Short answer: buy one DIN rail signal conditioner per noisy 0-10 V channel, and choose it by its documented response, not by its trim pots. One selectable-input family documents a 35 ms step response and 100 ms on its voltage range. That 100 ms is the same order as the 159 ms time constant of the 1 Hz filter you are after. Check the analog card's onboard filter first, and buy isolation whenever the field ground and the panel ground differ. Inside the box, keep the unshielded run under 10 in [250 mm] and land the cable shield once on the panel ground. Then calibrate the whole chain end to end: unity gain on a trim pot is a moving target, and your scaling belongs in the PLC.
Where the noise gets in
A voltage analog signal meets three kinds of trouble inside a panel, and each has a different fix. Coupling comes first: a wire run beside a VFD output or a 120/240 V AC bundle picks up noise for the length of the run. Keep 4 in [100 mm] between analog wiring and power runs, and cross at 90 degrees where they must meet. That separation figure is the one typical drive installation guides use inside cabinets. Ground offset is the second: when the field device's earth sits a volt or two from the panel's earth, the difference lands on the input as real signal error. The check for that lives in the analog output ground offset inside a grounded enclosure article. Card conversion dither is the third, and a count or two of flicker on a clean wire is normal.
A first-order 1 Hz low-pass is the right tool when you want the DC value. DC passes at unity gain, and amplitude falls to 70.7% at 1 Hz (the -3 dB corner), to about 10% at 10 Hz and to about 1% at 100 Hz. Every reading is kept, the fast wobble is crushed, and the slow trend survives. That is what the corner buys you, and the conditioner datasheet is where you confirm it in numbers.
The spec that matters when you order
Check the card manual before you spend anything, because many analog input families carry a configurable digital low-pass filter. One classic card family's setting is written up in the SLC 500 digital low-pass filter for noisy analog signals. A card filter cleans conversion noise at the card; it cannot break a ground offset, and it does nothing for coupling that reaches the wiring. The conditioner is the purchase when you need isolation, a different signal form, or a documented analog response ahead of the card.
| Spec line | What to order | Why it matters |
|---|---|---|
| Input | 0-10 V, high impedance | Matches the field signal without loading the source |
| Output | Voltage for short runs; 4-20 mA when the conditioner sits far from the card | A current loop shrugs off ground offsets along the run |
| Response | Documented on the voltage range, not only on the mA ranges | One selectable-input family lists 35 ms typical, 100 ms on the voltage range |
| Isolation | Galvanic, input from output from supply | Breaks a field-to-panel ground offset dead |
| Mounting | 35 mm DIN rail; slim isolators run 6-12 mm wide, wider units 17.5-22.5 mm | Sets how many channels one rail length takes |
| Scaling | Zero and span trim or DIP, set once at commissioning | The trims are a commissioning tool, not a service adjustment |
The response line decides the filter question, so read how the datasheet defines its number. Some makers quote a time constant, some a 10-90% rise, some settling to within a percent of final. The same figure means different speeds under those three definitions. A conditioner documented only on its mA ranges can behave differently on its voltage range; the 100 ms figure exists in one family precisely because the ranges differ.
What 1 Hz costs you in response
Take a worked example with declared inputs: a level pot driving the input full-scale, with 50 mV pk-pk of ripple at 100 Hz, into a 12-bit card. Swap in your own span, ripple and card resolution; the method stays the same.
- Resolution: full-scale 10 V / 4096 counts = 2.44 mV per count, so 50 mV of ripple is 50 / 2.44 ≈ 20 counts of flicker at the input.
- Attenuation: a 1 Hz first-order filter cuts 100 Hz amplitude to 1 / √(1 + (100/1)²) ≈ 1%, so the ripple drops to 50 mV × 0.01 = 0.5 mV, about 0.2 counts — below one least-significant bit.
- Cost: the time constant is 1 / (2π × 1 Hz) = 159 ms, and the output settles to within 2% of a step in 4 × 159 ms ≈ 640 ms.
A conditioner documenting 100 ms on its voltage range lands in the same territory. Read as a time constant, 100 ms puts the corner at 1 / (2π × 0.100 s) ≈ 1.6 Hz. That corner turns 50 mV of 100 Hz ripple into about 0.8 mV, or 0.3 counts. The 640 ms settling is the price of the smoothing. It is fine for a level, a temperature or a setpoint, and wrong for a motion axis, where that much lag destabilises the loop.
A one-second stability timer is not this filter, whatever the ladder suggests. The timer discards every reading until the signal sits still for 1 s, so it hides a slow drift and adds up to a full second of dead time. The low-pass keeps every sample and only reduces amplitude above the corner. Use the timer when the process needs a qualified steady state; use the filter when it needs the DC value in real time.
Mounting and wiring inside the box
Mount the conditioners on the same rail run as the card terminals, because rail distance is wire distance. Keep the unshielded conditioner-to-terminal run under 10 in [250 mm], and switch to shielded twisted pair beyond that. How to mount DIN rail on a backplate shows the spacing that leaves room for duct. The analog signal conditioning enclosure layout article sets rail positions that keep analog away from power.
Give the analog pair its own duct run, and hold the fill at or under 50% of the duct's interior cross-section. That 50% figure is the wire fill one wiring-duct maker sets across all its fill tables, citing NFPA 79, because round cables leave air gaps. The backplate and DIN rail layout guide carries the duct-and-spacing pattern for the whole plate. An analog pair squeezed into a stuffed duct beside VFD output wiring hands back everything the conditioner removed.
