Short answer: the shock between a mobile servo cabinet and other metal in the room is high-frequency common-mode current from the drive with no short, low-inductance way back. A bigger ground conductor will not fix it; resistance at 60 Hz is not the problem. Bond the cabinet frame to building steel with a short flat braid. Land the motor ground lead and the cable shield on the drive chassis terminal with a 360° termination at the gland, and confirm the supply transformer secondary is bonded as a solidly grounded wye. On the installations behind these numbers, a 500 ft [150 m] feeder with a 2/0 grounding conductor and a 250 kcmil bond is already oversized for fault current. The missing piece is a high-frequency path a few inches long.
If people are receiving shocks from accessible metal, stop contact with the equipment. Have qualified electrical personnel de-energize and verify absence of voltage before inspecting bonding connections.
What each symptom points to
- A small shock between cabinet and other metal, only while the drive and motor run. Common-mode current developing a touch voltage across an inductive bonding path. If it persists with the drive off, suspect an insulation fault or a broken protective-earth connection instead.
- Shock felt between two metal parts, not from one part to a person standing alone. The current is flowing between those parts, and you become a parallel path. A person does not need to be the lowest-impedance path to receive current; it divides.
- Inductive sensors dropping out in a zone near the drives, recovering when the drives stop. Radiated and conducted coupling from the same common-mode current. This is the diagnostic clue that confirms a switching-frequency mechanism.
- Bonding resistance reads low but the voltage persists while running. High-frequency impedance in the path, or a fast waveform the meter cannot characterize. Low DC resistance and low AC inductance are different properties.
- Different meters read different voltages on the same metal. A fast pulse measured with meters of different bandwidth and lead routing. Use a suitably rated oscilloscope or differential probe before trusting any single reading.
- Reinstalling the drive grounding jumper helped a little. The jumper changed the internal common-mode return or filter path. Its correct state depends on the supply grounding arrangement. Verify it against the transformer, not against the meter.
The causes, most likely first
- No short high-frequency bond between the cabinet frame and the surrounding grounded metal. Casters and rubber mounts are the usual reason on a mobile cabinet. The frame rides on wheels, the room metal is grounded through the building structure, and the only connection between them is hundreds of feet of wire, which is inductive at switching frequency.
- Motor ground lead or shield not landed on the drive chassis terminal. If the motor ground goes to a ground bar instead of the drive's own chassis PE terminal, the common-mode current flows out into the building ground system. It should circulate back to the drive over inches.
- Shield terminated with pigtails or not at all. A pigtail adds inductance right where the current needs to change conductor. A 360° clamp at the gland does the job.
- Transformer secondary bonding missing or wrong. A dedicated step-down transformer is a separately derived system. Its secondary needs its bonding connection to the equipment grounding system; an upstream grounded system does not ground the secondary by itself.
- A genuine insulation or leakage fault. Always ruled out with an insulation test, but unlikely when the symptom tracks drive operation exactly.
How to check each cause
De-energize, lock out and verify absence of voltage first. Then:
- Confirm the supply grounding. At the transformer secondary, find the grounded point and its bonding connection. The system here is a grounded wye step-down. On such a supply most drives ship with their grounding jumper installed, and that is the state the instructions call for. On a high-resistance, impedance-grounded or floating supply, the instructions call for removing the factory screws. Match the jumper to what you find at the transformer.
- Inspect the motor cable terminations. The motor ground lead lands on the drive chassis PE terminal, not on a ground bar. The shield clamps 360 degrees at the drive gland and at the motor box. Details of why both ends matter are in VFD motor cable shield grounding: both ends and why, and the gland-side termination in Grounding conductor enclosure entry: connector and bond.
- Check the drive chassis-to-frame bond. The drive must bolt through paint to bare cabinet metal. Nonconductive coatings at grounding contact surfaces have to be removed at the joint, a rule NEC 250.12 states for equipment and enclosures.
- Find the path from cabinet frame to room metal. On a mobile cabinet this is often only the caster plates scraping a floor and then the building slab. This is the inductive gap the braid closes.
- Measure with the right instrument. Use a rated oscilloscope or differential probe across the joint, with the probe leads routed away from the motor cable, while the drive runs. Keep everyone clear and use insulated tools; this is live troubleshooting near power electronics.
Sizing the braided bond: the arithmetic
The rule: the voltage developed along a bonding conductor during a fast current change follows V = L × di/dt. A straight round conductor has roughly 1 µH of inductance per meter of length at these frequencies, whatever its cross-section. Flat braid shortens the loop and lowers the inductance. Shortening the path matters more than fattening the wire.
