Short answer: run a full rebuild of the HMI application before the next download, and keep the engineering PC's display scaling at 100% (96 DPI). Text that shrinks while its boxes hold size is stale generated runtime code, and editing font properties will not bring it back. The compile that runs during a download stages the generated files for transfer; it is not the full regeneration that shared faceplate types need, which rebuilds every screen and faceplate instance for the selected panel. Work in this order: save a dated copy, set the station to 100%, rebuild the affected device, download, set the panel clock, then measure on the glass. The checks below need a steel rule and the project file, and the worked example shows when the numbers say rebuild.
What the symptoms point to
Read the panel before you open the project. Two measurements separate the causes: the width of a text box and the height of the glyphs inside it. One clock fault mimics a value fault, so the list below sorts that out too.
- Boxes and buttons hold size, only text shrinks — stale generated runtime resources on that panel; run the full rebuild first, because this is the cause in most reported cases.
- Everything scales together, text, boxes and spacing — device selection, screen resolution or the engineering PC's display scaling, not text resources.
- Numeric fields show
###while other text looks normal — value, format or panel-clock trouble; fonts are innocent. - The editor looks right and the panel looks wrong — the download compiled files for transfer and skipped the full regeneration.
- Faceplate content shrinks while loose objects on the same screen hold size — the shared faceplate type regenerated inconsistently; check every instance after the rebuild.
Why text shrinks while the boxes hold size
A faceplate is one shared type, and every instance on every screen draws from the runtime files generated for that device, not from the drawing in the editor. An incremental compile refreshes only what the engineering software flags as changed, and shared types with many instances are where it falls short. The compile shown during a download converts generated files into a transfer format, and practitioners on these platforms have separated it from a manual full rebuild for well over a decade. Case after case carries the same signature: identical font properties in the editor, small glyphs on the panel, full rebuild restores the text. On a four-panel project, each device gets its own generated set, so one rebuild never covers the other three.
The second cause lives on the engineering PC. The software's installation requirements state that it adapts to monitor scaling up to 350%, yet stations set above 100% (96 DPI) have been tied to formatting faults in the generated panel output. Windows scaling multiplies that 96 DPI baseline: at 125%, the editor draws at 96 × 1.25 = 120 DPI, so a 9 px label renders about 11 px while the stored value stays 9. Set the station to 100% before you author or rebuild. Where site policy forces higher scaling, right-click the application, open Properties, choose the Compatibility tab and select Change High DPI settings. The same Windows-side route cures too-small dialog boxes in other packages; the FT View Studio dialog-box fix walks it step by step.
Third comes a device or resolution change: re-target the screen to another panel or resolution and the whole runtime rescales, boxes included. That is why the two measurements above do the sorting. One nearby trap: a download can reset the panel date and time, and numeric fields then show ### until the clock reads correctly. That is a clock fault, the clock fix restores the numbers, and the shrunken text survives it untouched.
How to check each cause
Run the checks in this order. Each one either clears a cause or hands the problem to the next.
- Read the panel date and time. A download can clear it; set it and re-check the numeric fields before anything else.
- Compare one numeric field with the controller value. If
###survives a correct clock, treat it as a value, format or connection problem; the numeric-field hash marks article lists the causes and fixes, and the question-marks-instead-of-data article covers the connection side. - Measure one text box on the glass. A steel rule reads 68 mm [2.7 in] to within a millimetre; compare it with the project baseline.
- Measure the capital height of the same text. Expect about 1.7 mm [0.07 in] for 9 px on the example panel; the next section shows the arithmetic.
- Check an unaffected button or graphic. If it shrank too, the text resources are innocent, and the search moves to device settings and the PC scaling setting.
- Open the project and read the definitions. The faceplate type and every instance should carry the same faceplate version, and the font should read as configured: the family, 9 px, bold. Note what the panel stores on its own side, clock and any values held at the panel rather than in the controller, because a download or power cycle clears them; the HMI setpoints article explains who stores what.
Measuring the shrink: 9 px text on a 10.4 in panel
Inputs. Panel: a 10.4 in SVGA display, 800 × 600 pixels, active area 8.32 in [211 mm] wide; these are the example's assumed values, so take the resolution and active area from your panel's datasheet and repeat the arithmetic. Text: 9 px, bold, a common sans face, the project baseline in this case. Measured after the download: box width 68 mm [2.7 in], capital height 1.2 mm [0.05 in].
Rule. Pixel pitch equals active width divided by horizontal pixels, in millimetres per pixel. Expected capital height equals configured size in pixels, times pitch, times 0.7, because a typical sans face draws capitals at about 70% of its em size.
