No — the Category 0 result at the MCC stops at the transformer, and you label each 120 V control panel from its own bus. The lighting transformer between them resets both numbers that set incident energy: the fault current, now set by the transformer's impedance, and the clearing time, set by whichever device actually opens. Panels on transformer secondaries routinely calculate higher than the switchgear ahead of them. Two shortcuts people reach for both fail. The old guidance that a single 125 kVA or smaller transformer at up to 208 V could be treated as 1.2 cal/cm² or less left NFPA 70E in the 2012 edition. And cutting assumed arcing time from 2 s to 0.5 s divides the calculated energy by four while proving nothing about the device. Here is how to get the number that goes on the door.
Why the MCC result stops at the transformer
The Category 0 label was calculated at the MCC bucket, with the fault current available there and the upstream device that clears a fault there. Your 120 V panel sits behind a transformer, and a transformer is a new source with its own impedance. Treat the primary as an infinite bus and divide secondary full-load current by the impedance figure: a 3% impedance transformer caps its own secondary fault at about 33x full-load current, and cable impedance trims it further on the way to your panel.
Clearing time moves the other way. With no dedicated device on the secondary, a fault at the panel waits for the primary fuse, and the reduced current can sit far down that fuse's curve — seconds instead of cycles. Low current held for a long time is the recipe for high incident energy, which is why lighting panels so often carry the biggest numbers in a plant. A label describes one working location; where one enclosure holds two energy levels, you need multiple arc flash labels on one enclosure.
Where the 125 kVA cutoff went
Until 2012, NFPA 70E let you skip the calculation for circuits fed by a single 125 kVA or smaller transformer at up to 208 V and treat them as 1.2 cal/cm² or less. The 2012 edition removed the exception, and it has not come back. Two things killed it. Later test data questioned whether those small transformers were safe to ignore. And the exception had come from 2002-era IEEE 1584, so it only covered studies run to that one method.
The physics behind the old cutoff is real. At 120, 208 and 240 V, arcs tend to self-extinguish, while the IEEE 1584 equations assume a stable, sustained arc — so the math leans conservative on a small lighting panel. Conservative math you can defend beats an exemption you cannot. Run the incident-energy method down to the panel, or use the task tables with their conditions met at that panel.
Using the NFPA 70E tables at the panel
The tables assign a PPE category by task, equipment class and voltage. Voltage testing at a 120 V panel lands in Category 1, minimum arc rating 4 cal/cm², provided the panel meets the table's printed conditions — a maximum available fault current and a maximum clearing time. Those two numbers come from the transformer impedance and the secondary device's curve, so the table route still hands you the same calculations. Do them, compare them with your edition's limits, and the Category 1 result stands on its own.
Two notes while you are in the tables. Newer NFPA 70E editions list Categories 1 through 4; what used to be Category 0 is now the case of incident energy at or below 1.2 cal/cm², where arc-rated clothing leaves the table. And since voltage testing is energized work, keep the shock side separate — boundaries and gloves follow the 120 V voltage, and arc flash PPE starts with the work task, not with the box.
The arcing time you may enter
Incident energy scales linearly with arcing duration, which makes time the lever everyone is tempted to pull. The 2 s figure in most studies is a cap, not a measurement: the convention says a person can move away inside 2 s, so a device slower than that gets entered as 2 s. Capping a slow device at 2 s has a documented basis. Cutting 2 s to 0.5 s has none — it divides the result by exactly four (2 ÷ 0.5 = 4) and describes a clearing time nobody has shown to exist.
Get the units right while you are in there. One cycle at 60 Hz is 16.7 ms, so a breaker clearing in 1–2 cycles takes 0.017–0.033 s. A report that prints "1–2 cycles (0.16–0.30 s)" has slipped a factor of ten; that range is ten cycles. The time you enter is the total clearing time of the installed device at the calculated arcing current, read from its time-current curve.
A worked example: 75 kVA feeding one panel
Work this through with example assumptions, then replace each with your transformer's nameplate and your study's output. The study models the three-phase arc at the panel bus and takes it as the conservative case for the 120/208 V circuits.
- 75 kVA dry-type transformer, 480 V primary, 120/208 V secondary, 3.0% impedance
- Secondary full-load current: 75,000 VA ÷ (1.732 × 208 V) = 208 A
- Bolted three-phase fault at the secondary, infinite primary bus: 208 A ÷ 0.03 = 6,930 A, call it 6.9 kA
- Arcing current at the panel after cable impedance: 5.8 kA, the study's output (illustrative here)
- Working distance 18 in [457 mm], the usual panelboard distance
Case 1 — no dedicated secondary device. The fault clears on the primary fuse, whose curve at the reflected current gives 2.0 s. The study returns 4.8 cal/cm², and that is the label: incident energy 4.8 cal/cm² at 18 in, clothing arc-rated to match, boundary from the same run.
