Short answer: order an ungrounded-junction probe whenever the input card asks for galvanically isolated sensors. The junction is welded first, then insulated from the sheath with mineral powder, and the probe datasheet states that isolation as 1 MΩ or more tip-to-sheath, commonly at a 500 V DC test level. A grounded probe welds the junction straight to the sheath, and that sheath usually threads into machine steel — faster to respond, and the wrong construction for any channel that shares its reference with another. You get the construction table, the error arithmetic, the bench check that proves the isolation, and the panel wiring that keeps it.
What is the difference between a grounded and ungrounded thermocouple?
The difference is one weld: a grounded probe bonds its measuring junction to the sheath tip, so the junction sits at machine potential, while an ungrounded probe holds 1 MΩ or more of insulation between junction and sheath.
Probe makers ship the grounded junction as their most common style, so an order without the word "ungrounded" arrives grounded. The sheath then threads into a thermowell or clamps to machine steel, and your microvolt circuit is tied to the structure. A metal sheath can carry an insulated junction, and an insulated cable jacket tells you nothing about the tip, so the order code decides, not the look of the probe.
| Construction | Junction to sheath | Response | Where it belongs |
|---|---|---|---|
| Grounded | welded, a few ohms | fastest sealed tip | isolated channels, fast loops |
| Ungrounded | insulated, 1 MΩ or more | about twice the time constant | isolated cards, shared-reference cards |
| Exposed | bare, in the medium | fastest of the three | clean dry gas, isolated channel |
Which junction does an isolated thermocouple input card need?
An ungrounded one, on every channel: cards whose channels share a reference — the two-channel modules whose manuals say "use galvanically isolated sensors" — reject grounded probes, and some datasheets list them as unsupported.
One two-channel card puts it in a single line: "Use galvanically isolated sensors to avoid falsified measured values." Cards built with per-channel isolation between channel and system read either construction happily. Read the card's spec the way you read the probe's: one shared common between two channels means both probes are ungrounded, because either grounded tip ties that common to its machine frame. For a card-by-card treatment, the grounded vs ungrounded thermocouple selection for Allen-Bradley I/O page works through the same decision on named I/O. When a grounded probe is already in the machine, a DIN-rail signal conditioner between probe and card isolates the loop electrically, one module per channel on 35 mm rail.
When is a grounded thermocouple the better probe to order?
When response time leads the spec and the channel is isolated: the welded tip settles in roughly half the time of an insulated tip of the same diameter, because heat skips the mineral powder.
Use the grounded junction when the card gives each channel its own isolation, when the probe feeds a controller that floats with the machine — stem-mounted indicators work that way — and when a fast loop needs every tenth of a second. Two things move the tradeoff back toward ungrounded. A smaller sheath recovers speed: a 1/8 in [3 mm] ungrounded tip runs close to a 1/4 in [6 mm] grounded one. A thermowell dominates the lag budget instead: a 1 in [25 mm] stainless well often adds more lag than the junction choice saves. For loops with seconds of process lag, order ungrounded and spend your attention elsewhere.
How much can a grounded junction shift your reading?
About 49 °C on Type K from a 2 mV frame-to-panel difference: the Type K table slopes near 41 µV per °C, and 2 mV divided by 41 µV/°C gives 48.8 °C.
Two millivolts is an ordinary field number with a drive in the building, and it lands in series with your signal. The symptoms read three ways: the value wanders with drive load, it jumps when other equipment switches, or it sits repeatable but biased by tens of degrees. If the number changes when you touch the shield, find the bad bond; if the box itself is the antenna, noisy thermocouple on a metal enclosure covers that path.
How do you prove a probe is ungrounded before it goes in the box?
Lift both legs off the terminal block and read pin to sheath with your meter: open (OL) on a 10 MΩ instrument means ungrounded; a few ohms — commonly 3 to 30 Ω of lead and junction on panel-length runs — means grounded.
- Pull the probe out of service and lift both thermocouple legs at the terminal block or the card.
- Measure from either pin to the sheath, or to the thermowell if the two are bonded: OL is an ungrounded tip.
- Confirm to datasheet level with an insulation tester at the datasheet's test voltage, 1 MΩ or more tip to sheath; ASTM E780 is the room-temperature test method for sheathed thermocouples.
