Shielded analog cable to a PLC input: ground it right

Bond the analog signal cable shield to the panel earth bar at the enclosure entry, drain tail under 50 mm, and keep the bare jumper from terminal block to analog input under 300 mm. A floating shield lets one switching transient push a 4-20 mA input about 0.7 V past full scale — 117% on a transmitter that spans 0-100% RH — and the pump stop is correct logic on a corrupt signal.

NEMA4 Enclosure engineering team · Published November 25, 2026 · 7 min read

Short answer: land the shield on the panel earth bar at the cable entry, keep the bare drain tail under 50 mm [2 in], and hold the unscreened jumper from terminal block to analog input under 300 mm [12 in]. A shield cut and taped at both ends leaves the pair acting as a receiving antenna. One contactor drop-out nearby then pushes a 4-20 mA input about 0.7 V past full scale — a reading near 117% on a transmitter that spans 0-100% RH. When the pump stops at a 90% RH setpoint, the stop is correct logic acting on a corrupt input. So before you touch the program, touch the terminations: the fix is one bond, one crimp and one duct re-route.

What the symptoms point to

A value the transmitter cannot produce is an electrical event, not a process event. Each symptom below narrows the search for you:

  • A one-off reading above the span. A 0-100% RH transmitter has no 117% to give; anything past span is instrumentation noise, full stop.
  • One display catches it, the others miss it. The transmitter's own display and the historian hold 82% while the panel flashes the spike. Each device samples at its own instant, and a disturbance shorter than one PLC scan (small PLCs scan in 1-10 ms) is gone before a slower screen refreshes.
  • A smooth climb, then a step. The reading walks 80, 81, 82% and then jumps 30 points in one refresh. Humidity moves through a cooling coil over seconds; a one-refresh jump is a wire event.
  • The stop itself is correct. A 90% RH trip that halts the pump did what the logic asked; the corruption arrived upstream at the input terminals.
  • The event tracks a large load. If the spike lands when a compressor, contactor or drive starts nearby, the source is electromagnetic, not humidity.

Two or more of these together put a missing shield bond at the top of your list.

Why a reading lands past full scale

The worked example needs its assumptions on the table. A humidity transmitter spans 0-100% RH with a 4-20 mA output, on a 24 V DC loop. The analog input uses the classic 250 Ω sense resistor that turns 4-20 mA into 1-5 V. Substitute your module's actual input resistance; the arithmetic holds the same way.

  • Full scale: 20 mA × 250 Ω = 5.0 V at the input.
  • A display of 117% means the channel saw: 4 mA + (1.17 × 16 mA) = 22.7 mA.
  • 22.7 mA × 250 Ω = 5.7 V, which sits 0.7 V above the full-scale point.
  • 0.7 V across 250 Ω is 2.7 mA of coupled noise, about 17% of the 16 mA span.

Less than a volt at the terminals is enough to fake a trip. The signal itself needs almost no bandwidth: a humidity loop carries information below a few hertz. The interference is a different story. A coil drop-out with a 10 ns edge carries energy to roughly 35 MHz, by the standard 0.35 ÷ rise-time estimate. Shielding practice bonds a shield at one end for circuits below about 1 kHz, and at both ends above roughly 100 kHz. A transmitter loop sits far below that boundary, so one point at the panel is the answer. The same boundary decides one-end bonding for a VFD control cable shield. Motor cables are the exception, because they are a power circuit: bond them at both ends at the enclosure entry.

The bare tail decides how well that single bond works at the frequencies that matter. The EMC handbook estimate gives a straight wire about 1 nH of inductance per millimetre. A 300 mm tail is therefore 300 nH, and 2π × 35 MHz × 300 nH = 66 Ω at the transient's knee. Cut the tail to 50 mm and the same formula gives 11 Ω. At the signal's own 10 Hz, the long tail is microhms. That is why the loop reads clean all day and fails only inside the microsecond of a switching edge.

The causes, most likely first

Finding at the terminations Most likely cause Deciding check
Drain cut and taped at both ends Floating shield Ohm from shield to earth bar: open circuit
Bonded only at the transmitter end Whole panel run unscreened Follow the pair from entry to strip
Twisted under a signal terminal screw Bond open at high frequency Measure the bare tail at the bar
Long bare hop, or shared with a power duct Re-entry coupling at the module Lay the pair flat on the plate, clear of power
Steady high reading that never clears Channel or sense resistor fault Compare raw input and channel status

The first row is the classic finding on a loop that ran clean for months. The cable was always shielded, the shield never had a path to earth, and a new noise source arrived on site. The last row reads differently: a hardware fault holds the input high, it does not flash once and vanish. Work down the first four rows before you blame the module.

How to check each one

Isolate the loop and verify absence of voltage before you open any termination. Then work down the table:

  • Read both ends. At the transmitter and at the panel strip, look for the drain. Cut and taped means floating; landed under a signal screw means the bond exists on paper only.
  • Ohm the bond. From the shield at the entry to the earth bar stud, a healthy bond reads under 1 Ω including test leads. An open circuit is the fault, found.
  • Watch a floating shield. With the far end lifted, meter from shield to earth. A floating shield shows several volts of wandering AC that moves as your hand approaches the jacket; a bonded shield sits at millivolts.
  • Follow the last run. Trace the pair from strip to module. A long bare hop, or one that shares a duct with power wiring, couples a switching edge on its own.
  • Test the jacket. With both ends lifted and electronics disconnected, 500 V DC from shield to cores reads hundreds of megohms on healthy cable. A reading in kilohms means water or abrasion in the jacket.
  • Check the run length. A transmitter several hundred metres out adds its own design limits; the long transmitter cable run article lists them.

The fix: one bond, at the entry, on the bar

  1. Crimp the drain into an earth ring terminal and land it on the panel earth bar nearest the cable entry, with the bare tail under 50 mm [2 in].
  2. Bond to the earth bar, never to a signal terminal; the single-point scheme is laid out in the grounding and bonding guide.
  3. Give several shields a bar, not one stud — the earth bar or stud article sizes that choice.
  4. Keep the shield bar and the power earth bus as separate bars of one system, each bonded to the enclosure; the panel earth and shield earth article shows the arrangement.
  5. Shorten the bare hop: put the analog module within 300 mm of the field strip where the layout allows, run the pair flat on the mounting plate, and cross any power bundle at 90 degrees.
  6. Power up and log the raw input at the fastest interval the software offers for a full day of normal cycling. Every sample inside the configured range, with no step at a machine start, is the proof you are done.

A steel entry plate takes a shield clamp around the jacket at the gland cutout, which does the same job with no tail at all. The cutouts, glands and HMI windows guide covers specifying that entry.

If the reading turns from spikes into slow drift after you bond the shield, a loop is now circulating between two earth points. That separate fault has its own walkthrough in the PT100 shield article.

Keeping it fixed

  • Walk every shielded field cable in the panel and land it the same way. The cable that caused the first trip is rarely the only one with taped drains.
  • Hold 100 mm or more between signal and power bundles across the backplate, the EMC layout rule of thumb, and cross at right angles where paths must meet. The backplate and DIN rail layout guide carries the spacing rules for ducts and rail.
  • Add one line to the commissioning sheet: every shield reads under 1 Ω to the bar, and the reading is recorded with the date.

When the enclosure is the problem

Sometimes the box makes the fix hard to hold. A painted steel cabinet in a wet plant sweats on the lid, a plastic push-in gland gives the drain nothing clean to land on, and a full earth bar invites the next taped drain. Re-specify the enclosure when the entry has no bonding surface, the bar is out of space, or the panel faces washdown or salt air. Stainless NEMA 4X wall-mount enclosures in 304 suit indoor washdown and food areas; 316L suits salt, brine and chemical air. Ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed. We cut the gland plate at the entry positions on your drawing when you order custom stainless enclosures, and the 3D enclosure builder places gland and E-stop cutouts before anything is quoted. Custom work is delivered in 10 business days, counted from your approval of the drawing.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
6 × 6 × 4 in304 stainless6 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
8 × 6 × 4 in304 stainless8 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
10 × 8 × 4 in304 stainless10 x 8 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Should a 4-20 mA signal cable shield be grounded at one end or both ends?

At one end, on the panel earth bar at the enclosure entry. The signal carries information below a few hertz, and shielding practice bonds at one end for circuits below about 1 kHz; both-end bonding is reserved for fast circuits above roughly 100 kHz, where loop current cannot modulate the signal. Motor cables are the exception, because they are power circuits.

How long can the shield's drain tail be?

Keep the bare tail under 50 mm [2 in] from jacket to earth bar. The EMC estimate gives wire about 1 nH per millimetre, so 50 mm is about 50 nH — roughly 11 Ω at the 35 MHz knee of a switching transient, against 66 Ω for a 300 mm tail. A tail twisted back under a signal terminal behaves like an unbonded shield at those frequencies.

Why did the fault start suddenly after weeks of clean running?

Because the weak point was always there and a new noise source found it. A floating shield and a bare jumper stay harmless until something nearby switches hard: a compressor contactor, a new drive, a failing coil. The wiring did not change that day; the electromagnetic environment did. Fix the bond and the loop stops caring which machine cycles next.

Can the shield stop at the terminal strip instead of running to the module?

The shield can stop at the strip only when the bare hop to the module stays short and clear of power wiring. Build to 300 mm or less, lying flat on the mounting plate, at least 100 mm from power ducts. For a longer hop, carry the shield through on screened feed-through terminals so the pair is covered the whole way.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start a junction box from 6 × 6 × 4 inRequest a custom quote

Check the heat load in the calculator · Stainless junction boxes: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides