Short answer: that datasheet line is a supply condition, and an impedance-earthed IT receptacle does not meet it as wired. On a 240 V IT system the first earth fault parks the healthy conductor at line voltage to PE, and the insulation monitor only alarms. Feed the tool from its own isolating transformer, 300 VA covers a 1.2 A handset in the worked example below, with one secondary pole bonded to PE. Check the trailing-cable PE path reads under 1 Ω before you plug in, and you have met the datasheet condition while the machine keeps its IT behaviour.
What a grounded supply means on the datasheet
A "grounded power supply system" line describes your socket, not the tool. It means a TN-style source: one pole tied to earth at the source, so line-to-PE holds a steady full line voltage, the other pole sits near 0 V to PE, and a first fault clears in about 0.4 s on a final circuit up to 32 A, the IEC 60364-4-41 time. Protection class is a separate marking under IEC 61140. Class I gear relies on its PE pin for shock protection; Class II gear uses double or reinforced insulation and carries no pin.
A Class I tool also houses EMC filter capacitors from each supply pin to the PE pin, rated for the referenced supply just described. Read the whole power-input assembly, external adapter included, because the adapter has its own input rating and class mark. Two separate conditions, both printed, both on you to satisfy.
What the first earth fault does to your tool
On a healthy single-phase IT supply the two conductors float, each near 120 V to earth, set by stray capacitance. A heavy filter on one side can pull that anywhere between 0 V and the full line voltage. The first earth fault fixes the picture: the faulted conductor drops to about 0 V to PE, the healthy one rises to full line voltage, and nothing clears it, which is the design intent. A second fault on the other conductor then lands as a bolted line-to-line short through your bonding.
Run the numbers for a 240 V system through a 5 kΩ neutral impedance, mid-range of the 1–10 kΩ typically fitted under the IEC 60364-4-41 classification. Fault current is 240 V ÷ 5,000 Ω = 48 mA. Exposed parts bonded at, say, 5 Ω put the touch voltage at 48 mA × 5 Ω = 0.24 V, far under the 50 V that IEC 60364-4-41 lets you run on through a first fault.
So the monitor alarms, the machine keeps working, and the tool's earth-referenced pin holds full line voltage to PE for as long as that fault stands. Behind a TN socket the same event is a dead trip, which is what the input stage was built around. The why an IT panel shows phase-to-earth voltage article covers what your meter reads while this state exists.
Where the impedance sits decides the answer
Mobile machines often get described two ways at once: impedance grounded, yet with the neutral landed on the panel ground bus, and the bus carried out through a trailing cable and an overhead line to an earthing point far from the pit. Those describe different supplies, and the feed you give the tool follows from which one is real. Find the impedance on the drawing first.
| What the drawing shows | What you actually have | What you do |
|---|---|---|
| Neutral to earth through 1–10 kΩ at the source | A true IT system: first fault alarms and runs | Feed the tool from its own earthed isolating transformer |
| Neutral bolted straight to the panel ground bus | An earthed-at-the-panel supply wearing an IT label; the monitor reads a standing fault | Correct the drawing or the wiring first, then transformer-feed the tool |
| Neutral to the bus, bus tied only to a remote electrode | The PE conductor is the whole protection path | Keep the PE as the path and measure its continuity |
A voltmeter will not settle the question. A 10 MΩ instrument draws at most 24 µA at 240 V, and 24 µA through 5 kΩ moves the reading 0.12 V, so a solid tie and an impedance tie both show the same near-zero between neutral and PE. The drawing tells them apart, or the first fault does.
Two code anchors cover the far-away earthing point. The earth itself is not the effective ground-fault current path under NEC 250.4(A)(5), and a remote electrode serves only as an auxiliary one beside the PE conductor under NEC 250.54. A neutral bolted to the bus also puts return current on the frame, which NEC 250.6 exists to prevent. The panel earth and shield earth bars article shows the bar layout, and the enclosure grounding and bonding guide carries the fault-path fundamentals.
Give the tool its own earthed supply
The fix is a portable isolating transformer, same voltage in and out, in its own box on the machine, feeding one receptacle. Bond one secondary pole to the PE contact of that receptacle and you have built a local TN system: line-to-PE at line voltage, the other pole near 0 V, and a first fault on the tool clears through the transformer's secondary protection. The primary faces the IT float and the fault shift with insulation rated for full line-to-earth voltage, which is what an isolating transformer is for. A receptacle already fed from a site transformer with an earthed secondary does the same job.
