits at √2 × 480 ≈ 679 V, called 680 V here.
- 4 kHz carrier frequency; 400 pF per metre per core to shield; surge impedance 60 Ω.
- Total capacitance: 400 pF/m × 50 m = 20 nF per core.
- Charge per edge: Q = C × V = 20 nF × 680 V = 13.6 µC per core.
- Edge rate: about two edges per core per carrier cycle, so 2 × 4,000 = 8,000 edges per second.
- Average charging current: 13.6 µC × 8,000 /s ≈ 0.11 A per core.
- Peak at the edge: i = V / Z₀ = 680 V / 60 Ω ≈ 11 A, over in microseconds.
Run the same run unshielded in tray — call it 100 pF/m to earth and 130 Ω surge impedance — and you get 27 mA average with about 5 A peaks. Stretch that run to its 100 m [328 ft] manual limit and the average reaches 54 mA, still about half of what the shielded cable drew at half the length. The shielded threshold carries margin on purpose. The shield both raises the stored charge per metre and lowers the surge impedance from roughly 130 Ω to 60 Ω, so the drive is hit harder twice over.
Is the current in the shield a fault current?
No. Charging current is the cable's capacitance doing its job and flows with perfectly healthy insulation; an insulation fault is current through a damaged or contaminated path, and it shows on an insulation test at standstill.
With the shield bonded at both ends, charging current returns through the shield into your PE network and back to the drive. That is by design, and it scales with cable length, carrier frequency and supply voltage, so a long shielded run can sit near a drive's ground-fault threshold with nothing broken. Read the drive's exact fault code before changing hardware. Then isolate the cable and motor and insulation-test them: a good test result plus current only while the drive switches adds up to charging current, and the answer is a reactor or filter, not cable surgery.
What replaces the reactor on very long runs?
A dv/dt filter takes over: one drive maker's motor-lead guidance reaches about 600 ft [183 m] of total cable with a dv/dt filter, against about 300 ft [91 m] on a 3% impedance output reactor alone (application note AP040213EN).
| Device on the drive output | Typical reach | What it does |
|---|---|---|
| Direct output | about 50 m [164 ft] shielded, 100 m [328 ft] unshielded | the manual's base case |
| 3% impedance output reactor | to about 300 ft [91 m]; one drive family reaches about 300 m unshielded with a choke | series inductance slows the current's rate of change and damps the drive-cable interaction |
| dv/dt filter | to about 600 ft [183 m] | clamps the voltage rate of rise at the motor terminals |
| Sine filter | longest runs; use the manual's sine-filter table | near-sinusoidal output, lowest charging and leakage current |
The reactor treats the current; the dv/dt filter treats the voltage. A reflected wave at an open motor end can push terminal voltage toward 2 × 680 V ≈ 1,360 V on a 480 V drive, and that is what ages winding insulation on long leads. When your run is long and the motor is an older rewind, choose the dv/dt or sine filter for the voltage reason even where a reactor would cover the current alone.
Where does the output reactor go in the enclosure?
On the backplate between the drive's output terminals and the motor cable gland, with the clearance the reactor datasheet names — typically 4 in [100 mm] free above and below for convection — and with its losses added to the heat budget before you size cooling.
Order the plate drive → reactor → cable route down to the gland, keeping the duct and rail spacing from the backplate and DIN rail layout guide. Budget reactor losses like a dry-type transformer's, about 1-3% of the drive rating: 75-225 W for a 10 hp [7.5 kW] drive, on top of the drive's own losses. Fold that total into how to size an electrical enclosure before choosing between a sealed box and a cooler. Give large output conductors the bending space NEC 312.6 sets at terminals in cabinets and cutout boxes. One safety note: lock out, and give the DC bus its stated discharge time — typically 5 to 15 minutes — before opening output wiring. For PE bonding of the reactor itself and the torque work, see mounting and grounding a VFD output reactor in an enclosure.
Does the reactor change the shield bonding at the gland?
No. The reactor sits in the phase conductors, and the shield still bonds 360° at the gland and at the motor end — both ends, every time — because the shield is your high-frequency return path, not a spare earth wire.
Keep the pigtail from gland to PE bar short. A long pigtail is an inductor exactly where charging current lives, and it hands the noise back to the panel. The both-ends reasoning is in VFD motor cable shield grounding: both ends and why, and the hardware choices in terminating shielded cable at the enclosure. The box's environmental rating lives at the same hole: a manufacturer-rated NEMA 4X / IP66 enclosure — not UL listed — holds its rating only with glands rated to match it, installed to their instructions. The shield handles EMC; the equipment grounding conductor is sized from the overcurrent device ahead of it using NEC Table 250.122, which gives 10 AWG copper for a 60 A drive breaker, and the two share the PE system without doing each other's job.
What do you write on the enclosure order?
The gland count and sizes, the reactor's footprint plus clearance, and a PE bar with room for every shield landing — sent as a cutout drawing, so the shield bonding is done on paper instead of improvised on site.
- Gland entries: one per motor cable, hole sizes from the gland maker's dimensions, positioned clear of the door frame and backplate hardware; the cutouts and glands guide shows the drawing conventions.
- Space: drive footprint, reactor footprint, 4 in [100 mm] of reactor clearance, wire duct, and door-side depth; the enclosure selector sizes the box by inside height and width.
- Heat: name the reactor's watts in the heat budget — the 1-3% band from the placement section — so cooling is chosen with it, not after it.
- Bonding: PE bar sized for the EGC per NEC Table 250.122 plus the shield landings; neutrals on an isolated terminal and grounds on the ground bus, the way NEC 250.6 keeps neutral current off the metal.
- Entry style: locking connector versus conduit for the motor cable is its own trade-off, covered in VFD motor cable entry: locking connector or conduit.
Custom enclosures are delivered in 10 business days counted from your approval of the drawing, so the drawing is where the engineering lands.
Decide by run length:
- To about 50 m [164 ft] shielded or 100 m [328 ft] unshielded: leave the output direct, per your manual's table.
- Beyond that to roughly 90 m [300 ft]: a 3% impedance output reactor.
- To about 180 m [600 ft]: a dv/dt filter.
- Longest runs, or older motors with unknown winding insulation: a sine filter.
- Keep the shield bonded at both ends in every case.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Will 80 m of shielded cable without a reactor hurt the drive?
It loads the output stage past the manual's budget. The worked example draws about 110 mA average per core, so 80 m draws about 175 mA, with edge spikes still near 11 A. Most drives trip on overcurrent or ground fault first, and repeated restarts run the transistors hot. Fit the reactor, drop the carrier frequency, or shorten the run.
Can I use unshielded cable to double the allowed length?
Many drives allow about 100 m [328 ft] unshielded, but you trade away the EMC the shield gave you: switching noise couples into nearby signal wiring, and charging current returns through the tray instead. A 3% reactor on the shielded run fixes the limit for about 6 in [150 mm] of backplate. Keep shielded symmetrical cable on washdown and food lines.
Does a bigger drive allow more cable before a reactor?
The table is per drive model. Typical published limits let small drives to about 15 kW run 100 m, and frames above 15 kW reach about 300 m unshielded; the shielded row still sits near half of the unshielded one. Frame size, voltage and carrier frequency all move the number, so use your model's manual.
How much heat does an output reactor add to the enclosure?
It sits in the same sealed box as the drive, so every watt of its losses raises the enclosure temperature alongside the drive's own. Add the reactor's watts to the heat total before choosing between a sealed box and a cooler; the worked example in the placement section budgets it for a 10 hp [7.5 kW] drive.
Does the shield replace the equipment grounding conductor?
No. The shield is the high-frequency return for charging current, not a safety conductor. Your EGC carries the fault duty and both land on the same PE system — in the worked example that conductor is 10 AWG copper behind a 60 A drive breaker. Keep the two jobs separate.