Powering 24V passive PoE devices from a control panel

Short answer: wire a passive DIN-rail injector straight to the 24VDC bus — a 15 W radio draws 0.63 A, a 1 A fuse covers it, and Cat5e carries it about 75 m at a 19 V input floor. Use an 802.3af/at source with a bus-voltage input and an internal step-up when the endpoint speaks standard PoE. Add the radio's watts to the UPS load and about 1 W of injector heat to the enclosure's heat budget.

NEMA4 Enclosure engineering team · Published November 12, 2026 · 8 min read

Short answer: if the endpoint takes passive PoE at your bus voltage, you need no voltage conversion at all. Put a passive DIN-rail injector on the backplate, feed it from the 24 VDC bus through a 1 A fuse, and the bus becomes the line voltage — a 15 W radio draws 0.63 A. If the endpoint speaks IEEE 802.3af or 802.3at instead, order an industrial injector or switch with a bus-voltage input and an internal step-up stage, or leave a standard-to-passive splitter at the radio. The numbers below follow one example radio, 15 W with a 19 V input floor; swap in your radio's datasheet values where they differ.

Passive or IEEE: the endpoint decides

Read the powered device before you order anything for the panel. Many outdoor radios take passive PoE; the rest follow IEEE 802.3. Passive means the injector puts DC on the cable the moment it is powered, with no handshake and no detection. An IEEE source does the opposite. It probes for the 25 kΩ powered-device signature first, and only then delivers 44 to 57 V. The port budget is 15.4 W for 802.3af (12.95 W at the device) and 30 W for 802.3at (25.5 W at the device).

Power path Source behaviour Line voltage Endpoint must accept What lands on the DIN rail
Passive DC applied as soon as the injector is powered the panel bus, unregulated or held passive input, correct polarity and pins passive injector rated 12-24 VDC input
802.3af signature probe, then power 44-57 V af signature, 12.95 W injector or switch with bus-voltage input and internal step-up
802.3at same probe, bigger budget 44-57 V at, 25.5 W same unit in a 30 W port class
af source + splitter switch answers the signature; splitter converts at the radio 44-57 V to the splitter radio keeps its passive input af source in the panel, splitter at the mast

The two systems stay apart in both directions. An IEEE switch never powers a passive radio: the port probes, finds no signature and stays off, so you get a dark radio on perfect cabling. The reverse mistake costs hardware, because an 802.3af port pushes 48 to 57 V into a radio rated for half that, and that usually kills it.

Industrial passive injectors built for 12-24 VDC input hold the line at the input voltage; simpler ones pass the bus through unregulated, so read the injector sheet for what happens at your input. For the pair assignments behind the standard voltages, the PoE RJ45 pinout reference for 802.3af and 802.3at shows them conductor by conductor. Passive 100 M injectors usually follow pins 4-5 positive and 7-8 negative, so confirm polarity before first power-up.

Wiring the injector to the DC bus

Treat the injector like any other branch device on that bus:

  • Branch protection: a 1 A fuse or a 1.6 A breaker, carrying the 0.63 A load at 63 percent of rating.
  • Wire: 18 AWG is comfortable; the NFPA 79 ampacity table carries it at 6 A, nearly ten times the load.
  • Negative: land it with the panel's 0 V point. If you ground the negative, the injector joins that node, and whether the DC common needs to be grounded walks the choice.
  • Class 2: when the Ethernet run must stay a Class 2 circuit, feed the injector from a listed Class 2 source at the bus voltage. A branch fuse does not convert a 10 A supply into one.
  • Surge: give every run to an outdoor mast an Ethernet surge arrester at the entry, grounded to the panel ground bar on the shortest route you can bend. The cable shield lands on that same bar on the earth side; the grounding and bonding guide lays out the bar.
  • Lockout: lock out the branch and prove it dead before you land the injector terminals.

A DIN-rail outlet carrying the radio's own wall adapter achieves the same result with a listed adapter. It costs panel depth and leaves an unsecured brick, so the injector is the tidy version of the same idea.

