Short answer: when a ground-fault trip stays at one drive position after a different motor and a different cable have both tripped it, stop replacing drives. Work the position instead: the branch feed first, then the shield terminations, then the bonding at that cubicle, one variable per test. The running example is a 7.5 kW drive on a 5.5 kW, 415 V motor with about 30 m [98 ft] of braided-shield cable. It trips while two identical neighbors run clean. The capacitance and impedance figures below are worked-example assumptions; replace them with your cable datasheet and your drive manual. One plant burned seven drives in three weeks on exactly this pattern before anyone tested anything beyond the motor circuit.
What the trip is actually reporting
A ground-fault trip is the drive reporting that output current is escaping the phase-to-phase motor circuit, read as an imbalance among the three output currents. The trip names the condition; it does not name the failed part. A real insulation breakdown causes it, and so does capacitive leakage into the cable shield, an intermittently damaged conductor, a loose termination or damage inside the drive's output stage.
Capacitance sets the baseline on every run. The output swings between roughly +587 V and -587 V at the carrier — a 415 V drive idles with its DC bus near √2 × 415 ≈ 587 V — and every meter of shielded cable is a small capacitor to that shield. The switching edges charge it, the shield carries the current back through the drive, and the detector counts part of it. Two drives on identical runs should read identical leakage. When one position trips again and again while its neighbors never do, the baseline explains the plant; it does not explain the difference at that one position.
The capacitive leakage, in numbers
Worked example, inputs labeled: shielded VFD cable at 150 pF per meter per phase to shield (a datasheet figure you replace with your own), a 30 m run, a 4 kHz carrier, a 587 V DC bus. Treat the cable capacitance as a reactance at the carrier frequency: X = 1/(2πfC) = 1/(2π × 4,000 Hz × 4.5 nF) ≈ 8.8 kΩ. The leakage envelope per phase is I = V/X = 2πfCV ≈ 587 V / 8.8 kΩ ≈ 66 mA. Three phases together pulse about 0.2 A into the shield, and the drive's ground-fault detection sits above that baseline until something adds to it. Edge speed and modulation set the exact value; this estimate gives you the size and the direction.
| Change to the example run | Leakage per phase | What it moves |
|---|---|---|
| 30 m at 4 kHz (the example) | 66 mA | the baseline |
| 100 m at 4 kHz | 220 mA | length, linearly |
| 30 m at 8 kHz | 132 mA | carrier, linearly |
| 30 m at 2 kHz | 33 mA | halve the carrier, halve the leakage |
| output 75 Hz against 64 Hz | about 66 mA either way | output Hz sets speed, not leakage |
Every term in 2πfCV is linear: double the length and the leakage doubles, double the carrier and it doubles again. Output frequency barely enters the formula, which is why the popular 75 Hz to 64 Hz change moved nothing on a trip like this.
Read the swaps already run
A swap is only a test when you change one thing and write down the result. Read each outcome against what you changed:
- A different motor tripped at the same position: the original motor moves down the list.
- A temporary cable tripped at the same position: the original cable moves down the list.
- Both neighbors ran for weeks on the same source: a plant-wide supply problem is unlikely; one bad branch is still possible.
- The trip returned with the motor leads off the drive terminals: the external circuit is no longer creating a new leakage path. Treat that drive as damaged, quarantine it and stop resetting it.
- The feed swap is still open: it is the decision point, and the next section shows how to read it.
Record the drive serial number, the panel position, the breaker and the motor/cable set at every swap. A position that keeps popping drives can be popping a different serial number each time. 'The same drive failed again' and 'the same position failed again' are different diagnoses, and only the log separates them.
Swap the branch feed next
Leave the outputs exactly where they are and exchange the branch feeds between the tripping drive and a healthy neighbor: breaker for breaker, including the short feeder from breaker to drive terminals. Note on your labels which breaker now feeds which drive, then read the result:
- The fault follows the feed: the breaker, its terminations, the feeder or that branch's grounding is the suspect. Re-torque the line and load terminations and inspect the feeder run.
- The fault stays at the position: the drive side carries it — output terminations, shield termination, gland-plate bonding or the drive itself.
A continuity check proves a breaker closes; it does not show how it holds a switching load, so read the breaker in the panel, under the drive. Change one side per test: moving the motor assignment and the feed together hides which change moved the symptom.
Megger the motor circuit with the drive out
One safety rule before any of this: isolate, lock off and prove dead. Never apply a megger to a circuit still connected to the drive; disconnect the motor leads at the drive terminals and test the motor and the cable separately. Use a megger at or below the circuit's rated voltage: 500 V DC on a 415 V winding, 1000 V DC on the cable. Where the motor datasheet prints its own test figure, that figure wins. Measure phase-to-earth and phase-to-phase on both the motor and the cable, and compare your three phase readings against each other instead of hunting a single pass mark. IEEE 43, the rotating-machine insulation-resistance standard, puts the floor for a modern 415 V machine at about 1.4 MΩ, corrected to 40 °C.
Then tug-test every accessible termination: motor terminal box, gland backs, drive output terminals. A conductor can pass a stationary insulation test and touch ground once the assembly vibrates, heats or moves; the tug test finds that one. The motor-end details live in the article on grounding a motor junction box with the motor ground wire.
Re-terminate the shield at that position
A braided VFD cable shield does its work only when it lands 360° at both ends. A cable maker's termination note describes the 360° termination as a full-circle, large-surface bond between the shield and the termination hardware. Shield-terminating glands make exactly that contact when tightened onto the braid. A pigtail is a single-wire bond, not a shield termination; cut it back and clamp the braid instead.