Arithmetic. Pitch: 211 mm ÷ 800 px = 0.264 mm/px. Expected capital height: 9 px × 0.264 mm/px × 0.7 = 1.66 mm, call it 1.7 mm. Rendered size: 1.2 mm ÷ 1.66 mm = 0.72, so the glyphs draw at about 72% of the configured size. The box reads 68 mm against a 68 mm baseline, 100% of its geometry.
Decision. Geometry intact and text at 72% puts the fault in the generated text resources alone. Use 80% as the working threshold: glyphs below 80% of expected height, with the box at its baseline size, call for the full rebuild before any font edit. Boxes that shrink by the same factor as the text point to device or scaling configuration instead. At 72% with the box at 100%, this case goes straight to the rebuild.
The fix, in order
- Save a dated copy of the project. A rebuild can compound a problem, so keep a rollback you trust.
- Set the engineering PC to 100% display scaling (96 DPI). At 125% the editor draws at 120 DPI; the Compatibility-tab override covers stations locked higher by policy.
- Select the affected HMI device and run the full rebuild of the application. Let it finish; the download's compile only stages files for transfer.
- Download to the panel, then set its date and time. Watch one numeric field return to a real value.
- Repeat per device. A four-panel line means four rebuilds and four downloads, because each panel generates its own runtime set.
- Check the result on the glass. The box should read its baseline 68 mm, the capital height about 1.7 mm, and faceplate text should match a baseline photo taken before the update.
Keeping it fixed on the next download
- Run the full rebuild before every download; treat the download's compile as transfer preparation only.
- Keep the engineering station at 100% (96 DPI) as standard equipment, the way you treat a calibrated tool.
- Save a dated copy before every change set, and rebuild all devices after a firmware or project-version jump.
- On multi-panel projects, rebuild, download and check one device at a time on the glass before moving to the next.
- Write the panel clock, the faceplate version and the affected screens into the download record, so the next engineer separates a clock fault from a resource fault at a glance.
When the hardware is at fault
Small text never points at the housing, so replace hardware only for physical faults: a dim or dead backlight, dead pixel columns, or a touch layer that stays offset after recalibration. When the panel itself is the fault and the replacement is a small touchscreen, the compact HMI enclosure article covers matching a housing to it. Water or fog behind the glass is a different failure again, on the gasket, gland and cutout side, and the HMI window and cutout guide covers that side. Our housings carry a front seal rated with the display installed (an IP65-type seal from the manufacturer; not UL listed), and a seal rating says nothing about what the project renders. If small text survives a full rebuild from a clean project copy on every screen, suspect the source itself: restore the last known-good library copy and rebuild again.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 10.4" HMI enclosure | 304 stainless | 10.2 x 12.44 x 3.6 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 10.1" HMI enclosure | 304 stainless | 8.72 x 12.66 x 3.48 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 15.6" HMI enclosure | 304 stainless | 11.69 x 17.64 x 4.13 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
Questions
Why does the compile shown during a download leave the text small?
That compile stages the generated runtime files for transfer; it is incremental and trusts the resources it already holds. A full rebuild regenerates every screen and faceplate instance for the selected device from the project definitions. On a four-panel line, run it once per panel: each device draws from its own generated set, so rebuilding panel 1 leaves panels 2, 3 and 4 untouched.
Does the engineering PC's display scaling really change the panel?
It can. Windows scaling multiplies the 96 DPI baseline: a station at 125% draws the editor at 120 DPI, so a label configured at 9 px renders about 11 px on the development screen while the stored value stays 9. The engineering software's requirements allow scaling up to 350%, but stations above 100% have been tied to panel formatting faults, so set 100% before you author.
The numbers came back after I set the clock - isn't the clock the whole fix?
The clock fixes only the hash marks. A download can reset the panel date and time, and numeric fields fed by values with a bad timestamp show ### until the clock reads correctly. Glyph height is a separate fault: once the numbers return, measure a capital letter against the worked example. At 1.2 mm where 1.7 mm is expected, the generated text resources still need the full rebuild.
Should I replace the panel or the enclosure to fix the text?
Neither. The fault lives in generated project files, so a fresh panel behind the same housing renders the same small text until the project is rebuilt. Replace hardware only for physical faults: a dead backlight, dead pixels, or a touch layer that stays offset after recalibration. The housing matters only when water or fog shows behind the glass; the front seal is a manufacturer rating with the display installed, not UL listed.