- Apply the insulation test to the bare probe only, never through extension cable or a connected input card.
- Write the result beside the probe's order code on the loop sheet, so the next outage starts from fact.
Where do the shield and the earth land in the panel?
Bond the shield at one end only — the panel end, on a shield bar that sits beside but apart from the PE bar — and let the probe's insulation be the boundary at the machine.
Panel earth and shield earth form one grounding system on two bars; the shield lands on its own. Terminate it at the entry with an EMC gland or a 360° clamp, as cable shield termination at the enclosure entry shows, and keep the gland in metal-to-metal contact with the box. On painted steel, remove paint at the contact surfaces first: NEC 250.12 asks exactly that for grounding and bonding connections, and the enclosure grounding and bonding guide covers the bar layout in full. With an ungrounded probe you pick the shield's bonded end by system convention; the sensor-end or panel-end decision sets out when each wins. Between machine and panel, land the extension runs in a stainless junction box — 316L at the washdown end, rated NEMA 4X / IP66 by the manufacturer and not UL listed — with one DIN row for the blocks; instrument junction box selection sizes that box for your channel count.
What goes on the order for an ungrounded thermocouple loop?
Six lines cover it: the probe with its isolation spec, the card's isolation, the field box, the shield landing, the extension cable and the spares — the table below is the spec you send.
| Line | What to write | Example for a drive-fed machine |
|---|---|---|
| Probe | Type K, ungrounded, 1 MΩ min tip to sheath | 1/4 in [6 mm] sheath, thermowell to suit |
| Input card | per-channel isolation, or ungrounded probes on every channel | two channels, two ungrounded probes |
| Field box | 316L wall-mount, manufacturer-rated NEMA 4X / IP66, not UL listed | one 35 mm DIN row, one block per loop |
| Shield landing | EMC gland at the panel entry, shield bar, bond one end | panel end |
| Extension cable | KX for Type K, polarity colours kept, own tray | away from drive output cable |
| Spare | one ungrounded probe per critical loop, on the shelf | one |
Decide by case. A card that asks for isolated sensors gets ungrounded probes on all its channels. A per-channel-isolated card with a fast loop can take grounded. Several machines at different frame potentials get ungrounded plus a single-end shield. A grounded probe you must keep running today gets a DIN-rail isolator now and an ungrounded replacement at the next outage. Size the panel end with the enclosure selector — DIN module count and panel-to-door clearance — and cover the field end from the stainless junction boxes. Everything is delivered in 10 business days, counted from your order, or from your approval of the drawing for custom work.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can you keep a grounded probe on a card that wants isolated sensors?
Only through an isolator: a DIN-rail signal conditioner accepts the grounded sensor on its field side and feeds the card an isolated signal on the other, one 35 mm DIN module per channel. Treat it as the bridge until the next outage, then fit an ungrounded probe and remove the error at its source, the 49 °C class of error in this article's example.
Is an exposed junction a third construction to consider?
Yes. The bare junction sits in the medium and is the fastest of the three, with no sheath lag at all. It wears and corrodes, and any conductive film on the junction puts the medium straight into your thermocouple circuit, so keep it for clean, dry gas on an isolated channel. On machines, order ungrounded.
What should a multimeter read between pin and sheath?
OL on a meter with a 10 MΩ input for a healthy ungrounded probe; a grounded one reads the lead and junction resistance, commonly 3 to 30 Ω on panel-length runs of 24 AWG extension wire. Lift both legs from the terminal block first, and keep the insulation test on the bare probe only.
Do both channels of a two-channel card need ungrounded probes?
Yes, when the two channels share one reference: either grounded tip ties that shared reference to its machine frame and both readings move. Cards with per-channel isolation between channels let you mix, so a grounded probe on one channel and an ungrounded one on the other is legitimate there.
Does the enclosure material change the grounded vs ungrounded decision?
No. Junction isolation lives in the probe tip, whatever box you land the wiring in. Choose 304 stainless for indoor panels and 316L at the washdown probe head; both carry a manufacturer rating of NEMA 4X / IP66 and are not UL listed. The box changes the shield landing and the bar layout, never the junction.