Work the position end to end:
- Motor end: open the motor terminal box and confirm the braid is clamped full-circle, not twisted onto the earth stud and snipped. The motor earth keeps its own terminal.
- Drive end: the braid clamps to a bare gland plate or a clamp saddle, and the coating comes off the contact surfaces; NEC 250.12 requires paint, lacquer and enamel removed at grounding and bonding connections.
- Entries: every gland sits in a cut hole, and the box holds its rating only with glands rated for that hole; see what a panel keeps after you cut it and mount devices. Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.
- Routing: keep the motor cable along the compartment edge, off the control wiring and its duct; the backplate and DIN-rail layout guide shows the split.
Control shields follow their own rule: bond a control cable shield at one end, at the panel, and the control-shield grounding article shows where and why.
Judge the position, not the drive
If the trip survives the feed swap, a clean megger and fresh 360° terminations, two suspects remain: the bonding at that cubicle and disturbance between the drives.
Bonding first. The enclosure, back plate and gland plate at that position carry the fault current. NEC 250.96(A) calls for metal parts serving as equipment grounding conductors to be bonded so they can safely conduct that current, so confirm the back plate is bonded and not floating; the article on two ground bars in one enclosure shows what a back plate can and cannot carry. The earth is not the fault path here: NEC 250.4(A)(5) keeps it out of the effective ground-fault current path, so a driven rod at the cubicle fixes nothing.
Disturbance second. A healthy neighbor can put high-frequency noise onto a shared supply and stress the input filter of the drive next door. Ten minutes with a scope or a high-frequency current clamp on the incoming terminals of both drives, compared side by side, settles it. If the entry hardware itself is on your suspect list, the motor-cable-entry article weighs gland against locking connector.
Keep it from coming back
Write down the position, not just the part. A log that records drive serial number, panel position, breaker, motor/cable set and the saved parameter file turns the next trip into one swap. Save the drive's parameter set before every replacement so the new unit comes up identical. Keep one assembled spare of the frame you run, and mark every quarantined drive so it cannot wander back into service.
Fix the terminations once, properly: full-circle clamps at both ends, bare metal on the gland plate, output terminals torqued and tug-tested. Most repeat ground-fault sagas end at a termination, not at a seventh drive.
When to re-specify the enclosure
Some positions earn a rebuild rather than a seventh drive. Re-specify the cubicle when the fault traced to the gland plate or the bonding, when the motor entries crowd the control side, or when the washdown schedule keeps the box wet and the terminations damp:
- Separate the power entries from the control entries on the gland plate, and give every motor cable its own 360° clamp position.
- Bond the back plate and strap the door across its hinges; the grounding and bonding guide covers the fault path end to end.
- In a washdown plant, 316L stainless with rated glands holds the manufacturer's rating through hose-down; start from the washdown enclosures section or browse the 316L wall-mount sizes.
A re-cut gland plate is a custom order, delivered in 10 business days from your approval of the drawing. The closing decision, by case: a fault that follows the feed belongs to the branch; a fault that stays at the position belongs to the terminations, the bonding or the drive; and only when the feed, the megger and the terminations all come back clean does the drive itself earn the order.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What insulation-resistance reading is good enough on a 415 V motor?
IEEE 43 puts the floor at about 1.4 MΩ for a 415 V machine, corrected to 40 °C, but a healthy 5.5 kW random-wound winding reads in the hundreds of megohms at 20 °C. Insulation resistance roughly doubles for every 10 °C of cooling, so log the reading, the test voltage and the winding temperature for each phase, and judge the three phases against each other: one phase far below its two neighbors is the fault.
At what cable length does capacitive leakage start tripping drives?
Leakage scales with length: on the worked example's 150 pF per meter cable at a 4 kHz carrier and a 587 V DC bus, I = 2πfCV gives about 66 mA per phase at 30 m, 110 mA at 50 m and 220 mA at 100 m. Length alone rarely trips a healthy drive, but it stacks with carrier frequency, and drive installation manuals commonly ask for an output reactor or dv/dt filter on long runs, many from about 50 m.
Does dropping the output frequency from 75 Hz to 64 Hz stop the trips?
Output frequency sets motor speed; the leakage follows the carrier instead. On the worked example run, I = 2πfCV gives about 66 mA per phase at a 4 kHz carrier, 132 mA at 8 kHz and 33 mA at 2 kHz, so the carrier is the knob that moves leakage. Lowering the carrier adds a little audible motor noise and a small continuous-current derating, and the drive manual prints the exact figure for the frame.
Can a recurring ground fault come from the supply side?
It can, and the feed swap reads it: a fault that follows the branch points at that breaker, its terminations and the feeder, while one that stays at the position points back to the drive side. A neighbor can also inject high-frequency disturbance onto a shared supply, so ten minutes with a scope or a high-frequency current clamp on the incoming terminals of both drives settles it before any further replacement.
Do I bond the motor cable shield at one end or both ends?
Bond the braided power shield 360° at both ends, with shield-terminating glands or clamp saddles onto a bare gland plate. A 100 mm pigtail adds about 0.6 Ω at 1 MHz and 6 Ω at 10 MHz, taking roughly 1 µH per meter for the tail, where a full-circle clamp sits near zero. Control cable shields are the exception: bond those at one end, at the panel.