How to cover an HMI cutout until the mounting hardware arrives

Fit a rigid stainless plate 2 in [50 mm] larger than the open HMI cutout on every side, on a 1/8 in [3 mm] EPDM gasket, with screws no more than 10 in [250 mm] apart; a typical 15 in display opening works out to a 19.0 x 15.8 in [480 x 400 mm] plate with 8 screws. Cardboard and tape restore no ingress or contact protection.

NEMA4 Enclosure engineering team · Published November 11, 2026 · 7 min read

Cover the open cutout with a rigid, gasketed plate screwed to the panel: cut it 2 in [50 mm] larger than the hole on every side, lay a 1/8 in [3 mm] closed-cell EPDM gasket under it, and keep the screws 10 in [250 mm] apart or closer. That holds out washdown water and dust, keeps fingers and dropped tools away from what sits behind the hole, and takes the sharp cutout edge out of hand height until the mounting clamps land, usually 5-10 business days after the reorder. Cardboard and tape do none of those jobs. The worked example below sizes the plate for a typical 15 in display opening of 15.0 x 11.8 in [380 x 300 mm]; measure your own cutout and run your numbers through the same sums.

What the open cutout takes with it

An open display hole suspends four protections at once. The ingress rating left with the intact face. A Type 4X / IP66 enclosure is sealed by its wall, its gasketed door and the devices fitted in it, so the nameplate rating pauses until the face is whole again; what a panel keeps after you cut it and mount devices works through that. Ratings of this kind are manufacturer ratings; not UL listed. Reach protection went with the face too, because drive DC buses, power supply outputs and control terminals now sit a hand's reach behind the hole. The raw edge is a cut hazard that also abrades cable jackets, and the opening collects fasteners, swarf and washdown spray.

Closing an unused opening is a settled problem in this trade. Accessory makers sell reinforced gland plates whose entire job is covering spare entry cutouts on Type 3R and Type 4 enclosures, because an open port is where the rating stops. Whether your hole is in a main panel door or a machine-mounted HMI enclosure, the cover job is identical: rigid plate, gasket, real fasteners, and a date on the label.

What you need

Your bench stock covers all of it:

  • 16 ga [0.060 in / 1.5 mm] 304 or 316L stainless sheet for the plate; on a dry indoor panel with nothing live behind the hole, 6 mm [1/4 in] polycarbonate is the lighter fallback.
  • 1/8 in [3 mm] closed-cell EPDM gasket strip. Elastomer handbook ranges put EPDM at about -50 to 150 C and silicone at about -60 to 200 C, so silicone takes the hot-caustic washdown corner.
  • 10-32 stainless pan-head screws with washers, the standard thread on electrical cover plates (see these 10-32 cover screw thread specs), plus nuts where the panel holes are clearance-drilled.
  • Drill and bits, a deburring tool, and edge trim for the cutout edge.
  • A dated label for the plate, and the work order that will carry the follow-up task.

Closing openings permanently, with glands and blanking plates, is covered in the cutouts, glands and windows guide; this article is the short-term version.

Sizing the cover plate for a 15.0 x 11.8 in [380 x 300 mm] cutout

Inputs. The cutout is 15.0 x 11.8 in [380 x 300 mm], a hypothetical opening sized like a typical 15 in display, so replace both numbers with your tape measurement. The margin is 2 in [50 mm] per side, the rule this article sets so every screw lands on solid panel. The spacing limit is 10 in [250 mm], so the plate cannot bow and open the gasket at mid-span. The gasket is 1/8 in [3 mm] closed-cell EPDM.

Rule. Plate width equals cutout width plus two margins; height works the same way. Screws sit at each corner plus edge midpoints, 10 in apart at most, with every hole centered 1 in [25 mm] in from the plate edge.

Arithmetic.

  • Width: 15.0 + (2 x 2.0) = 19.0 in [480 mm]
  • Height: 11.8 + (2 x 2.0) = 15.8 in [400 mm]
  • Perimeter: 2 x (19.0 + 15.8) = 69.6 in [1.77 m]
  • Screws: 69.6 / 10 = 6.96, so 8 positions give an actual spacing of 69.6 / 8 = 8.7 in [220 mm]

Result. One 19.0 x 15.8 in [480 x 400 mm] plate in 16 ga stainless, 8 screws at 8.7 in [220 mm] spacing.

Decision. Corner screws alone hold only while the perimeter stays at 40 in [1.0 m] or less, because 4 x 10 in is the spacing limit; this plate runs 69.6 in, so it takes the four midpoints. Hold the 2 in margin as well: at 1.5 in [38 mm] the screw holes crowd the cutout and the fastener starts biting the edge instead of solid metal.

Fitting the plate

  1. Lock out and tag the panel, and prove absence of voltage with a tested meter before anyone works at or reaches through the opening.
  2. Measure the cutout at its widest points and check the flat metal around it. A hinge, stiffener or boss behind a planned screw position moves that hole; note the change on the plate sketch.
  3. Deburr the cutout edge and fit edge trim, because whatever the compared cutting methods left behind, the edge at hand height now rubs cable jackets every time the plate comes off.
  4. Mark the plate at cutout size plus 2 in per side, drill the screw holes with centers 1 in from the plate edges, and deburr both faces.
  5. Stick the EPDM gasket to the plate face, centered on the outline, so it bears on solid panel all round — the same sealing logic as an instrument cutout seal.
  6. Fasten the plate with its 8 screws, reusing the display's mounting holes where the pattern falls inside the plate. Any new hole through the wall gets a bonded sealing washer or sealant under the head, the way field-drilled conduit entries keep their rating.
  7. Push the plate hard at the center and at each corner: no visible flex, no shift, no gasket gap.
  8. Label the plate "temporary cover — HMI install pending — date" and log the follow-up task on the work order with an owner.