How far passive PoE reaches

Cat5e is 24 AWG copper, about 0.084 Ω per metre per conductor. Power runs out on one pair and back on another with the pair's conductors paralleled, so the round trip works out near 8.4 Ω per 100 m of cable. At full power the radio draws the 0.63 A from the introduction, and the drop is straight arithmetic:

Run Loop resistance Drop at 0.63 A Radio sees, from a 24.0 V bus
25 m 2.1 Ω 1.3 V 22.7 V
50 m 4.2 Ω 2.6 V 21.4 V
75 m 6.3 Ω 4.0 V 20.0 V
100 m 8.4 Ω 5.3 V 18.7 V

One correction shortens that table. The radio holds its watts as the input sags, so its current climbs; at the example 19 V floor it draws 15 / 19 = 0.79 A. Run the limit at that current: allowed drop 24 − 19 = 5 V, allowed loop 5 / 0.79 = 6.3 Ω, allowed length 6.3 / 0.084 = 75 m. Plan 75 m for this radio and redo the sum with your radio's floor — a 20 V floor lands near 65 m, and a 30 W passive radio, at 1.58 A near the floor, runs out before 40 m.

This is what IEEE buys you. The same power at 50 V is 0.3 A, dropping 2.5 V across a full 100 m, well inside the 13 V window between 44 and 57 V.

Worked example: one radio on a UPS-backed panel

Take a panel with a supply of 24 V at 5 A, 2.0 A of I/O (48 W) and a 5 W PLC, backed by a DC UPS holding a 9 Ah battery. Add the example radio. Every input here is an example; replace each with your own.

  • Branch: 15 / 24 = 0.63 A on the 1 A fuse. The bus moves from 48 W to 63 W of the supply's 120 W.
  • UPS runtime: 24 V × 9 Ah = 216 Wh; at 85 percent usable depth that is 184 Wh. Before the radio, 184 / 48 = 3.8 h; with it, 184 / 63 = 2.9 h. The radio costs 0.9 h.
  • Heat inside: supply loss 48 / 0.9 − 48 = 5.3 W, PLC 5 W, injector about 1 W; call it 11 W.
  • Indoor box: a 12 x 10 x 6 in 304 wall-mount enclosure has about 0.33 m² of surface. Stainless walls pass about 3.7 W/m²K, so the rise is 11 / (3.7 × 0.33) ≈ 9 K. A 25 C panel room sits the electronics near 34 C, and 30 C pushes 39 C — under the 40 C most DIN-rail gear is rated for.
  • Outdoor box: at 35 C ambient you have 5 K of headroom, so the box needs k·A ≥ 11 / 5 = 2.2 W/K, meaning at least 0.6 m². The 20 x 16 x 6 in 316L wall-mount enclosure gives 0.69 m², a 4.3 K rise and 39 C inside at 35 C — the one to order at the base of a coastal mast.

When the watts grow past what a wall can shed, sizing a sealed enclosure for a PoE switch heat load carries the same method into fans and air conditioners.

Backplate space and depth

Budget two to six DIN modules (35 to 105 mm) for the injector, two to four more for the surge arrester, and a terminal group beside them; the backplate layout guide sets rail and duct spacing. The 12 x 10 x 6 in box in the example leaves 5.91 in [150 mm] of inside depth, so check the injector's projection above the rail against that before you order. For several radios, swap injectors for a DIN-rail PoE switch: DIN rail enclosure for network switches sizes that box, and outdoor enclosure for a PoE switch and UPS covers the battery side.

Entries that keep the enclosure rating

Every cable that pierces the wall is a rating decision. Use a sealing Ethernet gland rated at least IP66 against jets, or an outdoor-rated RJ45 bulkhead, installed to the hole diameter and torque on its sheet. The assembly keeps only its weakest part's rating, so a NEMA 4X box with an IP54 gland is an IP54 box. Send the gland hole sizes with your order and we cut them as the box is built; the cutouts and glands guide lists what belongs on the drawing, and cord grip hole sizes for common fittings maps the rest.

