Short answer: bond each shielded signal cable to the panel ground bar at one end, 12 in [300 mm] clear of drive output cable. Unshielded signal cable needs 3 ft [900 mm]. Give the weigh structure a real bond before you buy an isolation transformer. In a plant with drives from 5.5 to 22 kW beside a 140 kW press drive, the drive output cables are the noisiest wiring on the site. An intermittent COM error plus a drifting load cell is the classic signature of that noise finding its way into signal wiring.
Work the list below in order. The first three checks need a screwdriver, an ohmmeter and a tape measure. The isolation transformer sits last, and it earns a place only when your checks land on two panels tied together at different ground potentials.
What each symptom points to
Each symptom narrows the hunt before you open a single gland:
- One COM port errors at random moments. The cable on that port, its connectors and the settings at both endpoints. A baud, parity or station-number mismatch raises the same alarm as noise, so read the configured values at both ends first.
- The load-cell value jumps or drifts while the COM link stays healthy. The measurement path: the load-cell cable's route, its shield bond and the bond at the weigh structure.
- Both faults cluster when the press starts. Noise coupled from the power cables during the 140 kW drive's ramp, plus about 5 minutes of vibration working on terminals and module latches.
- The displayed weight looks plausible but resin or quartz still gets over-dosed. The measurement chain from load cell to input, not the PLC-to-HMI link. A COM alarm does not explain every bad batch.
- The control power supply runs near 60 °C [140 °F]. Interior panel temperature. Most industrial control electronics carry their full rating only to 40 °C [104 °F] ambient, so a supply that hot is derating or cycling.
Write down which device reports each fault and when. A port label narrows the hunt to one cable and two endpoints. Trace the real conductors before you re-terminate anything.
The causes, most likely first
These turn up in this order in a mixed drive-and-weigh panel:
- The shield lands on the power supply negative. A drain wire parked on the 0 V rail carries supply return current and rides the 24 V rail instead of sitting at earth. That one habit produces jumpy analog readings and serial faults together, and it is the first thing to undo. The same mistake on RTD and thermocouple cable gives the same result, and the fix is identical — see why an RTD shield on DC negative spoils the reading.
- Signal cable shares a route with drive output cable. PWM switching on a drive output couples into anything running parallel to it. The cabling guideline published for VFD systems recommends 1 ft [300 mm] between shielded instrumentation cable and drive cable, and 3 ft [900 mm] for unshielded signal cable; a trench shared with a 140 kW output deserves more. Drive makers' wiring application notes ask for the same inside the cabinet: input and output wiring in separate paths. 4-20 mA or RS-485 cable in one trunk or duct with motor cable is the classic setup for faults that come and go.
- The far end has no real bond. Motor frames without their grounding conductor and a weigh structure sitting on insulating load-cell mounts leave metalwork floating wherever the noise pushes it. Grounding ten forgotten motor frames improved this fault once, which points the diagnosis straight at bonding and routing. The equipment grounding conductor carries fault current; the earth itself is not part of that path under NEC 250.4(A)(5).
- The serial link outgrew its interface. RS-232 was drawn up around runs near 50 ft [15 m], set by the 2,500 pF load-capacitance limit at the receiver. The first panel sat 50 m [164 ft] away, 3.3 times that length; the second sits 100 m [328 ft] away, 6.7 times. Cat7 patch cable buys no length here: the category describes the cable, and the interface limit still ends the run.
- Press vibration loosens terminations. Roughly 5 minutes of hard shaking at every start backs terminal screws out and works on crimps and module latches.
- The control compartment runs hot. A supply case at 60 °C sits 20 K past the 40 °C point where derating usually starts, so resets and brownouts join the COM faults.
How to check each one
Lock off and tag the panel supply, and confirm absence of voltage on the power side, before you open gland plates or pull terminations. Each check takes minutes and ends in a verdict:
| Cause | How to check | What the verdict means |
|---|---|---|
| Shield on 0 V | Follow every drain wire from gland to terminal | Any landing on a supply terminal: move it to the ground bar |
| Parallel route | Tape measure on the worst shared section | Gap under the shielded-cable distance: reroute or re-trunk |
| Far-end bond | Ohmmeter from the weigh structure to the panel ground bar | Whole ohms: paint, rust or a missing jumper. A sound bond reads a fraction of an ohm |
| Link length | Measure the port-to-port route | Past 50 ft [15 m] on RS-232: convert the link |
| Vibration | Re-torque ten sample terminals after a press run | Any screw that turns by hand: re-terminate that panel with ferrules |
| Compartment heat | Thermometer inside the panel, 10 min into a press cycle | 60 °C at the supply case: size airflow with the heat calculation |
Is the 0.75 mm² cable the fault?
Take the 100 m [328 ft] load-cell run at 0.75 mm² copper. That size runs about 24 Ω per km at 20 °C, so each excitation conductor adds 2.4 Ω over the run. The two excitation conductors together add 4.8 Ω round trip. A 350 Ω bridge excited at 10 V draws 10 V ÷ 350 Ω = 28.6 mA. The cable drop is 0.0286 A × 4.8 Ω = 0.137 V, which is 1.4 % of the 10 V excitation. Without sense conductors, every reading scales down by that 1.4 %, steadily and silently — a calibration error, not a jump. The signal conductors feed a high-impedance input, so their own drop is microvolts. Copper resistance rises about 0.39 % per K, so a warm ceiling adds a little more of the same steady error. Six-wire load-cell cable with sense lines removes even that. Conductor size gives you a small constant offset; it is not what makes the weight leap when the press starts.
The fixes, in the order that pays
- Move every drain wire to the ground bar, one end only. Instrument shields bond at the panel end and stay insulated at the far end; drive control cable follows the same one-end rule, as the VFD control cable shield guide shows. What lands where the cable meets the box, clamp or pigtail, is set out in the guide to shield termination at enclosure entry. On a long serial link the bond point is its own decision, and the guide to choosing the RS-485 shield bond walks it. Bond the 24 V common to that same bar at one point; a floating 0 V takes its earth through whatever is plugged in, which is the story in the PLC 0 V and USB fault case.
- Separate the routes, outside and inside the panel. Restore the gap from the check table on every shared run, cross unavoidable crossings at right angles, and put instrument cable in its own steel trunk or conduit. Inside the box, land signal entries on one face and power entries on the other, so the two duct runs never sit side by side on the plate.
- Bond the weigh structure and the motor frames. A bonding strap across each load-cell mounting assembly holds the frame at earth while the cell keeps its electrical isolation; the load-cell enclosure guide shows the wiring without upsetting the weigh signal. Return motor frames to the panel on their equipment grounding conductor. A rod driven beside the frame is an auxiliary electrode under NEC 250.54: bond it to that conductor and treat its resistance as a bonus, not the fix.
- Convert the long link. RS-485 carries 1,200 m at 100 kbit/s under the RS-485 standard, so a converter pair or an isolated repeater fixes the length and the ground-domain problem in one move — when an RS-485 node needs isolation explains the ground-domain side. Fiber does the same job optically where the field around the press drive is at its worst. Match the settings at both endpoints, and fit the termination the interface calls for, typically 120 Ω at each bus end.
- Re-terminate for vibration. Fit ferrules on every stranded control conductor, seat the DIN end brackets and module latches, torque the screws to the value printed on the terminal, and dress cables so no connector carries wire weight. Recheck a sample after a week of presses.
- Cool the compartment. Add the heat loads and fit a filter fan or air conditioner sized to hold the interior near the 40 °C rating point; the enclosure heat calculation guide walks the sum. Read the supply's derating curve for its own maximum ambient.
- Buy the isolation transformer last, if at all. It changes the galvanic story of the supply and nothing else: no help for noise coupled along a parallel route, a shield on the 24 V rail, or a missing bond. When the checks do land on two panels at different ground potentials, an isolated repeater or a fiber pair usually solves it in a fraction of the panel space.
Keep it from coming back
- Log COM faults and bad weight readings per shift for two weeks, alongside press starts. A count that falls to zero when the press idles points straight at the coupling path.
- Run one stopped-drive shift against one running-drive shift after the fixes. A clean stopped shift and a noisy running one close the case; identical counts send you back to settings or a failing device.
- Audit terminal torque a month in. Vibration finds the screws the first pass missed.
- Label the signal trunk instrument only, and keep every future cable on the separated route.
- Look at the drain wires after any panel work. Shields get lifted for a test and forgotten more often than any other bond.
When to re-specify the enclosure
Sometimes the box itself is on the list. Order the panel the room needs:
- Depth for separation. A deeper box lets signal duct and power duct stay apart on the plate instead of crossing at the terminals.
- Two entry fields. Instrument glands on one face, power glands on the other, so the clean routing starts at the wall.
- A real ground bar. Every shield and every earth wire lands on studs; whether the back panel alone is enough ground in one enclosure is its own question.
- A rating for the room. Quartz dust and dripping condensate call for a box rated NEMA 12 by the manufacturer; not UL listed. Where the room gets hosed down or the solvents attack paint, stainless is the answer, and the 304-versus-316L comparison picks the grade.
- Cutouts on the drawing. Extra gland holes for the two entry fields are drawing lines on a custom box, not field rework; send the layout with the cutout drawing checklist or start from the guide to cutouts, glands and HMI windows.
We build these to your drawing — material, width, height, depth, every cutout, from one piece — and deliver in 10 business days from your approval of the drawing (custom enclosures). Swap the PLC brand after the wiring is right, not before. Every fault above shows up on premium hardware when the cables run wrong.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does an isolation transformer fix intermittent PLC COM errors?
Rarely, and only one case earns it: two panels at different ground potentials tied together by a serial cable. For noise coupled along a parallel route, a shield on the 24 V rail or a missing bond at the weigh frame, it does nothing. Fix routing and bonds first. When the checks do land on a ground-domain problem, an isolated repeater or a fiber link usually solves it in less panel space than a transformer sized for the panel supply.
How much separation does signal cable need from drive cables?
Hold shielded instrumentation cable at least 12 in [300 mm] from drive output cable, and 3 ft [900 mm] for unshielded signal cable; those are the figures the published cabling guideline for VFD systems recommends. Cross routes at right angles when they must meet, and keep 4-20 mA or RS-485 cable in its own steel trunk rather than sharing a run with motor cable. In a trench shared with a 140 kW output, treat those distances as floors, not targets.
Can a cable shield bond to the 24 V supply negative instead of ground?
It can, and that connection is a prime suspect when load cells jump: on the negative rail the shield carries supply return current and follows the rail instead of sitting at earth. Move each drain wire to the panel ground bar, bond at one end only, then watch one full shift of press cycles. A steady trend confirms the bond did the work, before anyone orders a new earth rod.
How long can an RS-232 run between two PLC panels be?
The RS-232 standard was drawn up around 50 ft [15 m] runs at 20 kbit/s, limited by a 2,500 pF load capacitance at the receiver. A 100 m [328 ft] link sits 6.7 times past that, so intermittent errors at that length are expected behavior, not bad luck. Convert the link to RS-485, specified for 1,200 m at 100 kbit/s, or fit an isolated repeater or a fiber pair, then match the settings at both ends.