Checks before you hand the machine back

  • Push test again after an hour, once the gasket has taken its set: plate rigid at center and corners, no rattle.
  • Light test: with the panel locked out, a flashlight inside shows no daylight lines round the plate.
  • Fastener ends sit short of anything live, and nothing new sits within reach of the opening.
  • Function check: start, stop and E-stop run a full cycle with the display absent, and the operator workaround for alarms and setpoints is agreed with production.
  • Records: label on the plate, dated follow-up task, and the plate added to the spares list once the display goes in.

What happens to the cables you already pulled

Cap and insulate each stripped conductor end individually, and park them where they cannot touch metal. De-energize the display's power feed at its protective device and tag it, since the feed has no load at the moment. Coil the Ethernet or serial cable behind the plate, tie it back, and keep it off the cutout edge and separated from power wiring. Cable that is pulled but unterminated still needs mechanical protection and segregation — the same points the rear-wiring protection guide covers.

Then prove the machine runs without the display: operating mode, alarm acknowledgement, any recipe or setpoint entry operators need. If production depends on HMI input, a cover plate hands back a sealed panel, not a working machine, and the release conversation changes.

Mistakes that cost the release

  • Cardboard and tape. Cardboard softens at the first washdown, tape lifts at the edges within a day or two, and a palm pushes the sheet in. OSHA's published interpretation of a temporary cover for an exposed opening describes rigid corrugated plastic rated 600 V, held on by nonconductive magnetic strips: rigid sheet, rated insulation, mechanical retention. Cardboard and tape meet none of the three.
  • Borrowed clamps. Pulling one or two mounting clamps from each identical display elsewhere cuts the clamping force and gasket compression on every donor machine, and the shortfall goes undocumented until those doors leak.
  • Tape as retention. Tape aligns the plate during fitting; screws hold it. An adhesive-held cover leaves with a shove or a warm afternoon.
  • Long screws. A screw through a thin panel can reach terminals on the far side, so size the screw to the stack — see how a protruding screw trades away the Type 4 rating.
  • The unlabeled plate. A cover with no date and no tracked task stays on for months, and the missing display quietly becomes a permanent deviation.

Release the machine when the plate passes the push and light tests, every conductor end is capped, and the follow-up task carries an owner and a date. When the clamps arrive, the plate comes off, the display goes in with its full clamp set, and the plate goes on the shelf as the blanking cover for that opening.

For the permanent install, lay the display opening and its fixing holes out in the cutout designer, which checks spacing on any face and exports the drawing with the quote request. And if the cover ever needs to be fabrication rather than bench stock, the drawing checklist on the custom stainless page is the route: send the measured size and hole pattern, and a quoted plate follows the standard promise, delivered in 10 business days from your approval of the drawing.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
8" HMI enclosure304 stainless8.39 x 9.98 x 3.92 inIP65-type front seal with the display installed, manufacturer rated; not UL listed
15" HMI enclosure304 stainless12.91 x 16.06 x 3.88 inIP65-type front seal with the display installed, manufacturer rated; not UL listed
10.1" HMI enclosure304 stainless8.72 x 12.66 x 3.48 inIP65-type front seal with the display installed, manufacturer rated; not UL listed
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

How long can a temporary cover stay on the panel?

Mechanically, a gasketed stainless plate seals as well on day 60 as on day 1, so the limit is administrative. Log the cover on the work order with an owner and a removal date tied to the clamp reorder, and chase the task weekly. The plate becomes a problem only when nobody owns it; a dated label and a tracked task keep the temporary state from turning into a permanent deviation.

What screw length does the cover plate take?

Add the stack and leave 3-4 engaged threads. For the example plate: 0.060 in [1.5 mm] sheet plus 0.125 in [3 mm] gasket plus a 10 ga [0.135 in] door comes to 0.32 in [8 mm], so a 1/2 in [13 mm] screw leaves about 0.18 in [5 mm] of engagement, roughly 6 threads on a 10-32, with the tip short of anything live. Remeasure with your own door thickness, since a thicker door moves the screw length up.

Does the screwed-on plate give the enclosure its NEMA 4X rating back?

With a gasket bearing on solid panel and screws at 10 in [250 mm] spacing or closer, the plate closes the hole to the same washdown intent as the surrounding door, and the assembly is only ever as good as that joint. An uncovered hole or a taped sheet returns nothing. The full nameplate rating applies again once the display and its gasket are clamped in; ratings are manufacturer ratings, not UL listed.

Where do the missing mounting clamps come from?

From the display maker or its authorized distributor, quoting the exact model and the panel thickness they must clamp. Clamp sets are sized to a panel-thickness and cutout range, so hardware from a different model rarely matches and can leave the gasket under-clamped. Ask for expedited shipment: with the gasketed plate fitted, a 5-10 business-day wait is a releasable machine rather than a closed line.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Configure an HMI housing in 3DRequest a custom quote

NEMA 4X enclosures: sizes for this job · HMI panel cutout dimensions by series

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides