Short answer: land every sensor cable shield on the earthed cabinet chassis, or on an instrument-ground bar bonded to it, and keep the 24 V negative out of the shield business. An isolated supply negative reaches earth through about 1 nF of isolation capacitance, roughly 3.2 MΩ at 50 Hz, so a shield landed there drains almost nothing. Referencing the negative to earth is a separate decision you make with a ground-disconnect terminal. The capacitances below are typical values for an industrial supply and a 20 m tray run; your datasheet's isolation figure shifts the volts, never the decision, because megohms against a bolted bond under 0.1 Ω is seven orders of magnitude.
Does the cable shield go to earth or to the power supply negative?
Earth. The shield and its drain wire land on the cabinet chassis or on an instrument-ground bar bonded to it; a floating supply negative, sitting megohms from the chassis through its isolation capacitance, is no landing point at all.
A shield intercepts the electric field before it reaches the pair and gives the intercepted current somewhere to go; the landing point is the whole decision. Interference collected on the braid leaves through a low-impedance joint, or it shows up as common-mode voltage across the conductors you were protecting.
| Where the shield lands | What it buys | Decision |
|---|---|---|
| Chassis or PE bar, bolted | Under 0.1 Ω into the equipment grounding system | Default for every analog cable |
| Instrument-ground bar bonded to the chassis | The same earth, with terminals sized for drain wires | Same thing, tidier on a full backplate |
| Isolated 0 V rail | Megohms to earth through ~1 nF of stray capacitance | Keeps the noise it collected |
| 0 V rail earthed at one point | Shield current rides the conductor carrying your returns | Earth side, same as above |
The grounding system behind the first two rows is its own subject. The enclosure grounding and bonding guide covers the PE conductor, the bars, and bonding the door and backplate. The topology — one earth system, separate bars for panel earth and instrument earth — is in panel earth and shield earth on separate bars.
Why does an isolated DC negative drain almost nothing?
Because the only route from a floating negative to earth is capacitive, and the isolation capacitance leaves it megohms away, while a bolted chassis bond measures under 0.1 Ω — a factor of about 30 million.
An isolated 24 V output has no metal path to earth. It has the stray capacitance across the isolation barrier, commonly near 1 nF and printed in the datasheet as isolation capacitance or leakage current. Put numbers on a cabinet whose sensor cable runs 20 m in the same tray as a 230 V, 50 Hz circuit, coupling through about 30 pF:
X = 1 / (2π × 50 Hz × 1 nF) ≈ 3.2 MΩ
| Step | Arithmetic | Result |
|---|---|---|
| Ride-up of the floating 24 V system | 230 V × 30 / (30 + 1000) | ≈ 6.7 V |
| What the loop measures | 4-20 mA across a 250 Ω input | 1-5 V, a 4 V span |
| Current that coupling can supply | 2π × 50 × 30 pF × 230 V | ≈ 2 µA |
| Same coupling, shield on the chassis | 2 µA through 0.1 Ω | ≈ 0.2 µV |
The ride-up is bigger than the whole measurement span, and it sits across the input module's signal-to-earth common-mode limit until something bonds it. Land the shield on the chassis and the same interference ends as 0.2 µV across the bond. Faster interference is worse for the floating rail: at 100 kHz the same 1 nF is 1.6 kΩ, still about 16,000 times a bolted bond. The RTD-specific version of this — a drain landed on DC negative instead of the instrument bar — is walked through in RTD cable shield on DC negative; the physics is identical for the 24 V and 0-10 V cables in the same bundle.
Does the answer change if the supply negative is already earthed?
Only in that the temptation grows: once 0 V sits at earth potential, landing a shield on it looks harmless, but the shield current then shares the conductor carrying your signal returns, so the shields still go to the earth bar.
The negative is a working conductor: every sensor returns its current on it, and the analog commons tie to it. The earth bar carries no return current and is built for exactly that. NEC 250.6 makes the same separation on the AC side of the panel — it keeps neutral current off metal parts by landing neutrals on an isolated terminal and grounds on the bus — and the logic transfers straight across to your DC system.
Supplies ship with floating outputs so you can series two 12 V units for ±12 V or stack them for other rails, which is why referencing is your call, made once, at one point. When a second supply or a mixed system joins the panel, bonding 0 V to earth with mixed supplies sorts the reference points without creating loops.
Should you ground the shield at both cable ends?
For 4-20 mA and 0-10 V field wiring, no: bond at the cabinet end and insulate the drain at the sensor, because any voltage between the two earth points drives a circulating current straight down the shield.
Between the panel's earth bar and a machine frame 50 m away, a 1 V difference is ordinary. A 100 m braid loop of about 2 Ω turns that into 0.5 A circulating in the shield, whose field couples into the pair inside. Some transmitters bond the drain to their case internally, and an EMC gland clamps the braid if one is fitted; a continuity check from drain to the transmitter's mounting thread before power-up tells you which you have. When the far end is already bonded, insulate the cabinet end and let that bond be the single one — one bond total, at whichever end has it.
Cables carrying drive output or fast digital traffic live under a different regime; VFD control cable shield practice covers their one-end rule, and the EMC glands that terminate a 360° screen start in the cutouts and glands guide. For thermocouple and RTD extensions, the end choice has its own answer in thermocouple and RTD shield grounding: sensor end or cabinet.
Is it safe to leave the 24 V supply floating?
Yes, it runs fine, and suppliers leave the output floating so you can series two 12 V units; but an unreferenced system rides at whatever stray capacitance decides — 6.7 V in the example above — so make the bond a decision, not an accident.
The clean way to decide is a ground-disconnect terminal: a terminal with a removable metal link between the 0 V rail and the earth bar. Link closed, your 24 V system has a defined reference; link lifted, you can measure insulation or chase leakage without unwiring anything. Either position, the shields stay on the earth side. The full when-and-how — which supplies to reference, where, and what to do about multiple secondaries — is in grounding the 0 V of a 24 V supply.
One point of vocabulary decides where your bond lands: "earth" in a cabinet means the PE conductor and bonded metal back to the source. NEC 250.4(A)(5) is explicit that the earth itself forms no part of the effective ground-fault current path, so the chassis bond and the PE conductor are the path. Whether a 0.5 Ω earth stops 50 Hz instrument noise is a separate question, answered in does a 0.5 Ω earth stop 50 Hz instrument noise.
How do you land the shields inside the cabinet?
On shield terminals on an instrument-ground bar bolted to the backplate with the paint scraped at the contact points — NEC 250.12 requires paint, lacquer and enamel removed at grounding and bonding connections, and a coated surface is where milliohms become ohms.
- Mount the instrument-ground bar and the PE bar with contact points bare to the metal, and bond each to the chassis with its own stranded jumper — green, or green with a yellow stripe, for insulated conductors of 6 AWG and smaller (NEC 250.119).
- Bond the door to the bar with a dedicated jumper rather than through the hinges — the same argument as tank grounding with a dedicated bond, not anchor bolts: incidental metal contact is not a bond.
- Land each drain wire under a shield terminal or clamp on the instrument bar, trim the braid back, and tape or heat-shrink the far end you are insulating.
- Keep 0 V returns on their own terminal group; shield landings and return landings never share a terminal.
- Route the shielded pairs away from the 230 V tray and any drive output, and hold duct fill to 50 % of the cross-section, the figure one wiring-duct maker's fill tables set, citing NFPA 79-2012 13.5.2.
- Size the PE conductor from the overcurrent device ahead of it per NEC Table 250.122: 10 AWG copper for a 60 A feed, 8 AWG for 100 A.
A stainless cabinet is a good earth reference for all of this. Our wall-mount boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and the 304-versus-316L choice is about corrosion, never about grounding. Backplate and DIN rail layout places the bars, duct and rails so the shield runs stay short.
What proves the shield termination at commissioning?
Three measurements: under 0.1 Ω from each drain wire to bare chassis, an open circuit from drain to earth at the sensor end with the sensor disconnected, and a 4-20 mA reading that holds within ±0.05 mA when an interference source nearby switches on.
Before any of it, lock out the supply and prove the field wiring dead; the analog side is 24 V, and the circuit next to it in the tray is not. Then work through the list:
- Measure drain-to-chassis at each shield terminal with a low-resistance ohmmeter; anything above 0.1 Ω points at paint or a loose clamp under the bar.
- Lift the sensor end and read drain-to-earth there: megohms is the single-bond proof. A reading near zero means the far end bonds internally, so move your insulation to the cabinet end.
- Run the loop and switch a contactor coil or a hand drill beside the cable; holding within ±0.05 mA of a 20 mA span, a quarter of a percent, is a practical target for a clean installation.
If the reading shifts when you touch or move the shield, a second bond exists somewhere in the run; RTD reading changes when you move the shield walks the hunt for it.
What goes on the enclosure order?
Two ground bars on the backplate — one PE, one instrument ground, both bonded to the chassis — plus a gland plate drilled for every shielded cable, on a stainless box delivered in 10 business days from your approval of the drawing.
- Material: 304 stainless for indoor and general outdoor duty, 316L where washdown chemicals and chlorides reach the box — the NEMA 4X stainless range carries both.
- Backplate: mounting holes for both bars, the door-bond jumper point, and space for the shield terminals near the gland side.
- Gland plate: one hole per cable, sized to the gland, planned so the drain reaches its terminal without crossing the power section; the cutouts and glands guide sets the dimensions.
- Size: from the module count, the duct allowance and the working room at the door; the enclosure selector shortlists by inside height, width and DIN module count, and carries the rest to a custom quote.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 316L stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 316L stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What is a ground-disconnect terminal for?
It bonds the 0 V rail to the earth bar through a removable metal link. Closed, the rail carries a defined earth reference; lifted, insulation tests and leakage hunts happen without unwiring anything. Shields stay on the earth side of the link, so lifting it never floats your shield terminations.
How much resistance should there be from a shield drain to the chassis?
Under 0.1 Ω at the bond, measured with a low-resistance ohmmeter from the drain wire to bare chassis metal. A bolted joint on paint-free steel sits in milliohms; paint or an anodized surface under the bar is what pushes it up, which is why the contact points are scraped to bare metal before the bar goes on.
Will earthing the 0 V rail stop the noise on its own?
It fixes the reference, and it is worth doing through a ground-disconnect terminal, but the shields still land on the earth bar. In the worked example the floating system rode at 6.7 V; with a 0.1 Ω bond the same coupling develops about 0.2 µV. Referencing the rail and draining the shields are two different jobs.
Does a 0-10 V signal need different shield treatment than 4-20 mA?
Same landing point, lower tolerance for leakage. A 4-20 mA loop reads through a 250 Ω burden, 1 to 5 V, and shrugs off small series drops. A 0-10 V input typically reads through 100 kΩ or more, roughly 400 times the impedance, so the same induced current becomes a voltage error hundreds of times larger.





