Short answer: keep one 3% reactor stage in front of the drive group on every transformer that feeds several drives. An unchoked six-pulse input draws current at about 86% total harmonic distortion; a 3% impedance reactor pulls that down to roughly 35%. On a 45 kVA transformer, that difference is the line between a 68% harmonic derating and carrying a dozen 2 hp drives with margin. The same reactors limit the charging inrush into each DC bus and blunt the line transients that pass machine to machine on one supply. Ten to fifteen small drives sharing one secondary winding is exactly the load reactors were made for.
What the rectifier does to a shared supply
A drive front end is a six-pulse rectifier feeding a capacitor bank. It draws current in a narrow pulse at the crest of each half cycle instead of a sine wave, so the supply sees the fundamental plus 5th, 7th, 11th and 13th harmonics. With no inductance ahead of the rectifier, distortion routinely reaches 85-100% of the fundamental; reactor application guides put the same front end at roughly 35% behind 3% impedance.
Two consequences land on the transformer. The RMS current runs about 30% above the fundamental alone, because harmonics add in quadrature, so your amp math undershoots the copper heating. Worse, eddy-current losses in the windings climb with the square of the harmonic order, so the 5th and 7th burn far beyond their share of current. A standard dry-type runs 5-6% impedance; K-rated harmonic units can go as low as 2-3%, which filters even less. IEEE 519 sets how much distortion your installation may put on the point of common coupling, and a dozen unchoked drives on one dedicated transformer is the case it exists for.
What fails first when the reactors come out
The damage shows up in four places, roughly in this order:
| What suffers | Mechanism without a reactor | What you see |
|---|---|---|
| Supply transformer | Harmonic-loss factor near 17 on a six-pulse group; eddy losses climb with the square of harmonic order | Hot enclosure at three-quarters load; winding insulation life roughly halves for every 10 C sustained |
| Drive input stage | Nothing limits the charging peak at power-up or the incoming transients | Blown input fuses at energize, occasional rectifier failures |
| Other electronics | Flat-topped voltage and conducted noise ride the shared bus | Wandering analog readings, nuisance trips, comms and encoder errors |
| Power-factor capacitors | Drive harmonics can resonate with the bank on the same secondary | Failed capacitor fuses, swollen cans, voltage swelling |
Two measurements settle the argument on any existing job: current THD at the transformer secondary with every drive running, and the winding or enclosure temperature at the same condition. Take the same readings with the drives off and you have your before-and-after. For the conducted-EMI side of drive noise, the AC line reactor versus RFI filter comparison covers which device does what. Where capacitor banks share the transformer, capacitor bank reactors for surge limiting versus detuning explains the resonance in depth.
Three percent or five: the impedance to order
Order 3% unless a measurement tells you otherwise. Drive application guides call 3% impedance, sized on the drive kVA, adequate to reduce line transients for most cases, and it is the default on small drives. The 5% winding gives better harmonic control and better surge resistance, and you pay for it in loss and in voltage drop. At 460 V and full load, 3% impedance costs about 14 V and 5% costs about 23 V; on a drive already near its undervoltage trip, 23 V is a real risk.
Two situations justify 5%. A K-rated supply transformer at 2-3% impedance gives you less natural filtering than a standard 5-6% unit, and a measured full-load THD still above about 35% with 3% installed says the drives need more impedance. Before ordering anything, open the drive manual: many drives ship with a DC choke, which smooths the same pulses inside the unit. The DC choke versus AC line reactor comparison walks that trade, and the split between the two sides of the drive is the line reactor or load reactor question.
One shared reactor or one per drive
Both arrangements work; the trade is where the iron sits. A shared reactor sized on the group, about 33 kVA at 41 A for a dozen 2 hp drives, bolts into the main cabinet ahead of the drive distribution and takes one footprint. At partial load the effective impedance rises above the nameplate 3%, so a lightly running group filters even better. Per-drive reactors travel with each drive: a swap on the floor stays local, and every rectifier keeps its own transient buffer. For a single small drive the question changes shape entirely; line reactors for small drives on long motor cables covers that case.
The rule by layout: drives in one enclosure on one transformer take one shared 3% unit at the input terminals. Drives scattered across panels take a reactor at each panel input, so every cabinet keeps its own buffer between rectifier and line.
Sizing reactors for 12 two-horsepower drives on a 45 kVA transformer
Inputs, each with its basis:
- 12 drives, 2 hp, 460 V, about 3.4 A input each at full load, the standard full-load figure for that motor; group current 12 x 3.4 = 40.8, call it 41 A.
- One 45 kVA transformer, 480 V secondary, standard 5-6% impedance; full-load current 45,000 / (1.732 x 480) = 54 A.
- Six-pulse harmonic content, typical of drive application guides: 5th, 7th, 11th and 13th at 70, 45, 20 and 10% of the fundamental with nothing ahead of the rectifier, and at 30, 15, 8 and 5% behind a 3% reactor.
- Eddy-current losses at 8% of load losses, a typical dry-type share; use your transformer's datasheet value when you have it.
- Method from IEEE C57.110: harmonic loss factor F_HL = sum of (h squared x I_h squared) divided by sum of (I_h squared), then allowable current = 54 A x sqrt((1 + 0.08) / (1 + F_HL x 0.08)).
In words, the factor scores a spectrum for transformer heating against pure sine heating, and the square root turns it into the share of rated current the unit may still carry.
Without reactors:
- Sum of I_h squared = 1 + 0.49 + 0.2025 + 0.04 + 0.01 = 1.74, so THD = sqrt(1.74 - 1) = 0.86, or 86%.
- Sum of h squared x I_h squared = 1 + 25 x 0.49 + 49 x 0.2025 + 121 x 0.04 + 169 x 0.01 = 1 + 12.25 + 9.92 + 4.84 + 1.69 = 29.7.
- F_HL = 29.7 / 1.74 = 17.1.
- Allowable current = 54 x sqrt(1.08 / (1 + 17.1 x 0.08)) = 54 x sqrt(0.456) = 36.5 A.
With 3% reactors:
- Sum of I_h squared = 1 + 0.09 + 0.0225 + 0.0064 + 0.0025 = 1.12, so THD = 35%.
- Sum of h squared x I_h squared = 1 + 2.25 + 1.10 + 0.77 + 0.42 = 5.55.
- F_HL = 5.55 / 1.12 = 4.95.
- Allowable current = 54 x sqrt(1.08 / (1 + 4.95 x 0.08)) = 54 x sqrt(0.774) = 47.5 A.
The drives draw 41 A. Without reactors the transformer may carry 36.5 A on this spectrum, so you sit 4.5 A, about 12%, past its harmonic limit while only 76% loaded by nameplate. With the reactors the limit is 47.5 A and the group fits with 6.5 A of margin. Keep them: order twelve 3% reactors in a 4 A class, or one shared unit at 41 A, group kVA = 1.732 x 460 x 41 = 32.7, so a 33 kVA class.
Dropping them instead means bigger iron. An F_HL of 17 calls for a K-20 rated transformer, or a standard unit large enough that 0.68 x full-load current covers 41 A, which needs about 60 A and lands you on 75 kVA (90 A). Twelve small reactors against a transformer swap is the whole cost argument.
The threshold this example generalizes to: with these spectra and 8% eddy losses, an unchoked six-pulse group above about two-thirds of a standard transformer's full-load current exceeds its harmonic limit. Below one-third you would skate by, and that is the honest window for leaving reactors out. It closes the day someone adds drives.
Fitting the reactors and their heat into the enclosure
Reactors change three things in the cabinet: weight, heat and wiring. A 3 A reactor dissipates about 10-20 W, so twelve of them add 120-240 W. Each 2 hp drive rejects roughly 40 W at 97-98% efficiency, so the whole group with reactors puts 600-700 W into the box. That figure goes straight into the enclosure heat calculation, and in a sealed box it becomes the small-enclosure heat removal problem. A washdown cabinet rated NEMA 4X / IP66 by the manufacturer and not UL listed holds that heat in with the drives, so choose the cooling before the backplate fills.
Mount the reactors low on the backplate near the input terminals, and run their wiring with the power conductors, never beside analog or communications cables. Twelve reactors plus duct plus drives stretches a layout sized for drives alone; the backplate and DIN rail layout guide and drive enclosure sizing from heat and clearance keep the spacing honest. If the iron pushes you one size up, the enclosure selector or a custom build to your cutout list is the next step.
What to put on the order
- Reactor impedance: 3% as the default; 5% when the supply transformer is a K-rated unit at 2-3% impedance, or when measured THD stays above about 35% at full load.
- Rating basis: drive input current per drive, a 4 A class for a 2 hp unit at 460 V, or group kVA for a shared reactor, 33 kVA at 41 A in the worked example.
- Enclosure: backplate area and depth for the reactors and their wiring bends, plus the combined heat of drives and reactors in the fan or air-conditioner choice.
- Commissioning measurement: current THD at the transformer secondary with every drive loaded. Expect about 35% with the reactors in, and chase anything back up in the 80s.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can one line reactor feed several drives together?
Yes, and on one shared transformer it is the cheaper shape. Size it on the group: 12 drives at 3.4 A each are about 41 A, so one 33 kVA, 3% reactor covers them. At partial load the group's effective impedance rises above the nameplate 3%, so light running filters even better. You give up local isolation for swaps and diagnostics, and the reactor must live in the main cabinet.
Will a line reactor protect the drive from a lightning strike?
It tames switching transients, line notching and the everyday surges a shared bus serves up: 3% impedance is what drive application guides call adequate for most cases. A direct or nearby strike is surge-protector work. Fit a listed surge protective device upstream of the drives and let the reactor handle the events that happen weekly.
Does an input reactor protect long motor cables?
No. Reflected-wave voltage on the motor cable is a load-side effect, and the input reactor sits ahead of the rectifier and never sees it. Motor lead length limits, dv/dt filters and output reactors are decided at the drive output. The line-side unit does nothing for a long motor run, so budget those separately.
Is a DC bus choke a substitute for the input reactor?
For harmonics and charging inrush, largely yes: a choke between the rectifier and the bus capacitors smooths the same pulses, which is why several drive makers build one in. It does nothing for transients arriving on the line ahead of the rectifier, and it stays with that one drive. If your drives ship with a DC choke, the case for adding a line reactor shrinks to surge buffering and shared-bus noise.
How much heat do 3% reactors add to the enclosure?
Roughly 1% of through power. Small 3 A units dissipate about 10-20 W each, so a dozen add 120-240 W inside the panel. Add the drives' own losses, around 40 W per 2 hp unit, and a dozen-drive cabinet lands near 700 W. That belongs in the enclosure heat calculation before you choose fans or an air conditioner.