Land the cable shield once, at the panel ground bar on the conditioner side. A shield bonded at both ends becomes a conductor for the voltage between two earths, which is the loop the VFD control cable shield grounding: bond one end article works through. The grounding and bonding guide carries the bar and bonding fundamentals.
Depth rounds out the layout: a slim isolator is small, but six of them with duct and terminals change the box fast. The enclosure size for DIN rail devices article works the minimum depth from rail, body and wiring. If you service the panel energized, keep 3 ft [900 mm] of clear depth in front of it. That is the depth NEC 110.26(A) asks for 0-150 V to ground in Condition 1, along with room for the door to open 90 degrees.
Calibrate the chain, not the trim pots
Most voltage conditioners are op-amp front ends with zero and span trimmers, and a datasheet that promises unity gain is rare. The gain is whatever the trims leave, and it moves whenever someone turns a screwdriver. Treat the conditioner as a pass-through with an unknown constant, and put the scaling where it is documented: in the PLC.
Inject known points — 0.00, 5.00 and 10.00 V from a meter accurate to 0.1% or better — and record the raw counts at the card for each. On the 12-bit card above, 0.1% of full scale is 10 mV, about 4 counts, so the calibration error stays invisible next to the 20-count flicker you started with. Enter the scaling in the controller and repeat the three-point check after any rewire, module swap or conditioner replacement. Do not tune a trim pot in service to rescue a reading; find out first whether the wire, the source or the scaling moved.
The wiring contributes almost nothing you could trim out. At full-scale output, a 1 MΩ card input draws 10 µA. 18 AWG runs about 6.4 Ω per 1000 ft, so a 10 ft run there and back is about 0.13 Ω and drops roughly 1.3 µV at that current. The 50 mV problem was never copper resistance; it was coupling, so the fix lives in layout and filtering rather than in gain.
What goes on the order
For each noisy channel, the order is short:
- one conditioner with its response documented on the voltage range
- a length of 35 mm rail and the end brackets
- wire duct for the analog run, held to 50% fill or less
- a shield-termination point on the ground bar
- a meter accurate to 0.1% and ten minutes at the three calibration points
The box is the other half of the order. A few channels fit a wall-mount stainless junction box: the line covers the nine smallest wall-mount sizes, each with a removable mounting panel and a hinged gasketed door. A bank of conditioners with terminals, duct and an HMI later deserves a custom stainless enclosure, cut from one piece to your width, height, depth and cutouts. Delivery on both is 10 business days — counted from your order, or from your approval of the drawing on custom work. Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.
The decision by case
| Case | Order this | The number behind the call |
|---|---|---|
| Slow process value, noise is coupling (level, temperature, setpoint) | Conditioner documented near 100 ms on the voltage range, 4 in [100 mm] separation, three-point calibration | Ripple to 0.3 counts, 640 ms settling |
| Field earth and panel earth differ | Galvanically isolated conditioner, shield bonded once at the panel bar | Isolation breaks an offset no filter can touch |
| Motion or fast axis | Skip the heavy lag: fix coupling and use the card's fast onboard filter | 640 ms of lag destabilises a loop |
| Clean grounds and a card filter available | No conditioner; set the card filter and calibrate | A card filter cleans conversion noise only |
One conditioner, a documented response, 10 in of unshielded wire, one shield bond and one calibration session: that is the whole job. It scales from a single channel in a junction box to twenty in a custom cabinet.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is a 1-second stability timer the same as a 1 Hz low-pass filter?
No. The timer samples once and discards the rest of the second, so it hides a slow drift and adds up to 1 s of dead time. A first-order 1 Hz filter keeps every reading, passes DC at unity gain, and cuts amplitude to 70.7% at its corner, about 10% a decade up and 1% two decades up. Use the timer for a qualified steady state and the filter for a live DC value.
How much response time does a 1 Hz filter cost?
A time constant of 159 ms and settling to within 2% of a step in about 0.64 s. A conditioner documented at 100 ms on its voltage range is the same order; read as a time constant, that is a corner near 1.6 Hz. Fine for a level or temperature, too slow for a motion axis.
Does the conditioner need unity gain?
No. Most voltage conditioners are op-amp front ends with trimmers, and gain moves whenever the trims move. Inject 0.00, 5.00 and 10.00 V from a 0.1% meter, record the card's raw counts, and scale in the PLC. A 0.1% meter sits within about 4 counts of a 12-bit card across full scale, so calibration error stays invisible.
How long can the analog wiring run inside the enclosure?
Under 10 in [250 mm] unshielded; beyond that, use shielded twisted pair. Hold at least 4 in [100 mm] between analog wiring and VFD output or 120/240 V AC runs, and cross at 90 degrees where they must meet. Bond the shield at one point only: the panel ground bar on the conditioner side.
When must the conditioner be isolating?
When the field device's earth and the panel's earth differ. That offset lands on a non-isolated input as real signal error, volts of it in VFD-rich plants, and no filter removes it because it is DC. Galvanic isolation between input, output and supply breaks the path; the shield still lands once, at the panel bar.
What enclosure suits a bank of DIN rail conditioners?
A few channels fit a wall-mount stainless junction box with a removable mounting panel and a 35 mm rail. A bank with terminals, duct and an HMI deserves a custom width, height, depth and cutouts. Our stainless boxes are manufacturer-rated NEMA 4X / IP66, not UL listed, and delivered in 10 business days.