Case 2 — a 200 A main breaker in the panel, instantaneous pickup near 10x handle rating, about 2,000 A. The 5.8 kA arcing current is nearly three times that pickup, so the breaker clears in its instantaneous region, about 2 cycles: 0.033 s total. Same box, same distance, so energy scales by the time ratio:
4.8 cal/cm² × (0.033 s ÷ 2.0 s) = 0.08 cal/cm²
One device in its fast region moves the label from 4.8 cal/cm² to 0.08 cal/cm², below the 1.2 cal/cm² level where arc-rated clothing leaves the table. A 200 A time-delay Class J fuse is faster still — the table below shows how to check one against your study.
What the transformer secondary needs
When the panel main is the only device on the secondary, a fault on the secondary lugs or the feeder clears on the primary side, limited by transformer and cable impedance alone. That is the classic high label. The fix is a dedicated device near the transformer — a fused disconnect or a breaker, in the panel you are labeling or in its own enclosure beside it. For the selection logic, read when to use a fused disconnect switch.
Size whichever you choose against your arcing current:
| Device | How it clears fast | What to check against your study |
|---|---|---|
| Molded-case breaker | Instantaneous pickup near 10x handle rating; 1–2 cycles (17–33 ms at 60 Hz) to clear | Arcing current above the pickup — about 2,000 A for a 200 A breaker |
| Time-delay Class J fuse | Current-limiting only at high current; it carries 5x its rating for at least 10 s (UL 248-8) | Arcing current many times the rating — 200 A and below favors this on a small lighting transformer |
Accept the coordination trade that comes with it: a secondary device clearing in 33 ms takes selectivity from everything above it. For a panel people open and probe live, that trade is worth making.
The box is part of the number
IEEE 1584's 2018 equations take enclosure height, width and depth as inputs, so the steel around the arc moves the answer. A shallower enclosure calculates lower incident energy for the same fault, and compartmented equipment is modeled box by box — see how IEEE 1584 handles MCC buckets. Feed the study the enclosure you are actually buying: choose it with the enclosure selector while the design is still open. If the panel is a small stainless box at the machine, the stainless junction box sizes page lists each size's depth and panel, and that geometry is what the study should use.
What goes on the label, and on the order
NFPA 70E has the label carry the nominal system voltage, the arc flash boundary, and either the incident energy at its working distance or the PPE category. Put the study date and reference on it too. Reviews come at least every 5 years, and sooner after any change that moves fault current or clearing time — your new secondary disconnect is exactly such a change, so re-run before you relabel.
The door already needs an enclosure type number for its location: NEC 409.110 puts one on an industrial control panel, and NEC Table 110.28 lists which types suit which conditions. Set the arc flash label beside that marking. If a disconnect on the same box sits under lockout, it still carries its own arc flash label.
Ordering sequence that saves a redo: put the secondary device on the enclosure drawing now — door cutout, mounting pattern, gland entries. A custom box is delivered in 10 business days from your approval of the drawing, and the study wants the finished geometry.
The decision by case
- Panel installed and unlabeled: extend the study through the transformer to the panel's own bus and label from that number. In many plants it beats the MCC's Category 0.
- Tables are your method: compute available fault current and clearing time at the panel first. With the conditions met, the Category 1 result for voltage testing is sound.
- Label came out high: add secondary protection that clears your arcing current in its fast region, then re-run. The example moved 4.8 cal/cm² to 0.08 cal/cm².
- Panel still on paper: choose the enclosure and the secondary device together, feed the study the real dimensions, label once.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I label the 120 V control panels with the MCC's Category 0 result?
No. The lighting transformer between them changes both inputs: fault current at the panel is set by the transformer impedance (about 33x full-load current at 3% impedance), and clearing is set by whichever device actually opens, often the primary fuse in seconds. Assess and label each panel at its own bus; secondaries routinely calculate higher than the upstream switchgear.
Is there still an exemption for panels on transformers of 125 kVA or less?
Not since the 2012 edition. The old guidance — a single 125 kVA or smaller transformer at up to 208 V treated as 1.2 cal/cm² or less — came from 2002-era IEEE 1584, and later test data questioned it. Calculate down to the panel, or meet the NFPA 70E table conditions at that panel.
Can I enter 0.5 s as the arcing time to lower the energy?
Only when the installed device's time-current curve clears your calculated arcing current in 0.5 s or less. Energy is linear in time, so moving from 2 s to 0.5 s divides the result by four (2 ÷ 0.5 = 4) — which is exactly why an invented time is dangerous. One cycle at 60 Hz is 16.7 ms; a breaker clearing in 2 cycles is 0.033 s, not 0.3 s.
Will a fused disconnect on the transformer secondary lower the label?
Yes, usually by an order of magnitude, when your arcing current sits several times the fuse rating. In the worked example, 5.8 kA against a 200 A time-delay Class J fuse is 29x rating, inside its current-limiting range, clearing in under half a cycle (8.3 ms at 60 Hz). Read the fuse's curve against your current, then re-run the study before relabeling.
How often does the study behind the label need a review?
At least every 5 years, and sooner after any change that moves fault current or clearing time — a new transformer, a replaced breaker, or the secondary disconnect you just added. Keep the one-line diagram and the study in agreement with what is actually installed.