Take the case behind the numbers: the drive connects to ground through a #12 lead to a ground bar, then a feeder roughly 500 ft [150 m] long with a 2/0 grounding conductor, and a 250 kcmil bond at the transformer. That feeds a 70 A breaker and three motors of 10, 5 and 3 hp. Assume a common-mode current step of 1 A in 100 ns at the drive output (a typical order for a small servo axis; measure it with a clamp and scope before relying on it).
- Inductance of the effective return path: even 10 m [33 ft] of routing through the building steel loop gives L = 10 m × 1 µH/m = 10 µH.
- di/dt = 1 A ÷ 100 ns = 1 × 10^7 A/s.
- V = 10 µH × 10^7 A/s = 100 V peak. The pulse is fast and the energy small, so it feels as a sting and reads differently on every meter, exactly the symptom described.
Now fit a 0.5 m [20 in] flat braided bond between cabinet frame and building steel: L ≈ 0.5 µH, so V = 0.5 µH × 10^7 A/s = 5 V peak. Above roughly 20 V of measured touch voltage while running, the high-frequency bond is inadequate; below that, it does its job. Replacing the #12 with a 2/0 along the same 10 m route still gives 10 µH and the same 100 V. That is why a larger conductor is money spent on the wrong property of the wire.
The fix, in order
- Fit a short flat braided bond, at least as wide as it is long and no more than 0.5 m [20 in] long, from bare cabinet frame metal to the nearest building steel or grounded column. Bolt it through removed paint at both ends.
- Land the motor ground lead on the drive chassis PE terminal and the motor cable shield in 360-degree clamps at the drive gland and the motor junction box.
- Keep motor cables separated from control and sensor wiring, and keep the sensor wiring out of the coupling zone near the drive bottom.
- Confirm the transformer secondary bonding and the drive grounding jumper against the supply grounding arrangement.
- Re-run the equipment grounding check for fault current. The existing 2/0 and 250 kcmil already exceed what a 70 A breaker needs at power frequency, so leave that path alone.
- If bearing noise or fluting shows up on the motors afterwards, read Shaft grounding brush and VFD enclosure: route the bearing current out before replacing bearings.
How the grounding checks prove it: touch voltage between cabinet and room metal below roughly 20 V while the drive runs at full output, sensors stable with the drives running, and the oscilloscope showing the pulse confined to the drive chassis loop.
Keeping it fixed on a mobile cabinet
A cabinet on casters moves, and every move can scrape or lift the bond. Give the braid slack for the cabinet's full travel. Bolt it rather than clip it, and put the bond check on the cabinet's move-in checklist. If the cabinet rolls between rooms with different ground references, the bond goes to the steel in each room. Grounding fundamentals and the effective fault-current path are covered in the enclosure grounding and bonding guide. How shared paths create the stray currents that confuse these measurements is in Stray current on equipment grounding conductor: find the cause.
When to re-specify the enclosure
Re-specify when the fix keeps coming undone. If the cabinet must roll constantly and no fixed braid survives, order the next cabinet with a welded grounding lug on the frame and a dedicated braided bond as a fitted accessory. That makes the connection a designed joint instead of a field improvisation. A custom stainless cabinet can carry that lug from the drawing stage, which keeps the paint masked at the joint and the 360° shield clamps in the gland plate from day one. Two cabinets with the same symptom in one building means the detail is systematic; fix the detail, not one cabinet.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Will a larger ground conductor stop the shock from a drive cabinet?
No. A 2/0 or 250 kcmil conductor lowers resistance at 60 Hz, but the touch voltage on a running drive follows V = L × di/dt. A long round wire has about 1 µH of inductance per meter regardless of its cross-section. Fix the high-frequency path: a short flat braid to building steel, motor ground and shield landed on the drive chassis terminal, and a 360° shield termination at the gland.
How much voltage can common-mode current develop between two metal parts?
Enough to feel and to measure differently on different meters. For example, a 1 A common-mode step in 100 ns through 10 µH of bonding wire gives V = 10 µH × 10^7 A/s = 100 V peak, and through a 0.5 µH braided bond only about 5 V. The waveform is a fast pulse, so meter bandwidth and lead routing change the reading by tens of volts.
Does the drive grounding jumper belong in or out?
In, on a solidly grounded wye supply, which is the common case and the arrangement most drives ship configured for. Match the jumper to the supply grounding at the transformer secondary, not to whether a trial change makes the meter read smaller.
Why do nearby inductive sensors drop out when the drives run?
The same common-mode current radiates from the motor cables and from displaced return current in the bonding network, and the field couples into the sensor wiring. It is a diagnostic clue that points at the cable shield termination and the return path. Fix those and the interference stops with the touch voltage.