On ratings and listings, three sentences you can quote. NEC 110.28 says an IP code alone will not satisfy a US spec that calls for a NEMA enclosure type, so carry both numbers on the order. Our enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and NEMA itself does not test or certify enclosures. When the finished panel must be listed, UL 508A is the industrial control panel standard, NEC 409.110 puts an enclosure type number on the panel, and a UL listed enclosure is one evaluated to UL 50E — settle that before the box is cut.

For material, 304 stainless covers most outdoor sites; move to 316L within sight of salt water or under brine and washdown, and both grades run through the wall-mount range. Mount the box on the shaded side of the mast, because direct sun adds heat the worked example does not carry.

What to order

Line item Specify Example for one radio
Power path passive DIN-rail injector, 12-24 VDC input class 0.63 A branch
Branch protection 1 A fuse or 1.6 A breaker 63 percent loaded
Surge Ethernet arrester at the entry, bonded to the ground bar one per outdoor run
Cable entry sealing gland or bulkhead, IP66 minimum hole size from its sheet
Enclosure, indoor 12 x 10 x 6 in, 304, manufacturer-rated NEMA 4X / IP66 9 K rise at 11 W
Enclosure, outdoor 35 C 20 x 16 x 6 in, 316L near salt water 4.3 K rise at 11 W
UPS add the radio and injector watts 3.8 h drops to 2.9 h on 184 Wh

Order the passive injector when the radio takes passive power at the bus voltage: one DIN part, 0.63 A, no conversion. Order the 802.3af/at source with the internal step-up when the endpoint follows the standard, and hand its input current — about 1.4 A per 30 W port — to whoever sizes the supply. Both paths end at the same cut-to-order box, delivered in 10 business days counted from your approval of the drawing.

Enclosures in this article

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
12 × 10 × 6 in316L stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 6 in304 stainless20 x 16 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 6 in316L stainless20 x 16 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can I wire a passive 24 V PoE injector straight to the panel's DC bus?

Yes. A passive injector has no IEEE handshake; it feeds the cable from its input terminals through a fuse and magnetics. Industrial units rated 12-24 VDC input hold the line at the bus voltage. The example radio above draws 0.63 A, so a 1 A branch fuse and 18 AWG wire carry it with room to spare.

Do I need a 48 V power supply for an 802.3af switch on a DC panel?

No. Choose an industrial PoE injector or switch with a bus-voltage input and an internal step-up stage; it generates the 44-57 V line itself. A 30 W port at 90 percent efficiency draws 33.3 W, about 1.4 A from the panel bus. Add a separate supply only for a unit whose input rating demands one.

How far can passive PoE reach on Cat5e?

About 75 m for the example radio with its 19 V floor. The loop is near 8.4 Ω per 100 m, and the current climbs to 0.79 A at the floor, so the allowed 5 V drop buys 6.3 Ω, or 75 m. A 20 V floor cuts it to about 65 m, and IEEE systems carry the same power the full 100 m.

What happens when an 802.3af switch meets a passive radio?

The port stays off. The switch probes for the 25 kΩ powered-device signature before delivering power, and a passive radio presents none, so the port never enables — a dark radio on healthy cable. Fix it with a passive injector at the panel, or a standard-to-passive splitter at the radio that answers the signature and feeds the radio its passive input.

How much heat does a PoE injector add inside a sealed enclosure?

About 1 W for a passive unit on one radio. A step-up injector delivering 30 W at 90 percent efficiency dissipates 3.3 W, and a 120 W four-port switch about 13 W, which lifts a 16 x 14 x 6 in stainless box roughly 7 K. Run that rise against your box before you seal it.

What enclosure rating do the radio panel and its cable entries need?

Manufacturer-rated NEMA 4X / IP66 for anything outdoors or hosed down, with glands or bulkheads rated at least IP66, because the assembly keeps only its weakest part's rating. Our boxes are rated NEMA 4X / IP66 by the manufacturer and not UL listed, and NEC 110.28 says an IP code alone will not satisfy a US spec calling for a NEMA type.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job