Size it from the tool's plate. Worked example with typical handheld numbers: a 1.2 A handset draws 1.2 × 240 = 288 VA. A 300 VA unit runs at 288 ÷ 300 = 96 %, so pick 500 VA and it cruises at 288 ÷ 500 = 58 %, with room for a charger. Swap in your tool's real plate current before ordering.
The transformer, its breaker and the receptacle fit a small wall-mount stainless box. The sizes on the stainless junction boxes page start small, and the enclosure selector finds one by inside height and depth. When the depth does not fit, a custom box comes with every cutout done at the factory. You set 304 or 316L, the width, height and depth and the hole pattern, delivered in 10 business days from your approval of the drawing. Factory cutouts keep a box rated NEMA 4X / IP66 by the manufacturer (not UL listed) sealing as built. Bond the box, the transformer tie and the receptacle earth to the panel PE bus; bonding a metal receptacle junction box covers the landing, and earth continuity through a gasketed gland plate sizes the link.
Check the PE path before you plug in
Your new TN circuit clears faults on loop impedance, so give it a budget. A 16 A Type B breaker trips magnetically by 5 × In = 80 A under the IEC 60898-1 definition of Type B, and 240 V ÷ 80 A = 3 Ω for the whole loop. The transformer, its breaker and the short local run consume little of that; the machine-side PE path is what you measure.
Worked example, assumptions marked: a 25 m trailing cable with a 2.5 mm² copper PE runs 25 × 7.41 Ω/km ÷ 1,000 = 0.185 Ω cold, using the IEC 60228 resistance for that size. Warm at 70 °C, with copper climbing 0.39 % per K over 50 K, it is about 0.22 Ω. Hold the whole receptacle-to-main-bond path under 1 Ω and the cable owns a fifth of it, leaving connectors, gland bonds and box bonds to account for the rest. A reading near 1 Ω is a joint talking, not copper. Drive the test with a continuity or loop tester that supplies real current, the way IEC 60364-6 verification does; a bench multimeter reads its own leads. Isolate the machine and prove it dead before the test.
The decision, case by case
- Impedance at the source and the monitor healthy: a proper IT system, and it stays one. Transformer-feed the tool, and the 48 mA, 0.24 V first-fault behaviour keeps doing its job.
- Neutral solid on the bus: drawing and IT label disagree. Fix the classification first, because a monitor cannot alarm through a shorted impedance, then transformer-feed the tool regardless.
- Tool or adapter marked Class II: read the adapter plate, because a PE pin makes the assembly Class I in practice. The transformer covers both cases.
On the question you actually asked, life and warranty: the stress on the tool is the voltage its input sees, and behind its own earthed secondary that voltage is the one its filter was rated for. Warranty then reads the maker's terms against a supply that meets the datasheet, which is the position you want.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 6 in | 304 stainless | 10 x 8 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Will an IT supply shorten the life of a Class I tool?
It can. After a first earth fault the filter capacitors that expected about 0 V to PE on the referenced pin hold the full line voltage continuously, and dielectric stress and leakage heat rise with that voltage. Service life follows the stress, whatever the system is called. Warranty terms are the maker's to interpret for the exact model; an earthed local supply makes both questions moot.
Can I ground the tool by bolting the neutral to the panel bus?
That shorts out the impedance the IT design depends on. First-fault current stops being the 48 mA of the worked example, the insulation monitor sees a standing fault, and its alarm stops meaning anything. It also lets return current share the machine frame, which NEC 250.6 exists to prevent. Feed the tool from a transformer instead.
What should the PE path read on the trailing cable?
Under 1 Ω from the receptacle earth to the machine's main bonding point. A 25 m run of 2.5 mm² copper PE is about 0.22 Ω warm, so a reading near 1 Ω is a connector or a gland bond talking, not the copper. Re-measure after any trailing-cable repair.
Does a 0 V neutral-to-PE reading prove the supply is grounded?
It does not. A 10 MΩ meter draws about 24 µA at 240 V, and that current moves the reading just 0.12 V across a 5 kΩ impedance, so a solid tie and an impedance tie display the same near-zero. The difference shows on the first fault or on the drawing, never on that reading.
Do I keep the insulation monitor after adding the transformer?
Yes. The machine stays IT and the monitor still catches the first fault anywhere, transformer primary included. Keeping the tool's filter on the far side of the isolation also stops its leakage adding to the system capacitance the monitor has to see through, so the alarm stays meaningful.